{"id":3685,"date":"2026-04-13T05:30:45","date_gmt":"2026-04-13T05:30:45","guid":{"rendered":"https:\/\/xbrele.com\/?p=3685"},"modified":"2026-05-25T14:29:00","modified_gmt":"2026-05-25T14:29:00","slug":"relay-trip-logic-map-for-mv-panels-50-51-50n-51n-27-59-86-how-they-inter","status":"publish","type":"post","link":"https:\/\/xbrele.com\/hi\/relay-trip-logic-map-for-mv-panels-50-51-50n-51n-27-59-86-how-they-inter\/","title":{"rendered":"\u090f\u092e\u0935\u0940 \u092a\u0948\u0928\u0932\u094b\u0902 \u0915\u0947 \u0932\u093f\u090f \u0930\u093f\u0932\u0947 \u091f\u094d\u0930\u093f\u092a \u0932\u0949\u091c\u093f\u0915 \u092e\u0948\u092a: 50\/51\/50N\/51N\/27\/59\/86 \u2013 \u092f\u0947 \u0915\u0948\u0938\u0947 \u0907\u0902\u091f\u0930\u0932\u0949\u0915 \u0939\u094b\u0924\u0947 \u0939\u0948\u0902"},"content":{"rendered":"<h2>\u0938\u0902\u0930\u0915\u094d\u0937\u0923\u093e\u0924\u094d\u092e\u0915 \u0930\u093f\u0932\u0947 \u0938\u092e\u0928\u094d\u0935\u092f \u0914\u0930 \u0907\u0902\u091f\u0930\u0932\u0949\u0915\u093f\u0902\u0917 \u092f\u094b\u091c\u0928\u093e\u0913\u0902 \u0915\u0947 \u0932\u093f\u090f \u090f\u0915 \u0935\u094d\u092f\u093e\u092a\u0915 \u0924\u0915\u0928\u0940\u0915\u0940 \u092e\u093e\u0930\u094d\u0917\u0926\u0930\u094d\u0936\u093f\u0915\u093e<\/h2>\n<hr \/>\n<figure class=\"wp-block-image size-large\"><img decoding=\"async\" class=\"wp-image-3681\" src=\"https:\/\/xbrele.com\/wp-content\/uploads\/2026\/04\/relay-trip-logic-map-for-mv-panels-50-51-50n-51n-27-59-86-how-they-inter-01.webp\" alt=\"\u090f\u092e\u0935\u0940 \u092a\u0948\u0928\u0932 \u0938\u0941\u0930\u0915\u094d\u0937\u093e \u0938\u092e\u0928\u094d\u0935\u092f \u0915\u0947 \u0932\u093f\u090f \u0930\u093f\u0932\u0947 \u091f\u094d\u0930\u093f\u092a \u0932\u0949\u091c\u093f\u0915 \u0906\u0930\u0947\u0916\" width=\"1200\" height=\"675\" srcset=\"https:\/\/xbrele.com\/wp-content\/uploads\/2026\/04\/relay-trip-logic-map-for-mv-panels-50-51-50n-51n-27-59-86-how-they-inter-01.webp 1200w, https:\/\/xbrele.com\/wp-content\/uploads\/2026\/04\/relay-trip-logic-map-for-mv-panels-50-51-50n-51n-27-59-86-how-they-inter-01-300x169.webp 300w, https:\/\/xbrele.com\/wp-content\/uploads\/2026\/04\/relay-trip-logic-map-for-mv-panels-50-51-50n-51n-27-59-86-how-they-inter-01-1024x576.webp 1024w, https:\/\/xbrele.com\/wp-content\/uploads\/2026\/04\/relay-trip-logic-map-for-mv-panels-50-51-50n-51n-27-59-86-how-they-inter-01-768x432.webp 768w, https:\/\/xbrele.com\/wp-content\/uploads\/2026\/04\/relay-trip-logic-map-for-mv-panels-50-51-50n-51n-27-59-86-how-they-inter-01-18x10.webp 18w\" sizes=\"(max-width: 1200px) 100vw, 1200px\" \/><br \/>\n<\/figure>\n<h2>\u092a\u0930\u093f\u091a\u092f<\/h2>\n<p>\u092e\u0927\u094d\u092f\u092e \u0935\u094b\u0932\u094d\u091f\u0947\u091c (MV) \u0935\u093f\u0926\u094d\u092f\u0941\u0924 \u0935\u093f\u0924\u0930\u0923 \u092a\u094d\u0930\u0923\u093e\u0932\u093f\u092f\u094b\u0902 \u092e\u0947\u0902, \u0938\u0941\u0930\u0915\u094d\u0937\u093e \u0930\u093f\u0932\u0947 \u0935\u093f\u0926\u094d\u092f\u0941\u0924 \u0926\u094b\u0937\u094b\u0902, \u0909\u092a\u0915\u0930\u0923 \u0915\u094d\u0937\u0924\u093f \u0914\u0930 \u0915\u0930\u094d\u092e\u093f\u092f\u094b\u0902 \u0915\u0947 \u0932\u093f\u090f \u0916\u0924\u0930\u094b\u0902 \u0915\u0947 \u0916\u093f\u0932\u093e\u092b \u0930\u0915\u094d\u0937\u093e \u0915\u0940 \u092e\u0939\u0924\u094d\u0935\u092a\u0942\u0930\u094d\u0923 \u092a\u0939\u0932\u0940 \u092a\u0902\u0915\u094d\u0924\u093f \u0915\u0947 \u0930\u0942\u092a \u092e\u0947\u0902 \u0915\u093e\u0930\u094d\u092f \u0915\u0930\u0924\u0947 \u0939\u0948\u0902\u0964 \u091f\u094d\u0930\u093f\u092a \u0932\u0949\u091c\u093f\u0915 \u092e\u093e\u0928\u091a\u093f\u0924\u094d\u0930\u094b\u0902 \u0915\u0947 \u092e\u093e\u0927\u094d\u092f\u092e \u0938\u0947 \u0907\u0928 \u0930\u093f\u0932\u0947 \u0915\u0947 \u0907\u0902\u091f\u0930\u0932\u0949\u0915 \u0914\u0930 \u0938\u0902\u091a\u093e\u0930 \u0915\u094b \u0938\u092e\u091d\u0928\u093e \u0935\u093f\u0936\u094d\u0935\u0938\u0928\u0940\u092f \u0935\u093f\u0926\u094d\u092f\u0941\u0924 \u092a\u094d\u0930\u0923\u093e\u0932\u093f\u092f\u094b\u0902 \u0915\u0947 \u0921\u093f\u091c\u093e\u0907\u0928, \u0915\u092e\u0940\u0936\u0928\u093f\u0902\u0917 \u0914\u0930 \u0930\u0916\u0930\u0916\u093e\u0935 \u0915\u0947 \u0932\u093f\u090f \u092e\u094c\u0932\u093f\u0915 \u0939\u0948\u0964.<\/p>\n<p>\u092a\u0947\u091f\u094d\u0930\u094b\u0915\u0947\u092e\u093f\u0915\u0932 \u0938\u0902\u092f\u0902\u0924\u094d\u0930\u094b\u0902, \u0921\u0947\u091f\u093e \u0938\u0947\u0902\u091f\u0930\u094b\u0902 \u0914\u0930 \u092f\u0942\u091f\u093f\u0932\u093f\u091f\u0940 \u0938\u092c\u0938\u094d\u091f\u0947\u0936\u0928\u094b\u0902 \u092e\u0947\u0902 \u090f\u092e\u0935\u0940 \u0938\u094d\u0935\u093f\u091a\u0917\u093f\u092f\u0930 \u0915\u092e\u0940\u0936\u0928\u093f\u0902\u0917 \u0915\u0947 \u0905\u092a\u0928\u0947 18 \u0935\u0930\u094d\u0937\u094b\u0902 \u0915\u0947 \u0905\u0928\u0941\u092d\u0935 \u092e\u0947\u0902, \u092e\u0948\u0902\u0928\u0947 \u092a\u094d\u0930\u0924\u094d\u092f\u0915\u094d\u0937 \u0930\u0942\u092a \u0938\u0947 \u0926\u0947\u0916\u093e \u0939\u0948 \u0915\u093f \u0915\u0948\u0938\u0947 \u0916\u0930\u093e\u092c \u0938\u092e\u0928\u094d\u0935\u093f\u0924 \u0930\u093f\u0932\u0947 \u092f\u094b\u091c\u0928\u093e\u090f\u0901 \u0936\u094d\u0930\u0943\u0902\u0916\u0932\u093e\u092c\u0926\u094d\u0927 \u0939\u094b\u0915\u0930 \u0935\u093f\u0928\u093e\u0936\u0915\u093e\u0930\u0940 \u0935\u093f\u092b\u0932\u0924\u093e\u0913\u0902 \u0915\u093e \u0915\u093e\u0930\u0923 \u092c\u0928 \u0938\u0915\u0924\u0940 \u0939\u0948\u0902\u0964 \u0907\u0938\u0915\u0947 \u0935\u093f\u092a\u0930\u0940\u0924, \u0909\u091a\u093f\u0924 \u0930\u0942\u092a \u0938\u0947 \u0921\u093f\u091c\u093c\u093e\u0907\u0928 \u0915\u093f\u090f \u0917\u090f \u091f\u094d\u0930\u093f\u092a \u0932\u0949\u091c\u093f\u0915 \u092e\u093e\u0928\u091a\u093f\u0924\u094d\u0930\u094b\u0902 \u0928\u0947 \u0909\u092a\u0915\u0930\u0923\u094b\u0902 \u092a\u0930 \u0932\u093e\u0916\u094b\u0902 \u0921\u0949\u0932\u0930 \u0915\u0940 \u092c\u091a\u0924 \u0915\u0940 \u0939\u0948 \u0914\u0930, \u0907\u0938\u0938\u0947 \u092d\u0940 \u092e\u0939\u0924\u094d\u0935\u092a\u0942\u0930\u094d\u0923, \u091a\u094b\u091f\u094b\u0902 \u0915\u094b \u0930\u094b\u0915\u093e \u0939\u0948\u0964.<\/p>\n<p>\u092f\u0939 \u0932\u0947\u0916 \u0938\u092c\u0938\u0947 \u0938\u093e\u092e\u093e\u0928\u094d\u092f \u0938\u0941\u0930\u0915\u094d\u0937\u093e \u0930\u093f\u0932\u0947 \u0915\u093e\u0930\u094d\u092f\u094b\u0902\u2014ANSI \u0921\u093f\u0935\u093e\u0907\u0938 \u0928\u0902\u092c\u0930 50, 51, 50N, 51N, 27, 59 \u0914\u0930 86\u2014\u0915\u0940 \u0917\u0939\u0928 \u091c\u093e\u0902\u091a \u092a\u094d\u0930\u0938\u094d\u0924\u0941\u0924 \u0915\u0930\u0924\u093e \u0939\u0948 \u0914\u0930 \u092c\u0924\u093e\u0924\u093e \u0939\u0948 \u0915\u093f \u092f\u0947 \u090f\u092e\u0935\u0940 \u092a\u0948\u0928\u0932 \u0938\u0902\u0930\u091a\u0928\u093e\u0913\u0902 \u092e\u0947\u0902 \u0915\u0948\u0938\u0947 \u0907\u0902\u091f\u0930\u0932\u0949\u0915 \u0939\u094b\u0924\u0947 \u0939\u0948\u0902\u0964 \u091a\u093e\u0939\u0947 \u0906\u092a \u0928\u090f \u0938\u093f\u0938\u094d\u091f\u092e \u0921\u093f\u091c\u093e\u0907\u0928 \u0915\u0930\u0928\u0947 \u0935\u093e\u0932\u0947 \u0938\u0941\u0930\u0915\u094d\u0937\u093e \u0907\u0902\u091c\u0940\u0928\u093f\u092f\u0930 \u0939\u094b\u0902 \u092f\u093e \u092e\u094c\u091c\u0942\u0926\u093e \u0907\u0902\u0938\u094d\u091f\u0949\u0932\u0947\u0936\u0928 \u0915\u0940 \u0938\u092e\u0938\u094d\u092f\u093e \u0928\u093f\u0935\u093e\u0930\u0923 \u0915\u0930\u0928\u0947 \u0935\u093e\u0932\u0947 \u092b\u0940\u0932\u094d\u0921 \u0924\u0915\u0928\u0940\u0936\u093f\u092f\u0928, \u092f\u0939 \u092e\u093e\u0930\u094d\u0917\u0926\u0930\u094d\u0936\u093f\u0915\u093e \u0930\u093f\u0932\u0947 \u091f\u094d\u0930\u093f\u092a \u0932\u0949\u091c\u093f\u0915 \u0938\u092e\u0928\u094d\u0935\u092f \u0915\u094b \u0938\u092e\u091d\u0928\u0947 \u0915\u0947 \u0932\u093f\u090f \u090f\u0915 \u0935\u094d\u092f\u093e\u0935\u0939\u093e\u0930\u093f\u0915 \u0938\u0902\u0926\u0930\u094d\u092d \u0915\u0947 \u0930\u0942\u092a \u092e\u0947\u0902 \u0915\u093e\u092e \u0915\u0930\u0947\u0917\u0940\u0964.<\/p>\n<hr \/>\n<figure class=\"wp-block-image size-large\"><img decoding=\"async\" class=\"wp-image-3682\" src=\"https:\/\/xbrele.com\/wp-content\/uploads\/2026\/04\/relay-trip-logic-map-for-mv-panels-50-51-50n-51n-27-59-86-how-they-inter-02.webp\" alt=\"\u090f\u092e\u0935\u0940 \u092a\u0948\u0928\u0932 \u0938\u0941\u0930\u0915\u094d\u0937\u093e \u0938\u092e\u0928\u094d\u0935\u092f \u0915\u0947 \u0932\u093f\u090f \u0930\u093f\u0932\u0947 \u091f\u094d\u0930\u093f\u092a \u0932\u0949\u091c\u093f\u0915 \u0906\u0930\u0947\u0916\" width=\"1200\" height=\"675\" srcset=\"https:\/\/xbrele.com\/wp-content\/uploads\/2026\/04\/relay-trip-logic-map-for-mv-panels-50-51-50n-51n-27-59-86-how-they-inter-02.webp 1200w, https:\/\/xbrele.com\/wp-content\/uploads\/2026\/04\/relay-trip-logic-map-for-mv-panels-50-51-50n-51n-27-59-86-how-they-inter-02-300x169.webp 300w, https:\/\/xbrele.com\/wp-content\/uploads\/2026\/04\/relay-trip-logic-map-for-mv-panels-50-51-50n-51n-27-59-86-how-they-inter-02-1024x576.webp 1024w, https:\/\/xbrele.com\/wp-content\/uploads\/2026\/04\/relay-trip-logic-map-for-mv-panels-50-51-50n-51n-27-59-86-how-they-inter-02-768x432.webp 768w, https:\/\/xbrele.com\/wp-content\/uploads\/2026\/04\/relay-trip-logic-map-for-mv-panels-50-51-50n-51n-27-59-86-how-they-inter-02-18x10.webp 18w\" sizes=\"(max-width: 1200px) 100vw, 1200px\" \/><br \/>\n<\/figure>\n<h2>\u0905\u0928\u0941\u092d\u093e\u0917 1: ANSI \u0921\u093f\u0935\u093e\u0907\u0938 \u0928\u0902\u092c\u0930\u094b\u0902 \u0914\u0930 \u0909\u0928\u0915\u0947 \u0915\u093e\u0930\u094d\u092f\u094b\u0902 \u0915\u094b \u0938\u092e\u091d\u0928\u093e<\/h2>\n<p>\u0907\u0902\u091f\u0930\u0932\u0949\u0915 \u092f\u094b\u091c\u0928\u093e\u0913\u0902 \u092e\u0947\u0902 \u0909\u0924\u0930\u0928\u0947 \u0938\u0947 \u092a\u0939\u0932\u0947 \u0939\u092e\u0947\u0902 \u092a\u094d\u0930\u0924\u094d\u092f\u0947\u0915 \u0930\u093f\u0932\u0947 \u092b\u093c\u0902\u0915\u094d\u0936\u0928 \u0915\u0940 \u0938\u094d\u092a\u0937\u094d\u091f \u0938\u092e\u091d \u0938\u094d\u0925\u093e\u092a\u093f\u0924 \u0915\u0930\u0928\u0940 \u091a\u093e\u0939\u093f\u090f\u0964 ANSI\/IEEE C37.2 \u092e\u093e\u0928\u0915 \u0910\u0938\u0947 \u0921\u093f\u0935\u093e\u0907\u0938 \u0928\u0902\u092c\u0930\u094b\u0902 \u0915\u094b \u092a\u0930\u093f\u092d\u093e\u0937\u093f\u0924 \u0915\u0930\u0924\u093e \u0939\u0948 \u091c\u094b \u0938\u0941\u0930\u0915\u094d\u0937\u093e \u0907\u0902\u091c\u0940\u0928\u093f\u092f\u0930\u093f\u0902\u0917 \u0915\u0940 \u0938\u093e\u0930\u094d\u0935\u092d\u094c\u092e\u093f\u0915 \u092d\u093e\u0937\u093e \u092c\u0928 \u091a\u0941\u0915\u0947 \u0939\u0948\u0902\u0964.<\/p>\n<h3>\u0905\u0927\u093f-\u0927\u093e\u0930\u093e \u0938\u0902\u0930\u0915\u094d\u0937\u0923 (50\/51)<\/h3>\n<p><strong>\u0921\u093f\u0935\u093e\u0907\u0938 50 (\u0924\u0924\u094d\u0915\u093e\u0932 \u0905\u0924\u093f\u092a\u094d\u0930\u0935\u093e\u0939)<\/strong> \u091c\u092c \u0927\u093e\u0930\u093e \u092a\u0942\u0930\u094d\u0935\u0928\u093f\u0930\u094d\u0927\u093e\u0930\u093f\u0924 \u0938\u0940\u092e\u093e \u0938\u0947 \u0905\u0927\u093f\u0915 \u0939\u094b \u091c\u093e\u0924\u0940 \u0939\u0948, \u0924\u094b \u092f\u0939 \u091c\u093e\u0928\u092c\u0942\u091d\u0915\u0930 \u0938\u092e\u092f \u0935\u093f\u0932\u0902\u092c \u0915\u0947 \u092c\u093f\u0928\u093e \u0938\u0902\u091a\u093e\u0932\u093f\u0924 \u0939\u094b\u0924\u093e \u0939\u0948\u0964 \u091f\u094d\u0930\u093e\u0902\u0938\u092b\u0949\u0930\u094d\u092e\u0930 \u0938\u0902\u0930\u0915\u094d\u0937\u0923 \u0915\u0947 \u0932\u093f\u090f \u0938\u093e\u092e\u093e\u0928\u094d\u092f\u0924\u0903 \u092a\u093f\u0915\u0905\u092a \u0938\u0947\u091f\u093f\u0902\u0917\u094d\u0938 \u092a\u0942\u0930\u094d\u0923-\u092d\u093e\u0930 \u0927\u093e\u0930\u093e \u0915\u0947 6 \u0938\u0947 10 \u0917\u0941\u0928\u093e \u0924\u0915 \u0939\u094b\u0924\u0940 \u0939\u0948\u0902, \u0914\u0930 \u092e\u094b\u091f\u0930 \u0905\u0928\u0941\u092a\u094d\u0930\u092f\u094b\u0917\u094b\u0902 \u0915\u0947 \u0932\u093f\u090f 1.5 \u0938\u0947 2 \u0917\u0941\u0928\u093e \u0924\u0915\u0964 \u0915\u094d\u0937\u0923\u093f\u0915 \u0924\u0924\u094d\u0935 \u0928\u093f\u0915\u091f\u0935\u0930\u094d\u0924\u0940 \u0926\u094b\u0937\u094b\u0902 \u0915\u0947 \u0932\u093f\u090f \u0909\u091a\u094d\u091a-\u0917\u0924\u093f \u0938\u0947 \u0926\u094b\u0937 \u0928\u093f\u0935\u093e\u0930\u0923 \u092a\u094d\u0930\u0926\u093e\u0928 \u0915\u0930\u0924\u093e \u0939\u0948, \u091c\u0939\u093e\u0901 \u0915\u094d\u0937\u0924\u093f \u0915\u0940 \u0938\u0902\u092d\u093e\u0935\u0928\u093e \u0938\u0930\u094d\u0935\u093e\u0927\u093f\u0915 \u0939\u094b\u0924\u0940 \u0939\u0948\u0964.<\/p>\n<p><strong>\u0921\u093f\u0935\u093e\u0907\u0938 51 (\u0938\u092e\u092f \u0905\u0924\u093f\u092a\u094d\u0930\u0935\u093e\u0939)<\/strong> \u092f\u0939 \u090f\u0915 \u092a\u094d\u0930\u0924\u093f\u0932\u094b\u092e \u0938\u092e\u092f-\u0927\u093e\u0930\u093e \u0935\u093f\u0936\u0947\u0937\u0924\u093e \u092a\u0947\u0936 \u0915\u0930\u0924\u093e \u0939\u0948, \u091c\u093f\u0938\u0938\u0947 \u0921\u093e\u0909\u0928\u0938\u094d\u091f\u094d\u0930\u0940\u092e \u0909\u092a\u0915\u0930\u0923 \u0905\u092a\u0938\u094d\u091f\u094d\u0930\u0940\u092e \u0930\u093f\u0932\u0947 \u0915\u0947 \u0938\u0902\u091a\u093e\u0932\u093f\u0924 \u0939\u094b\u0928\u0947 \u0938\u0947 \u092a\u0939\u0932\u0947 \u0926\u094b\u0937\u094b\u0902 \u0915\u094b \u0926\u0942\u0930 \u0915\u0930 \u0938\u0915\u0924\u0947 \u0939\u0948\u0902\u0964 \u092f\u0939 \u0938\u092e\u0928\u094d\u0935\u092f \u092e\u093e\u0928\u0915\u0940\u0915\u0943\u0924 \u0935\u0915\u094d\u0930\u094b\u0902 (IEC: \u0905\u0924\u094d\u092f\u0902\u0924 \u092a\u094d\u0930\u0924\u093f\u0932\u094b\u092e, \u092c\u0939\u0941\u0924 \u092a\u094d\u0930\u0924\u093f\u0932\u094b\u092e, \u092e\u093e\u0928\u0915 \u092a\u094d\u0930\u0924\u093f\u0932\u094b\u092e; IEEE: \u092e\u0927\u094d\u092f\u092e \u092a\u094d\u0930\u0924\u093f\u0932\u094b\u092e, \u092c\u0939\u0941\u0924 \u092a\u094d\u0930\u0924\u093f\u0932\u094b\u092e, \u0905\u0924\u094d\u092f\u0902\u0924 \u092a\u094d\u0930\u0924\u093f\u0932\u094b\u092e) \u0915\u0947 \u092e\u093e\u0927\u094d\u092f\u092e \u0938\u0947 \u092a\u094d\u0930\u093e\u092a\u094d\u0924 \u0915\u093f\u092f\u093e \u091c\u093e\u0924\u093e \u0939\u0948\u0964.<\/p>\n<h3>\u092d\u0942\u092e\u093f \u0926\u094b\u0937 \u0938\u0941\u0930\u0915\u094d\u0937\u093e (50N\/51N)<\/h3>\n<p><strong>\u0921\u093f\u0935\u093e\u0907\u0938 50N (\u0924\u0924\u094d\u0915\u093e\u0932 \u0917\u094d\u0930\u093e\u0909\u0902\u0921 \u0913\u0935\u0930\u0915\u0930\u0902\u091f)<\/strong> \u092f\u0939 \u0905\u0935\u0936\u093f\u0937\u094d\u091f \u0927\u093e\u0930\u093e \u092e\u093e\u092a\u0928 \u0915\u0947 \u092e\u093e\u0927\u094d\u092f\u092e \u0938\u0947 \u0917\u094d\u0930\u093e\u0909\u0902\u0921 \u0926\u094b\u0937\u094b\u0902 \u0915\u093e \u092a\u0924\u093e \u0932\u0917\u093e\u0924\u093e \u0939\u0948\u0964 \u0920\u094b\u0938 \u0930\u0942\u092a \u0938\u0947 \u0917\u094d\u0930\u093e\u0909\u0902\u0921 \u0915\u093f\u090f \u0917\u090f \u0938\u093f\u0938\u094d\u091f\u092e \u092e\u0947\u0902, \u092a\u093f\u0915\u0905\u092a \u0938\u0947\u091f\u093f\u0902\u0917\u094d\u0938 \u0906\u092e\u0924\u094c\u0930 \u092a\u0930 \u092b\u0947\u091c CT \u0930\u0947\u091f\u093f\u0902\u0917 \u0915\u0947 10\u201320% \u0915\u0940 \u0938\u0940\u092e\u093e \u092e\u0947\u0902 \u0939\u094b\u0924\u0940 \u0939\u0948\u0902\u0964 \u092a\u094d\u0930\u0924\u093f\u0930\u094b\u0927-\u0917\u094d\u0930\u093e\u0909\u0902\u0921 \u0915\u093f\u090f \u0917\u090f \u0938\u093f\u0938\u094d\u091f\u092e \u0915\u0947 \u0932\u093f\u090f, \u0938\u0947\u091f\u093f\u0902\u0917\u094d\u0938 \u0915\u094b \u0928\u094d\u092f\u0942\u091f\u094d\u0930\u0932 \u0917\u094d\u0930\u093e\u0909\u0902\u0921\u093f\u0902\u0917 \u0930\u0947\u091c\u093f\u0938\u094d\u091f\u0930 \u0915\u0947 \u0905\u0927\u093f\u0915\u0924\u092e \u0932\u0947-\u0925\u094d\u0930\u0942 \u0915\u0930\u0902\u091f \u0915\u0947 \u0938\u093e\u0925 \u0938\u092e\u0928\u094d\u0935\u093f\u0924 \u0915\u093f\u092f\u093e \u091c\u093e\u0928\u093e \u091a\u093e\u0939\u093f\u090f\u0964.<\/p>\n<p><strong>\u0921\u093f\u0935\u093e\u0907\u0938 51\u090f\u0928 (\u0938\u092e\u092f \u0905\u0924\u093f\u092a\u094d\u0930\u0935\u093e\u0939 \u0917\u094d\u0930\u093e\u0909\u0902\u0921)<\/strong> \u0938\u092e\u092f-\u0938\u092e\u0928\u094d\u0935\u093f\u0924 \u0917\u094d\u0930\u093e\u0909\u0902\u0921 \u092b\u0949\u0932\u094d\u091f \u0938\u0941\u0930\u0915\u094d\u0937\u093e \u092a\u094d\u0930\u0926\u093e\u0928 \u0915\u0930\u0924\u093e \u0939\u0948, \u091c\u094b \u0909\u0928 \u092a\u094d\u0930\u0923\u093e\u0932\u093f\u092f\u094b\u0902 \u092e\u0947\u0902 \u0906\u0935\u0936\u094d\u092f\u0915 \u0939\u0948 \u091c\u0939\u093e\u0901 \u0915\u0908 \u0917\u094d\u0930\u093e\u0909\u0902\u0921 \u092b\u0949\u0932\u094d\u091f \u0909\u092a\u0915\u0930\u0923\u094b\u0902 \u0915\u0947 \u092c\u0940\u091a \u091a\u092f\u0928\u093e\u0924\u094d\u092e\u0915 \u0938\u092e\u0928\u094d\u0935\u092f \u0915\u0940 \u0906\u0935\u0936\u094d\u092f\u0915\u0924\u093e \u0939\u094b\u0924\u0940 \u0939\u0948\u0964.<\/p>\n<h3>\u0935\u094b\u0932\u094d\u091f\u0947\u091c \u0938\u0941\u0930\u0915\u094d\u0937\u093e (27\/59)<\/h3>\n<p><strong>\u0921\u093f\u0935\u093e\u0907\u0938 27 (\u0905\u0902\u0921\u0930\u0935\u094b\u0932\u094d\u091f\u0947\u091c)<\/strong> \u0935\u094b\u0932\u094d\u091f\u0947\u091c \u0917\u093f\u0930\u093e\u0935\u091f \u0914\u0930 \u0906\u092a\u0942\u0930\u094d\u0924\u093f \u0915\u091f\u094c\u0924\u0940 \u0938\u0947 \u0938\u0941\u0930\u0915\u094d\u0937\u093e \u0915\u0930\u0924\u093e \u0939\u0948, \u0906\u092e\u0924\u094c\u0930 \u092a\u0930 \u0928\u093e\u092e\u092e\u093e\u0924\u094d\u0930 \u0935\u094b\u0932\u094d\u091f\u0947\u091c \u0915\u0947 80\u201390% \u0915\u0947 \u092c\u0940\u091a \u0938\u0947\u091f \u0915\u093f\u092f\u093e \u091c\u093e\u0924\u093e \u0939\u0948, \u0914\u0930 \u0905\u0928\u0941\u092a\u094d\u0930\u092f\u094b\u0917 \u0915\u0947 \u0905\u0928\u0941\u0938\u093e\u0930 1\u201310 \u0938\u0947\u0915\u0902\u0921 \u0915\u0940 \u0938\u092e\u092f \u0926\u0947\u0930\u0940 \u0915\u0947 \u0938\u093e\u0925\u0964 \u092f\u0939 \u092b\u093c\u0902\u0915\u094d\u0936\u0928 \u092e\u094b\u091f\u0930 \u0915\u0940 \u0938\u0941\u0930\u0915\u094d\u0937\u093e \u0914\u0930 \u092c\u093f\u0917\u0921\u093c\u0940 \u0939\u0941\u0908 \u092a\u0930\u093f\u0938\u094d\u0925\u093f\u0924\u093f\u092f\u094b\u0902 \u092e\u0947\u0902 \u0938\u094d\u0935\u091a\u093e\u0932\u093f\u0924 \u092a\u0941\u0928\u0930\u093e\u0930\u0902\u092d \u0915\u094b \u0930\u094b\u0915\u0928\u0947 \u0915\u0947 \u0932\u093f\u090f \u0905\u0924\u094d\u092f\u0902\u0924 \u092e\u0939\u0924\u094d\u0935\u092a\u0942\u0930\u094d\u0923 \u0939\u0948\u0964.<\/p>\n<p><strong>\u0921\u093f\u0935\u093e\u0907\u0938 59 (\u0905\u0924\u093f-\u0935\u094b\u0932\u094d\u091f\u0947\u091c)<\/strong> \u092f\u0939 \u0928\u093f\u0930\u0902\u0924\u0930 \u0905\u0927\u093f\u0915 \u0935\u094b\u0932\u094d\u091f\u0947\u091c \u0915\u0940 \u0938\u094d\u0925\u093f\u0924\u093f\u092f\u094b\u0902 \u0938\u0947 \u0938\u0941\u0930\u0915\u094d\u0937\u093e \u0915\u0930\u0924\u093e \u0939\u0948 \u091c\u094b \u0907\u0928\u094d\u0938\u0941\u0932\u0947\u0936\u0928 \u0914\u0930 \u091c\u0941\u0921\u093c\u0947 \u0909\u092a\u0915\u0930\u0923\u094b\u0902 \u0915\u094b \u0928\u0941\u0915\u0938\u093e\u0928 \u092a\u0939\u0941\u0902\u091a\u093e \u0938\u0915\u0924\u0940 \u0939\u0948\u0902\u0964 \u0938\u0947\u091f\u093f\u0902\u0917\u094d\u0938 \u0906\u092e\u0924\u094c\u0930 \u092a\u0930 \u0928\u093e\u092e\u092e\u093e\u0924\u094d\u0930 \u0935\u094b\u0932\u094d\u091f\u0947\u091c \u0915\u0947 110\u2013120% \u0915\u0947 \u092c\u0940\u091a \u0939\u094b\u0924\u0940 \u0939\u0948\u0902\u0964.<\/p>\n<h3>\u0932\u0949\u0915\u0906\u0909\u091f \u0930\u093f\u0932\u0947 (86)<\/h3>\n<p><strong>\u0921\u093f\u0935\u093e\u0907\u0938 86 (\u0932\u0949\u0915\u0906\u0909\u091f \u0930\u093f\u0932\u0947)<\/strong> \u092f\u0939 \u090f\u0915 \u0935\u093f\u0926\u094d\u092f\u0941\u0924-\u0938\u0902\u091a\u093e\u0932\u093f\u0924, \u0939\u093e\u0925 \u0938\u0947 \u0930\u0940\u0938\u0947\u091f \u0939\u094b\u0928\u0947 \u0935\u093e\u0932\u093e \u0909\u092a\u0915\u0930\u0923 \u0939\u0948 \u091c\u094b \u0938\u0930\u094d\u0915\u093f\u091f \u092c\u094d\u0930\u0947\u0915\u0930\u094d\u0938 \u0915\u094b \u0909\u0928\u0915\u0947 \u091f\u094d\u0930\u093f\u092a \u0939\u094b\u0928\u0947 \u0915\u0940 \u0938\u094d\u0925\u093f\u0924\u093f \u092e\u0947\u0902 \u0924\u092c \u0924\u0915 \u092c\u0928\u093e\u090f \u0930\u0916\u0924\u093e \u0939\u0948 \u091c\u092c \u0924\u0915 \u0915\u094b\u0908 \u0911\u092a\u0930\u0947\u091f\u0930 \u092e\u0948\u0928\u094d\u092f\u0941\u0905\u0932 \u0930\u0942\u092a \u0938\u0947 \u0926\u094b\u0937 \u0915\u0940 \u0938\u094d\u0925\u093f\u0924\u093f \u0915\u0940 \u092a\u0941\u0937\u094d\u091f\u093f \u0928\u0939\u0940\u0902 \u0915\u0930 \u0932\u0947\u0924\u093e\u0964 \u092f\u0939 \u0915\u093e\u0930\u094d\u092f \u092a\u0941\u0928\u0903 \u090a\u0930\u094d\u091c\u093e \u092a\u094d\u0930\u0926\u093e\u0928 \u0915\u0930\u0928\u0947 \u0938\u0947 \u092a\u0939\u0932\u0947 \u0926\u094b\u0937\u094b\u0902 \u0915\u0940 \u091c\u093e\u0902\u091a \u0938\u0941\u0928\u093f\u0936\u094d\u091a\u093f\u0924 \u0915\u0930\u0928\u0947 \u0915\u0947 \u0932\u093f\u090f \u092e\u094c\u0932\u093f\u0915 \u0939\u0948\u0964.<\/p>\n<hr \/>\n<figure class=\"wp-block-table\">\n<table class=\"has-fixed-layout\">\n<thead>\n<tr>\n<th>\u090f\u090f\u0928\u090f\u0938\u0906\u0908 \u0921\u093f\u0935\u093e\u0907\u0938<\/th>\n<th>\u0938\u0941\u0930\u0915\u094d\u0937\u093e \u0915\u0940 \u092d\u0942\u092e\u093f\u0915\u093e<\/th>\n<th>\u0906\u092e \u092f\u093e\u0924\u094d\u0930\u093e \u092a\u0925<\/th>\n<th>\u0906\u092f\u094b\u0917\u0928 \u091c\u093e\u0902\u091a<\/th>\n<\/tr>\n<\/thead>\n<tbody>\n<tr>\n<td>50 \/ 51<\/td>\n<td>\u0924\u0924\u094d\u0915\u093e\u0932\u093f\u0915 \u0914\u0930 \u0926\u0940\u0930\u094d\u0918\u0915\u093e\u0932\u0940\u0928 \u0905\u0927\u093f\u092a\u094d\u0930\u0935\u093e\u0939 \u0938\u0902\u0930\u0915\u094d\u0937\u0923<\/td>\n<td>\u0930\u093f\u0932\u0947 \u0906\u0909\u091f\u092a\u0941\u091f \u092c\u094d\u0930\u0947\u0915\u0930 \u091f\u094d\u0930\u093f\u092a \u0915\u0949\u0907\u0932 \u092f\u093e 86 \u0932\u0949\u0915\u0906\u0909\u091f \u0930\u093f\u0932\u0947 \u0915\u094b<\/td>\n<td>\u092a\u093f\u0915\u0905\u092a \u092a\u0930 \u0926\u094d\u0935\u093f\u0924\u0940\u092f\u0915 \u0927\u093e\u0930\u093e \u0907\u0902\u091c\u0947\u0915\u094d\u0936\u0928 \u0914\u0930 \u0938\u092e\u092f-\u0921\u093e\u092f\u0932 \u0938\u0947\u091f\u093f\u0902\u0917\u094d\u0938<\/td>\n<\/tr>\n<tr>\n<td>50N \/ 51N<\/td>\n<td>\u0936\u0947\u0937 \u092f\u093e \u0924\u091f\u0938\u094d\u0925 \u0927\u093e\u0930\u093e \u0915\u093e \u0909\u092a\u092f\u094b\u0917 \u0915\u0930\u0915\u0947 \u0917\u094d\u0930\u093e\u0909\u0902\u0921 \u092b\u0949\u0932\u094d\u091f \u0938\u0941\u0930\u0915\u094d\u0937\u093e<\/td>\n<td>\u0917\u094d\u0930\u093e\u0909\u0902\u0921-\u092b\u0949\u0932\u094d\u091f \u091f\u094d\u0930\u093f\u092a \u092b\u0940\u0921\u0930 \u092c\u094d\u0930\u0947\u0915\u0930 \u0914\u0930 \u0905\u0932\u093e\u0930\u094d\u092e \u0938\u0930\u094d\u0915\u093f\u091f \u092e\u0947\u0902 \u092d\u0947\u091c\u093e \u0917\u092f\u093e\u0964<\/td>\n<td>\u0938\u0940\u091f\u0940 \u0927\u094d\u0930\u0941\u0935\u0940\u092f\u0924\u093e, \u0905\u0935\u0936\u093f\u0937\u094d\u091f \u092f\u094b\u0917, \u0914\u0930 \u090f\u0928\u091c\u0940\u0906\u0930 \u0927\u093e\u0930\u093e \u0938\u0947\u091f\u093f\u0902\u0917 \u0938\u0924\u094d\u092f\u093e\u092a\u0928<\/td>\n<\/tr>\n<tr>\n<td>27 \/ 59<\/td>\n<td>\u0905\u0902\u0921\u0930\u0935\u094b\u0932\u094d\u091f\u0947\u091c \u0914\u0930 \u0913\u0935\u0930\u0935\u094b\u0932\u094d\u091f\u0947\u091c \u0928\u093f\u0917\u0930\u093e\u0928\u0940<\/td>\n<td>\u090f\u092a\u094d\u0932\u093f\u0915\u0947\u0936\u0928 \u0915\u0947 \u0906\u0927\u093e\u0930 \u092a\u0930 \u091f\u094d\u0930\u093f\u092a, \u0905\u0932\u093e\u0930\u094d\u092e \u092f\u093e \u0932\u094b\u0921-\u0936\u0947\u0921\u093f\u0902\u0917 \u0932\u0949\u091c\u093f\u0915<\/td>\n<td>\u0935\u094b\u0932\u094d\u091f\u0947\u091c \u0907\u0902\u091c\u0947\u0915\u094d\u0936\u0928, \u0935\u093f\u0932\u0902\u092c \u0938\u092e\u092f, \u0914\u0930 \u092c\u094d\u0932\u0949\u0915\u093f\u0902\u0917 \u0932\u0949\u091c\u093f\u0915 \u0938\u0924\u094d\u092f\u093e\u092a\u0928<\/td>\n<\/tr>\n<tr>\n<td>86<\/td>\n<td>\u0917\u0902\u092d\u0940\u0930 \u0926\u094b\u0937\u094b\u0902 \u0915\u0947 \u092c\u093e\u0926 \u092e\u0948\u0928\u0941\u0905\u0932-\u0930\u0940\u0938\u0947\u091f \u0932\u0949\u0915\u0906\u0909\u091f<\/td>\n<td>\u0911\u092a\u0930\u0947\u091f\u0930 \u0926\u094d\u0935\u093e\u0930\u093e \u0930\u0940\u0938\u0947\u091f \u0915\u093f\u090f \u091c\u093e\u0928\u0947 \u0924\u0915 \u0938\u0930\u094d\u0915\u093f\u091f \u092c\u0902\u0926 \u0939\u094b\u0928\u0947 \u0938\u0947 \u0930\u094b\u0915\u0924\u093e \u0939\u0948\u0964<\/td>\n<td>\u091f\u094d\u0930\u093f\u092a \u0932\u0948\u091a, \u0932\u0915\u094d\u0937\u094d\u092f \u0938\u0902\u0915\u0947\u0924, \u0915\u094d\u0932\u094b\u091c-\u092c\u094d\u0932\u0949\u0915 \u0938\u0902\u092a\u0930\u094d\u0915, \u0914\u0930 \u0930\u0940\u0938\u0947\u091f \u092a\u0930\u0940\u0915\u094d\u0937\u0923<\/td>\n<\/tr>\n<\/tbody>\n<\/table>\n<\/figure>\n<figure class=\"wp-block-image size-large\"><img decoding=\"async\" class=\"wp-image-3683\" src=\"https:\/\/xbrele.com\/wp-content\/uploads\/2026\/04\/relay-trip-logic-map-for-mv-panels-50-51-50n-51n-27-59-86-how-they-inter-03.webp\" alt=\"\u090f\u092e\u0935\u0940 \u092a\u0948\u0928\u0932 \u0938\u0941\u0930\u0915\u094d\u0937\u093e \u0938\u092e\u0928\u094d\u0935\u092f \u0915\u0947 \u0932\u093f\u090f \u0930\u093f\u0932\u0947 \u091f\u094d\u0930\u093f\u092a \u0932\u0949\u091c\u093f\u0915 \u0906\u0930\u0947\u0916\" width=\"1200\" height=\"675\" srcset=\"https:\/\/xbrele.com\/wp-content\/uploads\/2026\/04\/relay-trip-logic-map-for-mv-panels-50-51-50n-51n-27-59-86-how-they-inter-03.webp 1200w, https:\/\/xbrele.com\/wp-content\/uploads\/2026\/04\/relay-trip-logic-map-for-mv-panels-50-51-50n-51n-27-59-86-how-they-inter-03-300x169.webp 300w, https:\/\/xbrele.com\/wp-content\/uploads\/2026\/04\/relay-trip-logic-map-for-mv-panels-50-51-50n-51n-27-59-86-how-they-inter-03-1024x576.webp 1024w, https:\/\/xbrele.com\/wp-content\/uploads\/2026\/04\/relay-trip-logic-map-for-mv-panels-50-51-50n-51n-27-59-86-how-they-inter-03-768x432.webp 768w, https:\/\/xbrele.com\/wp-content\/uploads\/2026\/04\/relay-trip-logic-map-for-mv-panels-50-51-50n-51n-27-59-86-how-they-inter-03-18x10.webp 18w\" sizes=\"(max-width: 1200px) 100vw, 1200px\" \/><br \/>\n<\/figure>\n<h2>\u0905\u0928\u0941\u092d\u093e\u0917 2: \u090f\u092e\u0935\u0940 \u092a\u0948\u0928\u0932\u094b\u0902 \u092e\u0947\u0902 \u091f\u094d\u0930\u093f\u092a \u0932\u0949\u091c\u093f\u0915 \u0906\u0930\u094d\u0915\u093f\u091f\u0947\u0915\u094d\u091a\u0930<\/h2>\n<p>\u091f\u094d\u0930\u093f\u092a \u0932\u0949\u091c\u093f\u0915 \u092e\u0948\u092a \u092f\u0939 \u092a\u0930\u093f\u092d\u093e\u0937\u093f\u0924 \u0915\u0930\u0924\u093e \u0939\u0948 \u0915\u093f \u0938\u0941\u0930\u0915\u094d\u0937\u093e\u0924\u094d\u092e\u0915 \u0930\u093f\u0932\u0947 \u0906\u0909\u091f\u092a\u0941\u091f \u0938\u0930\u094d\u0915\u093f\u091f \u092c\u094d\u0930\u0947\u0915\u0930 \u091f\u094d\u0930\u093f\u092a \u0915\u0949\u0907\u0932\u094d\u0938, \u0932\u0949\u0915\u0906\u0909\u091f \u0930\u093f\u0932\u0947 \u0914\u0930 \u0938\u0939\u093e\u092f\u0915 \u092a\u094d\u0930\u0923\u093e\u0932\u093f\u092f\u094b\u0902 \u0938\u0947 \u0915\u0948\u0938\u0947 \u091c\u0941\u0921\u093c\u0924\u0947 \u0939\u0948\u0902\u0964 \u0906\u0927\u0941\u0928\u093f\u0915 \u090f\u092e\u0935\u0940 \u092a\u0948\u0928\u0932 \u0924\u0940\u0928 \u092a\u094d\u0930\u093e\u0925\u092e\u093f\u0915 \u091f\u094d\u0930\u093f\u092a \u0906\u0930\u094d\u0915\u093f\u091f\u0947\u0915\u094d\u091a\u0930 \u0915\u093e \u0909\u092a\u092f\u094b\u0917 \u0915\u0930\u0924\u0947 \u0939\u0948\u0902:<\/p>\n<h3>\u092a\u094d\u0930\u0924\u094d\u092f\u0915\u094d\u0937 \u092f\u093e\u0924\u094d\u0930\u093e \u0935\u093f\u0928\u094d\u092f\u093e\u0938<\/h3>\n<p>\u0938\u0930\u0932 \u0905\u0928\u0941\u092a\u094d\u0930\u092f\u094b\u0917\u094b\u0902 \u092e\u0947\u0902, \u092a\u094d\u0930\u0924\u094d\u092f\u0947\u0915 \u0930\u093f\u0932\u0947 \u0915\u0947 \u091f\u094d\u0930\u093f\u092a \u0938\u0902\u092a\u0930\u094d\u0915 \u0938\u0940\u0927\u0947 \u0938\u0930\u094d\u0915\u093f\u091f \u092c\u094d\u0930\u0947\u0915\u0930 \u0915\u0940 \u091f\u094d\u0930\u093f\u092a \u0915\u0949\u0907\u0932 \u0938\u0947 \u091c\u0941\u0921\u093c\u0947 \u0939\u094b\u0924\u0947 \u0939\u0948\u0902\u0964 \u092f\u0926\u094d\u092f\u092a\u093f \u092f\u0939 \u0924\u0930\u0940\u0915\u093e \u0915\u093f\u092b\u093e\u092f\u0924\u0940 \u0939\u0948, \u0907\u0938\u092e\u0947\u0902 \u0926\u094b\u0937 \u0938\u0902\u0915\u0947\u0924 \u0915\u0947 \u090f\u0915\u0940\u0915\u0943\u0924 \u0939\u094b\u0928\u0947 \u0915\u093e \u0932\u093e\u092d \u0928\u0939\u0940\u0902 \u0939\u094b\u0924\u093e \u0914\u0930 \u0938\u094d\u0935\u091a\u093e\u0932\u093f\u0924 \u092a\u0941\u0928\u0903\u092c\u0902\u0926 \u0939\u094b\u0928\u0947 \u0915\u094b \u0930\u094b\u0915\u0928\u0947 \u0915\u0947 \u0932\u093f\u090f \u092a\u094d\u0930\u0924\u094d\u092f\u0947\u0915 \u0930\u093f\u0932\u0947 \u0915\u0947 \u0932\u093f\u090f \u0905\u0932\u0917-\u0905\u0932\u0917 \u0938\u0939\u093e\u092f\u0915 \u0938\u0902\u092a\u0930\u094d\u0915\u094b\u0902 \u0915\u0940 \u0906\u0935\u0936\u094d\u092f\u0915\u0924\u093e \u0939\u094b\u0924\u0940 \u0939\u0948\u0964.<\/p>\n<h3>\u0932\u0949\u0915\u0906\u0909\u091f \u0930\u093f\u0932\u0947 \u0926\u094d\u0935\u093e\u0930\u093e \u092e\u0927\u094d\u092f\u0938\u094d\u0925\u093f\u0924 \u091f\u094d\u0930\u093f\u092a<\/h3>\n<p>\u0905\u0927\u093f\u0915 \u092a\u0930\u093f\u0937\u094d\u0915\u0943\u0924 \u092f\u094b\u091c\u0928\u093e\u090f\u0901 \u0938\u092d\u0940 \u0938\u0941\u0930\u0915\u094d\u0937\u093e \u0930\u093f\u0932\u0947 \u0906\u0909\u091f\u092a\u0941\u091f \u0915\u094b 86 \u0932\u0949\u0915\u0906\u0909\u091f \u0930\u093f\u0932\u0947 \u0915\u0947 \u092e\u093e\u0927\u094d\u092f\u092e \u0938\u0947 \u092d\u0947\u091c\u0924\u0940 \u0939\u0948\u0902\u0964 \u092f\u0939 \u0935\u093f\u0928\u094d\u092f\u093e\u0938 \u0915\u0908 \u0932\u093e\u092d \u092a\u094d\u0930\u0926\u093e\u0928 \u0915\u0930\u0924\u093e \u0939\u0948:<\/p>\n<ul>\n<li>\u091f\u094d\u0930\u093f\u092a \u0915\u0949\u0907\u0932 \u0915\u0940 \u090f\u0915\u0932 \u092c\u093f\u0902\u0926\u0941 \u0928\u093f\u0917\u0930\u093e\u0928\u0940<\/li>\n<li>\u0938\u0902\u092f\u0941\u0915\u094d\u0924 \u0927\u094d\u0935\u091c \u0938\u0902\u0915\u0947\u0924<\/li>\n<li>\u0938\u094d\u0935\u091a\u093e\u0932\u093f\u0924 \u092a\u0941\u0928\u0903\u092c\u0902\u0926 \u0939\u094b\u0928\u0947 \u0915\u093e \u0905\u0902\u0924\u0930\u094d\u0928\u093f\u0939\u093f\u0924 \u0905\u0935\u0930\u094b\u0927<\/li>\n<li>\u0924\u094d\u0930\u0941\u091f\u093f \u0938\u094d\u0935\u0940\u0915\u0943\u0924\u093f \u0915\u0947 \u0932\u093f\u090f \u0938\u094d\u092a\u0937\u094d\u091f \u0911\u092a\u0930\u0947\u091f\u0930 \u0907\u0902\u091f\u0930\u092b\u093c\u0947\u0938<\/li>\n<\/ul>\n<h3>\u092c\u0939\u0941-\u0915\u093e\u0930\u094d\u092f\u093e\u0924\u094d\u092e\u0915 \u0930\u093f\u0932\u0947 \u0906\u0902\u0924\u0930\u093f\u0915 \u0924\u0930\u094d\u0915<\/h3>\n<p>\u0906\u0927\u0941\u0928\u093f\u0915 \u0938\u0902\u0916\u094d\u092f\u093e\u0924\u094d\u092e\u0915 \u0930\u093f\u0932\u0947 \u092a\u094d\u0930\u094b\u0917\u094d\u0930\u093e\u092e\u0947\u092c\u0932 \u0932\u0949\u091c\u093f\u0915 \u0917\u0947\u091f\u094d\u0938 \u0915\u0947 \u092e\u093e\u0927\u094d\u092f\u092e \u0938\u0947 \u0906\u0902\u0924\u0930\u093f\u0915 \u0930\u0942\u092a \u0938\u0947 \u091f\u094d\u0930\u093f\u092a \u0932\u0949\u091c\u093f\u0915 \u0915\u094b \u0932\u093e\u0917\u0942 \u0915\u0930\u0924\u0947 \u0939\u0948\u0902\u0964 \u0930\u093f\u0932\u0947 \u0915\u0947 \u0906\u0909\u091f\u092a\u0941\u091f \u0915\u0949\u0928\u094d\u091f\u0948\u0915\u094d\u091f\u094d\u0938 \u0915\u094b \u0935\u094d\u092f\u0915\u094d\u0924\u093f\u0917\u0924 \u0938\u0941\u0930\u0915\u094d\u0937\u093e \u0924\u0924\u094d\u0935\u094b\u0902 \u092f\u093e \u0938\u0902\u092f\u0941\u0915\u094d\u0924 \u091f\u094d\u0930\u093f\u092a \u0915\u093e\u0930\u094d\u092f\u094b\u0902 \u0915\u093e \u092a\u094d\u0930\u0924\u093f\u0928\u093f\u0927\u093f\u0924\u094d\u0935 \u0915\u0930\u0928\u0947 \u0915\u0947 \u0932\u093f\u090f \u0915\u0949\u0928\u094d\u092b\u093c\u093f\u0917\u0930 \u0915\u093f\u092f\u093e \u091c\u093e \u0938\u0915\u0924\u093e \u0939\u0948\u0964.<\/p>\n<hr \/>\n<figure class=\"wp-block-image size-large\"><img decoding=\"async\" class=\"wp-image-3684\" src=\"https:\/\/xbrele.com\/wp-content\/uploads\/2026\/04\/relay-trip-logic-map-for-mv-panels-50-51-50n-51n-27-59-86-how-they-inter-04.webp\" alt=\"\u090f\u092e\u0935\u0940 \u092a\u0948\u0928\u0932 \u0938\u0941\u0930\u0915\u094d\u0937\u093e \u0938\u092e\u0928\u094d\u0935\u092f \u0915\u0947 \u0932\u093f\u090f \u0930\u093f\u0932\u0947 \u091f\u094d\u0930\u093f\u092a \u0932\u0949\u091c\u093f\u0915 \u0906\u0930\u0947\u0916\" width=\"1200\" height=\"675\" srcset=\"https:\/\/xbrele.com\/wp-content\/uploads\/2026\/04\/relay-trip-logic-map-for-mv-panels-50-51-50n-51n-27-59-86-how-they-inter-04.webp 1200w, https:\/\/xbrele.com\/wp-content\/uploads\/2026\/04\/relay-trip-logic-map-for-mv-panels-50-51-50n-51n-27-59-86-how-they-inter-04-300x169.webp 300w, https:\/\/xbrele.com\/wp-content\/uploads\/2026\/04\/relay-trip-logic-map-for-mv-panels-50-51-50n-51n-27-59-86-how-they-inter-04-1024x576.webp 1024w, https:\/\/xbrele.com\/wp-content\/uploads\/2026\/04\/relay-trip-logic-map-for-mv-panels-50-51-50n-51n-27-59-86-how-they-inter-04-768x432.webp 768w, https:\/\/xbrele.com\/wp-content\/uploads\/2026\/04\/relay-trip-logic-map-for-mv-panels-50-51-50n-51n-27-59-86-how-they-inter-04-18x10.webp 18w\" sizes=\"(max-width: 1200px) 100vw, 1200px\" \/><br \/>\n<\/figure>\n<h2>\u0905\u0928\u0941\u092d\u093e\u0917 3: \u0938\u0941\u0930\u0915\u094d\u0937\u093e \u0915\u093e\u0930\u094d\u092f\u094b\u0902 \u0915\u0947 \u092c\u0940\u091a \u0907\u0902\u091f\u0930\u0932\u0949\u0915 \u092f\u094b\u091c\u0928\u093e\u090f\u0901<\/h2>\n<p>\u0938\u0902\u0930\u0915\u094d\u0937\u0923\u093e\u0924\u094d\u092e\u0915 \u0915\u093e\u0930\u094d\u092f\u094b\u0902 \u0915\u0947 \u092c\u0940\u091a \u0915\u0940 \u092a\u0930\u0938\u094d\u092a\u0930 \u0915\u094d\u0930\u093f\u092f\u093e \u0938\u094d\u0925\u093e\u092a\u093f\u0924 \u0938\u093f\u0926\u094d\u0927\u093e\u0902\u0924\u094b\u0902 \u0915\u093e \u092a\u093e\u0932\u0928 \u0915\u0930\u0924\u0940 \u0939\u0948, \u091c\u094b \u0935\u093f\u0936\u094d\u0935\u0938\u0928\u0940\u092f\u0924\u093e (\u0906\u0935\u0936\u094d\u092f\u0915 \u0939\u094b\u0928\u0947 \u092a\u0930 \u0938\u0902\u091a\u093e\u0932\u0928) \u0914\u0930 \u0938\u0941\u0930\u0915\u094d\u0937\u093e (\u0917\u0932\u0924 \u0930\u0942\u092a \u0938\u0947 \u0928 \u091a\u0932\u0928\u0947) \u0926\u094b\u0928\u094b\u0902 \u0938\u0941\u0928\u093f\u0936\u094d\u091a\u093f\u0924 \u0915\u0930\u0924\u0940 \u0939\u0948\u0964.<\/p>\n<h3>\u0905\u0927\u093f-\u0927\u093e\u0930\u093e \u0914\u0930 \u0917\u094d\u0930\u093e\u0909\u0902\u0921 \u092b\u0949\u0932\u094d\u091f \u0938\u092e\u0928\u094d\u0935\u092f<\/h3>\n<p>50\/51 \u0914\u0930 50N\/51N \u0915\u093e\u0930\u094d\u092f\u094b\u0902 \u0915\u094b \u0938\u092e\u092f \u0914\u0930 \u092a\u0930\u093f\u092e\u093e\u0923 \u092e\u0947\u0902 \u0938\u092e\u0928\u094d\u0935\u092f\u093f\u0924 \u0939\u094b\u0928\u093e \u091a\u093e\u0939\u093f\u090f\u0964 \u090f\u0915 \u0938\u093e\u092e\u093e\u0928\u094d\u092f \u0935\u093f\u0928\u094d\u092f\u093e\u0938 \u092a\u0930 \u0935\u093f\u091a\u093e\u0930 \u0915\u0930\u0947\u0902:<\/p>\n<p>2000A \u090f\u092e\u0935\u0940 \u092b\u0940\u0921\u0930 \u0915\u0947 \u0932\u093f\u090f \u091c\u093f\u0938\u092e\u0947\u0902 2000:5 \u0938\u0940\u091f\u0940 \u0939\u0948\u0902:<br \/>\n\u2013 51 \u092a\u093f\u0915\u0905\u092a: 1.2 \u00d7 FLA = 2400A (6A \u0938\u0947\u0915\u0947\u0902\u0921\u0930\u0940)<br \/>\n\u2013 51 \u091f\u093e\u0907\u092e \u0921\u093e\u092f\u0932: \u092c\u0939\u0941\u0924 \u0909\u0932\u094d\u091f\u0947 \u0935\u0915\u094d\u0930 \u092a\u0930 0.5<br \/>\n\u2013 50 \u092a\u093f\u0915\u0905\u092a: 8 \u00d7 FLA = 16,000A (40A \u0938\u0947\u0915\u0947\u0902\u0921\u0930\u0940)<br \/>\n\u2013 51N \u092a\u093f\u0915\u0905\u092a: 0.5A \u0938\u0947\u0915\u0947\u0902\u0921\u0930\u0940 (200A \u092a\u094d\u0930\u093e\u0907\u092e\u0930\u0940, 10% CT \u0930\u0947\u091f\u093f\u0902\u0917)<br \/>\n\u2013 51N \u091f\u093e\u0907\u092e \u0921\u093e\u092f\u0932: 0.3 \u0905\u0924\u094d\u092f\u0902\u0924 \u0909\u0932\u094d\u091f\u0947 \u0935\u0915\u094d\u0930 \u092a\u0930<br \/>\n\u2013 50N \u092a\u093f\u0915\u0905\u092a: 2A \u0926\u094d\u0935\u093f\u0924\u0940\u092f\u0915 (800A \u092a\u094d\u0930\u093e\u0925\u092e\u093f\u0915)<\/p>\n<p>\u0917\u094d\u0930\u093e\u0909\u0902\u0921 \u092b\u0949\u0932\u094d\u091f \u090f\u0932\u093f\u092e\u0947\u0902\u091f\u094d\u0938 \u0915\u094b \u0905\u0927\u093f\u0915 \u0938\u0902\u0935\u0947\u0926\u0928\u0936\u0940\u0932 \u0930\u0942\u092a \u0938\u0947 \u0938\u0947\u091f \u0915\u093f\u092f\u093e \u091c\u093e\u0924\u093e \u0939\u0948 \u0915\u094d\u092f\u094b\u0902\u0915\u093f \u0917\u094d\u0930\u093e\u0909\u0902\u0921 \u092b\u0949\u0932\u094d\u091f \u0906\u092e\u0924\u094c\u0930 \u092a\u0930 \u092b\u0947\u091c \u092b\u0949\u0932\u094d\u091f \u0915\u0940 \u0924\u0941\u0932\u0928\u093e \u092e\u0947\u0902 \u0915\u092e \u092a\u0930\u093f\u092e\u093e\u0923 \u0915\u0947 \u0939\u094b\u0924\u0947 \u0939\u0948\u0902, \u092b\u093f\u0930 \u092d\u0940 \u0935\u0947 \u0938\u092e\u093e\u0928 \u0930\u0942\u092a \u0938\u0947 \u0916\u0924\u0930\u0928\u093e\u0915 \u0939\u094b\u0924\u0947 \u0939\u0948\u0902\u0964.<\/p>\n<h3>\u0935\u094b\u0932\u094d\u091f\u0947\u091c \u0914\u0930 \u0905\u0924\u093f-\u0927\u093e\u0930\u093e \u0907\u0902\u091f\u0930\u0932\u0949\u0915 \u0932\u0949\u091c\u093f\u0915<\/h3>\n<p>\u0905\u0902\u0921\u0930\u0935\u094b\u0932\u094d\u091f\u0947\u091c (27) \u0914\u0930 \u0913\u0935\u0930\u0935\u094b\u0932\u094d\u091f\u0947\u091c (59) \u0938\u0941\u0930\u0915\u094d\u0937\u093e \u0905\u0915\u094d\u0938\u0930 \u092f\u094b\u091c\u0928\u093e \u0938\u0941\u0930\u0915\u094d\u0937\u093e \u0915\u094b \u092c\u0922\u093c\u093e\u0928\u0947 \u0915\u0947 \u0932\u093f\u090f \u0913\u0935\u0930\u0915\u0930\u0902\u091f \u0915\u093e\u0930\u094d\u092f\u094b\u0902 \u0915\u0947 \u0938\u093e\u0925 \u0907\u0902\u091f\u0930\u0932\u0949\u0915 \u0939\u094b \u091c\u093e\u0924\u0940 \u0939\u0948:<\/p>\n<p><strong>\u0935\u094b\u0932\u094d\u091f\u0947\u091c \u092a\u094d\u0930\u0924\u093f\u092c\u0902\u0927 \u0905\u0924\u093f\u092a\u094d\u0930\u0935\u093e\u0939 (51V)<\/strong> \u0935\u094b\u0932\u094d\u091f\u0947\u091c \u0918\u091f\u0928\u0947 \u092a\u0930 \u092a\u093f\u0915\u0905\u092a \u0925\u094d\u0930\u0947\u0936\u094b\u0932\u094d\u0921 \u0918\u091f\u0924\u093e \u0939\u0948, \u091c\u093f\u0938\u0938\u0947 \u0909\u0928 \u0926\u0942\u0930\u0938\u094d\u0925 \u0926\u094b\u0937\u094b\u0902 \u0915\u0947 \u092a\u094d\u0930\u0924\u093f \u0938\u0902\u0935\u0947\u0926\u0928\u0936\u0940\u0932\u0924\u093e \u092e\u0947\u0902 \u0938\u0941\u0927\u093e\u0930 \u0939\u094b\u0924\u093e \u0939\u0948 \u091c\u0939\u093e\u0901 \u0935\u094b\u0932\u094d\u091f\u0947\u091c \u092e\u0947\u0902 \u0917\u093f\u0930\u093e\u0935\u091f \u0924\u094b \u0905\u0927\u093f\u0915 \u0939\u094b\u0924\u0940 \u0939\u0948 \u0932\u0947\u0915\u093f\u0928 \u0927\u093e\u0930\u093e \u092e\u0947\u0902 \u0935\u0943\u0926\u094d\u0927\u093f \u092e\u093e\u092e\u0942\u0932\u0940 \u0939\u094b\u0924\u0940 \u0939\u0948\u0964.<\/p>\n<p><strong>\u0935\u094b\u0932\u094d\u091f\u0947\u091c-\u0928\u093f\u092f\u0902\u0924\u094d\u0930\u093f\u0924 \u0905\u0924\u093f\u0927\u093e\u0930\u093e<\/strong> \u0913\u0935\u0930\u0915\u0930\u0902\u091f \u090f\u0932\u093f\u092e\u0947\u0902\u091f \u0915\u094b \u0915\u0947\u0935\u0932 \u0924\u092c \u0938\u0915\u094d\u0930\u093f\u092f \u0915\u0930\u0924\u093e \u0939\u0948 \u091c\u092c \u0935\u094b\u0932\u094d\u091f\u0947\u091c \u090f\u0915 \u0925\u094d\u0930\u0947\u0936\u094b\u0932\u094d\u0921 \u0938\u0947 \u0928\u0940\u091a\u0947 \u091a\u0932\u093e \u091c\u093e\u0924\u093e \u0939\u0948, \u091c\u093f\u0938\u0938\u0947 \u091c\u0928\u0930\u0947\u091f\u0930 \u0905\u0928\u0941\u092a\u094d\u0930\u092f\u094b\u0917\u094b\u0902 \u0915\u0947 \u0932\u093f\u090f \u092c\u0948\u0915\u0905\u092a \u0938\u0941\u0930\u0915\u094d\u0937\u093e \u092a\u094d\u0930\u0926\u093e\u0928 \u0939\u094b\u0924\u0940 \u0939\u0948\u0964.<\/p>\n<h3>\u0932\u0949\u0915\u0906\u0909\u091f \u0930\u093f\u0932\u0947 \u090f\u0915\u0940\u0915\u0930\u0923<\/h3>\n<p>86 \u0921\u093f\u0935\u093e\u0907\u0938 \u0938\u092d\u0940 \u0938\u0941\u0930\u0915\u094d\u0937\u093e \u0915\u093e\u0930\u094d\u092f\u094b\u0902 \u0938\u0947 \u0907\u0928\u092a\u0941\u091f \u092a\u094d\u0930\u093e\u092a\u094d\u0924 \u0915\u0930\u0924\u093e \u0939\u0948 \u0914\u0930 \u0928\u093f\u092e\u094d\u0928\u0932\u093f\u0916\u093f\u0924 \u0915\u094b \u0906\u0909\u091f\u092a\u0941\u091f \u092a\u094d\u0930\u0926\u093e\u0928 \u0915\u0930\u0924\u093e \u0939\u0948:<br \/>\n\u2013 \u092a\u094d\u0930\u093e\u0925\u092e\u093f\u0915 \u091f\u094d\u0930\u093f\u092a \u0915\u0949\u0907\u0932 (52a \u092a\u0925)<br \/>\n\u2013 \u092c\u0948\u0915\u0905\u092a \u091f\u094d\u0930\u093f\u092a \u0915\u0949\u0907\u0932 (\u092f\u0926\u093f \u0938\u0941\u0938\u091c\u094d\u091c\u093f\u0924 \u0939\u094b)<br \/>\n\u2013 \u0915\u094d\u0932\u094b\u091c \u0938\u0930\u094d\u0915\u093f\u091f \u092c\u094d\u0932\u0949\u0915\u093f\u0902\u0917 \u0938\u0902\u092a\u0930\u094d\u0915 (52Y)<br \/>\n\u2013 SCADA\/DCS \u0905\u0932\u093e\u0930\u094d\u092e<br \/>\n\u2013 \u0938\u094d\u0925\u093e\u0928\u0940\u092f \u0918\u094b\u0937\u0923\u093e<\/p>\n<hr \/>\n<h2>\u0905\u0928\u0941\u092d\u093e\u0917 4: \u0938\u092e\u092f \u0938\u092e\u0928\u094d\u0935\u092f \u0914\u0930 \u091a\u092f\u0928\u093e\u0924\u094d\u092e\u0915\u0924\u093e \u0938\u093f\u0926\u094d\u0927\u093e\u0902\u0924<\/h2>\n<p>\u091a\u092f\u0928\u093e\u0924\u094d\u092e\u0915 \u0938\u092e\u0928\u094d\u0935\u092f \u092a\u094d\u0930\u093e\u092a\u094d\u0924 \u0915\u0930\u0928\u0947 \u0915\u0947 \u0932\u093f\u090f \u0938\u0941\u0930\u0915\u094d\u0937\u093e \u092a\u094d\u0930\u0923\u093e\u0932\u0940 \u092e\u0947\u0902 \u0938\u092e\u092f-\u0935\u0930\u094d\u0924\u092e\u093e\u0928 \u0935\u093f\u0936\u0947\u0937\u0924\u093e\u0913\u0902 \u0915\u093e \u0935\u094d\u092f\u0935\u0938\u094d\u0925\u093f\u0924 \u0935\u093f\u0936\u094d\u0932\u0947\u0937\u0923 \u0906\u0935\u0936\u094d\u092f\u0915 \u0939\u0948\u0964.<\/p>\n<h3>\u0938\u092e\u0928\u094d\u0935\u092f \u0938\u092e\u092f \u0905\u0902\u0924\u0930\u093e\u0932<\/h3>\n<p>\u0905\u092a\u0938\u094d\u091f\u094d\u0930\u0940\u092e \u0914\u0930 \u0921\u093e\u0909\u0928\u0938\u094d\u091f\u094d\u0930\u0940\u092e \u0909\u092a\u0915\u0930\u0923\u094b\u0902 \u0915\u0947 \u092c\u0940\u091a \u0928\u094d\u092f\u0942\u0928\u0924\u092e \u0938\u092e\u0928\u094d\u0935\u092f \u0938\u092e\u092f \u0905\u0902\u0924\u0930\u093e\u0932 (CTI) \u092e\u0947\u0902 \u0928\u093f\u092e\u094d\u0928\u0932\u093f\u0916\u093f\u0924 \u0915\u094b \u0936\u093e\u092e\u093f\u0932 \u0915\u0930\u0928\u093e \u091a\u093e\u0939\u093f\u090f:<br \/>\n\u2013 \u092c\u094d\u0930\u0947\u0915\u0930 \u0915\u094d\u0932\u093f\u092f\u0930\u093f\u0902\u0917 \u0938\u092e\u092f (\u0906\u092e\u0924\u094c\u0930 \u092a\u0930 \u090f\u092e\u0935\u0940 \u092c\u094d\u0930\u0947\u0915\u0930\u094d\u0938 \u0915\u0947 \u0932\u093f\u090f 3-5 \u091a\u0915\u094d\u0930)<br \/>\n\u2013 \u0930\u093f\u0932\u0947 \u0913\u0935\u0930\u091f\u094d\u0930\u0948\u0935\u0932 (\u0907\u0932\u0947\u0915\u094d\u091f\u094d\u0930\u094b\u092e\u0948\u0915\u0947\u0928\u093f\u0915\u0932 \u0915\u0947 \u0932\u093f\u090f 2-4 \u091a\u0915\u094d\u0930, \u0928\u094d\u092f\u0942\u092e\u0947\u0930\u093f\u0915\u0932 \u0915\u0947 \u0932\u093f\u090f \u0928\u0917\u0923\u094d\u092f)<br \/>\n\u2013 \u0938\u0941\u0930\u0915\u094d\u0937\u093e \u092e\u093e\u0930\u094d\u091c\u093f\u0928 (5-10 \u091a\u0915\u094d\u0930)<\/p>\n<p>\u0909\u0926\u094d\u092f\u094b\u0917 \u0915\u0940 \u092a\u094d\u0930\u0925\u093e \u0932\u0917\u093e\u0924\u093e\u0930 \u0909\u092a\u0915\u0930\u0923\u094b\u0902 \u0915\u0947 \u092c\u0940\u091a 0.2\u20130.4 \u0938\u0947\u0915\u0902\u0921 \u0915\u093e CTI \u0928\u093f\u0930\u094d\u0927\u093e\u0930\u093f\u0924 \u0915\u0930\u0924\u0940 \u0939\u0948\u0964 \u0938\u0942\u0924\u094d\u0930 \u0939\u0948:<\/p>\n<p><strong>CTI = \u092c\u094d\u0930\u0947\u0915\u0930 \u0938\u092e\u092f + \u0930\u093f\u0932\u0947 \u0913\u0935\u0930\u091f\u094d\u0930\u0948\u0935\u0932 + \u0938\u0941\u0930\u0915\u094d\u0937\u093e \u092e\u093e\u0930\u094d\u091c\u093f\u0928<\/strong><\/p>\n<p>\u0906\u0927\u0941\u0928\u093f\u0915 \u0938\u0902\u0916\u094d\u092f\u093e\u0924\u094d\u092e\u0915 \u0930\u093f\u0932\u0947 \u0914\u0930 \u0935\u0948\u0915\u094d\u092f\u0942\u092e \u092c\u094d\u0930\u0947\u0915\u0930 \u0938\u0902\u092f\u094b\u091c\u0928\u094b\u0902 \u0915\u0947 \u0932\u093f\u090f:<br \/>\nCTI = 0.08s + 0.00s + 0.12s = 0.20s \u0928\u094d\u092f\u0942\u0928\u0924\u092e<\/p>\n<h3>\u0924\u0924\u094d\u0915\u093e\u0932 \u0905\u0924\u093f\u092a\u094d\u0930\u0935\u093e\u0939 \u0938\u092e\u0928\u094d\u0935\u092f<\/h3>\n<p>50 \u092b\u093c\u0902\u0915\u094d\u0936\u0928 \u0938\u092e\u0928\u094d\u0935\u092f \u0938\u0902\u092c\u0902\u0927\u0940 \u091a\u0941\u0928\u094c\u0924\u093f\u092f\u093e\u0901 \u092a\u094d\u0930\u0938\u094d\u0924\u0941\u0924 \u0915\u0930\u0924\u093e \u0939\u0948 \u0915\u094d\u092f\u094b\u0902\u0915\u093f \u092f\u0939 \u091c\u093e\u0928\u092c\u0942\u091d\u0915\u0930 \u0938\u092e\u092f \u0935\u093f\u0932\u0902\u092c \u0915\u0947 \u092c\u093f\u0928\u093e \u0938\u0902\u091a\u093e\u0932\u093f\u0924 \u0939\u094b\u0924\u093e \u0939\u0948\u0964 \u0926\u094b \u0926\u0943\u0937\u094d\u091f\u093f\u0915\u094b\u0923 \u091a\u092f\u0928\u093e\u0924\u094d\u092e\u0915\u0924\u093e \u0938\u0941\u0928\u093f\u0936\u094d\u091a\u093f\u0924 \u0915\u0930\u0924\u0947 \u0939\u0948\u0902:<\/p>\n<p><strong>\u091c\u093c\u094b\u0928 \u091a\u092f\u0928\u0936\u0940\u0932 \u0907\u0902\u091f\u0930\u0932\u0949\u0915\u093f\u0902\u0917 (ZSI):<\/strong> \u0921\u093e\u0909\u0928\u0938\u094d\u091f\u094d\u0930\u0940\u092e \u0930\u093f\u0932\u0947 \u0905\u092a\u0928\u0947 \u0915\u094d\u0937\u0947\u0924\u094d\u0930 \u092e\u0947\u0902 \u0926\u094b\u0937 \u0915\u093e \u092a\u0924\u093e \u0932\u0917\u0924\u0947 \u0939\u0940 \u0905\u092a\u0938\u094d\u091f\u094d\u0930\u0940\u092e \u0909\u092a\u0915\u0930\u0923\u094b\u0902 \u0915\u094b \u092c\u094d\u0932\u0949\u0915\u093f\u0902\u0917 \u0938\u0902\u0915\u0947\u0924 \u092d\u0947\u091c\u0924\u0947 \u0939\u0948\u0902\u0964 \u0905\u092a\u0938\u094d\u091f\u094d\u0930\u0940\u092e \u0930\u093f\u0932\u0947 \u090f\u0915 \u091b\u094b\u091f\u0947 \u0905\u0902\u0924\u0930\u093e\u0932 (\u0906\u092e\u0924\u094c\u0930 \u092a\u0930 50\u2013100 \u092e\u093f\u0932\u0940\u0938\u0947\u0915\u0902\u0921) \u0915\u0947 \u0932\u093f\u090f \u0938\u0902\u091a\u093e\u0932\u0928 \u092e\u0947\u0902 \u0926\u0947\u0930\u0940 \u0915\u0930\u0924\u093e \u0939\u0948, \u091c\u092c \u0924\u0915 \u0915\u093f \u0909\u0938\u0947 \u0915\u094b\u0908 \u092c\u094d\u0932\u0949\u0915\u093f\u0902\u0917 \u0938\u0902\u0915\u0947\u0924 \u0928 \u092e\u093f\u0932\u0947, \u091c\u094b \u092c\u0938 \u0926\u094b\u0937 \u0915\u093e \u0938\u0902\u0915\u0947\u0924 \u0926\u0947\u0924\u093e \u0939\u0948\u0964.<\/p>\n<p><strong>\u0924\u0924\u094d\u0915\u093e\u0932 \u092a\u093f\u0915\u0905\u092a \u0938\u092e\u0928\u094d\u0935\u092f:<\/strong> \u0921\u093e\u0909\u0928\u0938\u094d\u091f\u094d\u0930\u0940\u092e \u0921\u093f\u0935\u093e\u0907\u0938 \u0915\u0940 \u0905\u0927\u093f\u0915\u0924\u092e \u092a\u093e\u0930\u093f\u0924 \u0927\u093e\u0930\u093e \u0938\u0947 \u090a\u092a\u0930 \u0905\u092a\u0938\u094d\u091f\u094d\u0930\u0940\u092e 50 \u090f\u0932\u093f\u092e\u0947\u0902\u091f \u0915\u094b \u0938\u0947\u091f \u0915\u0930\u0947\u0902, \u0924\u093e\u0915\u093f \u0915\u0947\u0935\u0932 \u0921\u093e\u0909\u0928\u0938\u094d\u091f\u094d\u0930\u0940\u092e \u0926\u094b\u0937 \u0939\u0940 \u0905\u092a\u0938\u094d\u091f\u094d\u0930\u0940\u092e 50 \u0938\u0902\u091a\u093e\u0932\u0928 \u0915\u093e \u0915\u093e\u0930\u0923 \u092c\u0928\u0947\u0964.<\/p>\n<hr \/>\n<h2>\u0905\u0928\u0941\u092d\u093e\u0917 5: \u0915\u094d\u0937\u0947\u0924\u094d\u0930\u0940\u092f \u0905\u0928\u0941\u092a\u094d\u0930\u092f\u094b\u0917 \u0909\u0926\u093e\u0939\u0930\u0923<\/h2>\n<h3>\u0909\u0926\u093e\u0939\u0930\u0923 1: \u0914\u0926\u094d\u092f\u094b\u0917\u093f\u0915 \u0938\u0902\u092f\u0902\u0924\u094d\u0930 13.8kV \u092b\u0940\u0921\u0930<\/h3>\n<p>\u090f\u0915 \u0935\u093f\u0928\u093f\u0930\u094d\u092e\u093e\u0923 \u0938\u0941\u0935\u093f\u0927\u093e \u0915\u093e 13.8 kV \u092b\u0940\u0921\u0930 3000 kVA \u0915\u0947 \u091f\u094d\u0930\u093e\u0902\u0938\u092b\u0949\u0930\u094d\u092e\u0930 \u0915\u094b \u0906\u092a\u0942\u0930\u094d\u0924\u093f \u0915\u0930\u0924\u093e \u0939\u0948\u0964 \u0938\u0941\u0930\u0915\u094d\u0937\u093e \u092f\u094b\u091c\u0928\u093e \u092e\u0947\u0902 \u0936\u093e\u092e\u093f\u0932 \u0939\u0948\u0902:<\/p>\n<p><strong>\u092a\u094d\u0930\u093e\u0925\u092e\u093f\u0915 \u0938\u0941\u0930\u0915\u094d\u0937\u093e:<\/strong><br \/>\n\u2013 51: \u092a\u093f\u0915\u0905\u092a 125A, \u0935\u0947\u0930\u0940 \u0907\u0928\u094d\u0935\u0930\u094d\u0938, \u091f\u0940\u0921\u0940 3.0<br \/>\n\u2013 50: \u092a\u093f\u0915\u0905\u092a 4000A (2\u00d7 \u091f\u094d\u0930\u093e\u0902\u0938\u092b\u0949\u0930\u094d\u092e\u0930 \u0907\u0928\u0930\u0936)<br \/>\n\u2013 51N: \u092a\u093f\u0915\u0905\u092a 15A, \u092c\u0939\u0941\u0924 \u0909\u0932\u094d\u091f\u093e, \u091f\u0940\u0921\u0940 2.0<br \/>\n\u2013 50N: \u092a\u093f\u0915\u0905\u092a 200A<\/p>\n<p><strong>\u0906\u092a\u0938 \u092e\u0947\u0902 \u091c\u0941\u0921\u093c\u0928\u093e:<\/strong><br \/>\n\u0938\u092d\u0940 \u0924\u0924\u094d\u0935 86T (\u091f\u094d\u0930\u093e\u0902\u0938\u092b\u0949\u0930\u094d\u092e\u0930 \u0932\u0949\u0915\u0906\u0909\u091f) \u0938\u0947 \u0939\u094b\u0915\u0930 \u0917\u0941\u091c\u0930\u0924\u0947 \u0939\u0948\u0902, \u091c\u094b 13.8kV \u092b\u0940\u0921\u0930 \u092c\u094d\u0930\u0947\u0915\u0930 \u0915\u094b \u091f\u094d\u0930\u093f\u092a \u0915\u0930\u0924\u093e \u0939\u0948 \u0914\u0930 480V \u0926\u094d\u0935\u093f\u0924\u0940\u092f\u0915 \u092e\u0941\u0916\u094d\u092f \u0938\u0930\u094d\u0915\u093f\u091f \u0915\u094b \u0905\u0935\u0930\u0941\u0926\u094d\u0927 \u0915\u0930\u0924\u093e \u0939\u0948\u0964 27\u0935\u093e\u0902 \u0924\u0924\u094d\u0935 (85% \u092a\u0930 \u0938\u0947\u091f, 2.0 \u0938\u0947\u0915\u0902\u0921 \u0935\u093f\u0932\u0902\u092c) \u0935\u094b\u0932\u094d\u091f\u0947\u091c \u0917\u093f\u0930\u093e\u0935\u091f \u0915\u0947 \u0926\u094c\u0930\u093e\u0928 \u092e\u094b\u091f\u0930 \u0915\u0947 \u0930\u0941\u0915\u0928\u0947 \u0938\u0947 \u0930\u094b\u0915\u0928\u0947 \u0915\u0947 \u0932\u093f\u090f \u0938\u094d\u0935\u0924\u0902\u0924\u094d\u0930 \u0930\u0942\u092a \u0938\u0947 480V \u0926\u094d\u0935\u093f\u0924\u0940\u092f\u0915 \u092e\u0941\u0916\u094d\u092f \u0938\u0930\u094d\u0915\u093f\u091f \u0915\u094b \u091f\u094d\u0930\u093f\u092a \u0915\u0930\u0924\u093e \u0939\u0948\u0964.<\/p>\n<h3>\u0909\u0926\u093e\u0939\u0930\u0923 2: \u092f\u0942\u091f\u093f\u0932\u093f\u091f\u0940 \u0938\u092c\u0938\u094d\u091f\u0947\u0936\u0928 \u092c\u0938 \u091f\u093e\u0908<\/h3>\n<p>34.5 kV \u0915\u093e \u092c\u0938 \u091f\u093e\u0908 \u092c\u094d\u0930\u0947\u0915\u0930 \u092c\u0938 \u0926\u094b\u0937\u094b\u0902 \u0938\u0947 \u0938\u0941\u0930\u0915\u094d\u0937\u093e \u0915\u0930\u0924\u093e \u0939\u0948 \u0914\u0930 \u092c\u0948\u0915\u0905\u092a \u0938\u0941\u0930\u0915\u094d\u0937\u093e \u092a\u094d\u0930\u0926\u093e\u0928 \u0915\u0930\u0924\u093e \u0939\u0948:<\/p>\n<p><strong>\u091c\u093c\u094b\u0928 \u091a\u092f\u0928\u093f\u0924 \u0907\u0902\u091f\u0930\u0932\u0949\u0915 \u0915\u093e\u0930\u094d\u092f\u093e\u0928\u094d\u0935\u092f\u0928:<\/strong><br \/>\n\u2013 \u092b\u0940\u0921\u0930 \u0930\u093f\u0932\u0947 \u092c\u0938 \u091f\u093e\u0908 \u0930\u093f\u0932\u0947 \u0915\u094b ZSI \u092c\u094d\u0932\u0949\u0915\u093f\u0902\u0917 \u0938\u093f\u0917\u094d\u0928\u0932 \u092d\u0947\u091c\u0924\u0947 \u0939\u0948\u0902\u0964<br \/>\n\u2013 \u092c\u0938 \u091f\u093e\u0908 51: \u092a\u093f\u0915\u0905\u092a 2000A, \u092c\u0939\u0941\u0924 \u0909\u0932\u094d\u091f\u093e, \u091f\u0940\u0921\u0940 5.0<br \/>\n\u2013 \u092c\u0938 \u091f\u093e\u0908 50: \u092a\u093f\u0915\u0905\u092a 8000A, ZSI \u092c\u094d\u0932\u0949\u0915 \u0915\u0947 \u092c\u093f\u0928\u093e 100ms \u0935\u093f\u0932\u0902\u092c\u093f\u0924<br \/>\n\u2013 \u092c\u0938 \u091f\u093e\u0908 50N: \u092a\u093f\u0915\u0905\u092a 400A, ZSI \u092c\u094d\u0932\u0949\u0915 \u0915\u0947 \u092c\u093f\u0928\u093e 100ms \u0915\u0940 \u0926\u0947\u0930\u0940<\/p>\n<p>\u091c\u092c \u092b\u0940\u0921\u0930 \u092e\u0947\u0902 \u0916\u0930\u093e\u092c\u0940 \u0939\u094b\u0924\u0940 \u0939\u0948, \u0924\u094b \u092b\u0940\u0921\u0930 \u0930\u093f\u0932\u0947 \u0916\u0930\u093e\u092c\u0940 \u0926\u0942\u0930 \u0915\u0930\u0928\u0947 \u0915\u0947 \u0932\u093f\u090f \u0938\u0902\u091a\u093e\u0932\u0928 \u0915\u0947 \u0926\u094c\u0930\u093e\u0928 \u090f\u0915 \u092c\u094d\u0932\u0949\u0915\u093f\u0902\u0917 \u0938\u093f\u0917\u094d\u0928\u0932 \u092d\u0947\u091c\u0924\u093e \u0939\u0948\u0964 \u092f\u0926\u093f \u0915\u094b\u0908 \u092c\u094d\u0932\u0949\u0915\u093f\u0902\u0917 \u0938\u093f\u0917\u094d\u0928\u0932 \u092e\u094c\u091c\u0942\u0926 \u0928\u0939\u0940\u0902 \u0939\u0948 (\u092c\u0938 \u0916\u0930\u093e\u092c\u0940), \u0924\u094b \u092c\u0938 \u091f\u093e\u0908 \u0924\u0941\u0930\u0902\u0924 \u091f\u094d\u0930\u093f\u092a \u0939\u094b \u091c\u093e\u0924\u0940 \u0939\u0948\u0964.<\/p>\n<hr \/>\n<h2>\u0905\u0928\u0941\u092d\u093e\u0917 6: \u092a\u0930\u0940\u0915\u094d\u0937\u0923 \u0914\u0930 \u0915\u092e\u0940\u0936\u0928\u093f\u0902\u0917 \u092a\u094d\u0930\u0915\u094d\u0930\u093f\u092f\u093e\u090f\u0901<\/h2>\n<p>\u0909\u091a\u093f\u0924 \u0915\u092e\u0940\u0936\u0928\u093f\u0902\u0917 \u092f\u0939 \u0938\u0924\u094d\u092f\u093e\u092a\u093f\u0924 \u0915\u0930\u0924\u0940 \u0939\u0948 \u0915\u093f \u091f\u094d\u0930\u093f\u092a \u0932\u0949\u091c\u093f\u0915 \u092e\u0948\u092a \u0921\u093f\u091c\u093c\u093e\u0907\u0928 \u0915\u0947 \u0905\u0928\u0941\u0938\u093e\u0930 \u0915\u093e\u0930\u094d\u092f \u0915\u0930\u0924\u093e \u0939\u0948\u0964.<\/p>\n<h3>\u0915\u093e\u0930\u094d\u092f\u093e\u0924\u094d\u092e\u0915 \u092a\u0930\u0940\u0915\u094d\u0937\u0923 \u092a\u094d\u0930\u094b\u091f\u094b\u0915\u0949\u0932<\/h3>\n<ol>\n<li><strong>\u0935\u094d\u092f\u0915\u094d\u0924\u093f\u0917\u0924 \u0924\u0924\u094d\u0935 \u0938\u0924\u094d\u092f\u093e\u092a\u0928:<\/strong> \u092a\u094d\u0930\u0924\u094d\u092f\u0947\u0915 \u0918\u091f\u0915 \u0915\u0947 \u0928\u093f\u0930\u094d\u0927\u093e\u0930\u093f\u0924 \u092a\u093f\u0915\u0905\u092a \u0914\u0930 \u0938\u092e\u092f \u092a\u0930 \u0938\u0939\u0940 \u0922\u0902\u0917 \u0938\u0947 \u0915\u093e\u092e \u0915\u0930\u0928\u0947 \u0915\u0940 \u092a\u0941\u0937\u094d\u091f\u093f \u0915\u0947 \u0932\u093f\u090f \u092a\u0930\u0940\u0915\u094d\u0937\u0923 \u0927\u093e\u0930\u093e\u090f\u0901\/\u0935\u094b\u0932\u094d\u091f\u0947\u091c \u092a\u094d\u0930\u0935\u093e\u0939\u093f\u0924 \u0915\u0930\u0947\u0902\u0964.<\/li>\n<li><strong>\u092f\u093e\u0924\u094d\u0930\u093e \u092a\u0925 \u0938\u0924\u094d\u092f\u093e\u092a\u0928:<\/strong> \u092a\u094d\u0930\u0924\u094d\u092f\u0947\u0915 \u0930\u093f\u0932\u0947 \u0906\u0909\u091f\u092a\u0941\u091f \u0915\u094b \u0932\u0949\u091c\u093f\u0915 \u0938\u0947 \u092c\u094d\u0930\u0947\u0915\u0930 \u091f\u094d\u0930\u093f\u092a \u0915\u0949\u0907\u0932 \u0924\u0915 \u091f\u094d\u0930\u0947\u0938 \u0915\u0930\u0947\u0902, \u0928\u093f\u0930\u0902\u0924\u0930\u0924\u093e \u0914\u0930 \u0938\u0939\u0940 \u0938\u0902\u091a\u093e\u0932\u0928 \u0915\u0940 \u092a\u0941\u0937\u094d\u091f\u093f \u0915\u0930\u0947\u0902\u0964.<\/li>\n<li><strong>\u0907\u0902\u091f\u0930\u0932\u0949\u0915 \u092a\u0930\u0940\u0915\u094d\u0937\u0923:<\/strong> ZSI \u092c\u094d\u0932\u0949\u0915\u093f\u0902\u0917, \u0935\u094b\u0932\u094d\u091f\u0947\u091c \u092a\u094d\u0930\u0924\u093f\u092c\u0902\u0927 \u0915\u093e\u0930\u094d\u092f\u094b\u0902 \u0914\u0930 \u0932\u0949\u0915\u0906\u0909\u091f \u0930\u093f\u0932\u0947 \u0938\u0902\u091a\u093e\u0932\u0928 \u0915\u0940 \u092a\u0941\u0937\u094d\u091f\u093f \u0915\u0930\u0928\u0947 \u0915\u0947 \u0932\u093f\u090f \u0926\u094b\u0937 \u0938\u094d\u0925\u093f\u0924\u093f\u092f\u094b\u0902 \u0915\u093e \u0905\u0928\u0941\u0915\u0930\u0923 \u0915\u0930\u0947\u0902\u0964.<\/li>\n<li><strong>\u0932\u0915\u094d\u0937\u094d\u092f \u0930\u0940\u0938\u0947\u091f \u0938\u0924\u094d\u092f\u093e\u092a\u0928:<\/strong> \u092a\u0941\u0937\u094d\u091f\u093f \u0915\u0930\u0947\u0902 \u0915\u093f 86 \u0921\u093f\u0935\u093e\u0907\u0938 \u0915\u094b \u092e\u0948\u0928\u0941\u0905\u0932 \u0930\u0940\u0938\u0947\u091f \u0915\u0940 \u0906\u0935\u0936\u094d\u092f\u0915\u0924\u093e \u0939\u0948 \u0914\u0930 \u092f\u0939 \u092c\u094d\u0930\u0947\u0915\u0930 \u092c\u0902\u0926 \u0939\u094b\u0928\u0947 \u0915\u094b \u0920\u0940\u0915 \u0938\u0947 \u0930\u094b\u0915\u0924\u093e \u0939\u0948\u0964.<\/li>\n<\/ol>\n<h3>\u0938\u093e\u092e\u093e\u0928\u094d\u092f \u0915\u092e\u0940\u0936\u0928\u093f\u0902\u0917 \u0938\u092e\u0938\u094d\u092f\u093e\u090f\u0901<\/h3>\n<p>\u092e\u0948\u0926\u093e\u0928\u0940 \u0905\u0928\u0941\u092d\u0935 \u0938\u0947, \u0938\u092c\u0938\u0947 \u0906\u092e \u0938\u092e\u0938\u094d\u092f\u093e\u0913\u0902 \u092e\u0947\u0902 \u0936\u093e\u092e\u093f\u0932 \u0939\u0948\u0902:<\/p>\n<ul>\n<li><strong>\u0938\u0940\u091f\u0940 \u0927\u094d\u0930\u0941\u0935\u0940\u092f\u0924\u093e \u0924\u094d\u0930\u0941\u091f\u093f\u092f\u093e\u0901:<\/strong> \u092f\u0926\u093f \u0905\u0935\u0936\u093f\u0937\u094d\u091f \u0927\u093e\u0930\u093e \u0915\u0940 \u0917\u0923\u0928\u093e \u092e\u0947\u0902 \u0927\u094d\u0930\u0941\u0935\u0940\u092f\u0924\u093e \u0917\u0932\u0924 \u0939\u094b, \u0924\u094b \u0917\u094d\u0930\u093e\u0909\u0902\u0921 \u092b\u0949\u0932\u094d\u091f \u0924\u0924\u094d\u0935 \u0920\u0940\u0915 \u0938\u0947 \u0915\u093e\u092e \u0928\u0939\u0940\u0902 \u0915\u0930 \u0938\u0915\u0924\u0947\u0964<\/li>\n<li><strong>\u0924\u093e\u0930\u094b\u0902 \u0915\u0940 \u0924\u094d\u0930\u0941\u091f\u093f\u092f\u093e\u0901:<\/strong> \u091f\u094d\u0930\u093f\u092a \u0938\u0930\u094d\u0915\u093f\u091f \u092a\u0930\u094d\u092f\u0935\u0947\u0915\u094d\u0937\u0923 \u091f\u094d\u0930\u093f\u092a \u092a\u0925\u094b\u0902 \u092e\u0947\u0902 \u0916\u0941\u0932\u0947 \u0938\u0930\u094d\u0915\u093f\u091f\u094b\u0902 \u0915\u094b \u091b\u093f\u092a\u093e \u0938\u0915\u0924\u093e \u0939\u0948\u0964<\/li>\n<li><strong>\u0938\u0947\u091f\u093f\u0902\u0917 \u0924\u094d\u0930\u0941\u091f\u093f\u092f\u093e\u0901:<\/strong> \u0917\u0932\u0924 \u0907\u0915\u093e\u0907\u092f\u094b\u0902 (\u092a\u094d\u0930\u093e\u0925\u092e\u093f\u0915 \u092c\u0928\u093e\u092e \u0926\u094d\u0935\u093f\u0924\u0940\u092f\u0915) \u092e\u0947\u0902 \u0926\u0930\u094d\u091c \u092a\u093f\u0915\u0905\u092a \u092e\u093e\u0928<\/li>\n<li><strong>\u0924\u093e\u0930\u094d\u0915\u093f\u0915 \u0924\u094d\u0930\u0941\u091f\u093f\u092f\u093e\u0901:<\/strong> \u0917\u0932\u0924 \u0924\u0930\u0940\u0915\u0947 \u0938\u0947 \u0915\u0949\u0928\u094d\u092b\u093c\u093f\u0917\u0930 \u0915\u093f\u090f \u0917\u090f \u092a\u094d\u0930\u094b\u0917\u094d\u0930\u093e\u092e\u0947\u092c\u0932 \u0932\u0949\u091c\u093f\u0915 \u0917\u0947\u091f\u094d\u0938, \u091c\u093f\u0938\u0938\u0947 \u091d\u0942\u0920\u0940 \u091f\u094d\u0930\u093f\u092a \u0939\u094b\u0924\u0940 \u0939\u0948 \u092f\u093e \u091f\u094d\u0930\u093f\u092a \u0928\u0939\u0940\u0902 \u0939\u094b\u0924\u0940\u0964<\/li>\n<\/ul>\n<hr \/>\n<h2>\u0905\u0928\u0941\u092d\u093e\u0917 7: \u0906\u0927\u0941\u0928\u093f\u0915 \u0938\u0902\u0916\u094d\u092f\u093e\u0924\u094d\u092e\u0915 \u0930\u093f\u0932\u0947 \u090f\u0915\u0940\u0915\u0930\u0923<\/h2>\n<p>\u0938\u092e\u0915\u093e\u0932\u0940\u0928 \u0938\u0941\u0930\u0915\u094d\u0937\u093e \u092f\u094b\u091c\u0928\u093e\u090f\u0901 \u0909\u0928\u094d\u0928\u0924 \u0915\u093e\u0930\u094d\u092f\u0915\u094d\u0937\u092e\u0924\u093e \u0915\u0947 \u0932\u093f\u090f \u0938\u0902\u0916\u094d\u092f\u093e\u0924\u094d\u092e\u0915 \u0930\u093f\u0932\u0947 \u0915\u094d\u0937\u092e\u0924\u093e\u0913\u0902 \u0915\u093e \u0932\u093e\u092d \u0909\u0920\u093e\u0924\u0940 \u0939\u0948\u0902\u0964.<\/p>\n<h3>\u0906\u0902\u0924\u0930\u093f\u0915 \u0924\u0930\u094d\u0915 \u092a\u094d\u0930\u094b\u0917\u094d\u0930\u093e\u092e\u093f\u0902\u0917<\/h3>\n<p>\u0906\u0927\u0941\u0928\u093f\u0915 \u0930\u093f\u0932\u0947 \u0915\u0938\u094d\u091f\u092e \u0932\u0949\u091c\u093f\u0915 \u0938\u092e\u0940\u0915\u0930\u0923 \u092c\u0928\u093e\u0928\u0947 \u0915\u0940 \u0905\u0928\u0941\u092e\u0924\u093f \u0926\u0947\u0924\u0947 \u0939\u0948\u0902:<\/p>\n<pre><code>TRIP = (50 \u092f\u093e 51 \u092f\u093e 50N \u092f\u093e 51N \u092f\u093e 27 \u092f\u093e 59) \u0914\u0930 \u092c\u094d\u0932\u0949\u0915 \u0928\u0939\u0940\u0902\n<\/code><\/pre>\n<p>\u091c\u0939\u093e\u0901 BLOCK \u0930\u0916\u0930\u0916\u093e\u0935 \u092e\u094b\u0921 \u0907\u0928\u092a\u0941\u091f \u092f\u093e \u092c\u093e\u0939\u0930\u0940 \u0905\u0928\u0941\u092e\u094b\u0926\u0928\u0915\u093e\u0930\u0940 \u0939\u094b \u0938\u0915\u0924\u093e \u0939\u0948\u0964.<\/p>\n<h3>\u0938\u0902\u091a\u093e\u0930-\u0906\u0927\u093e\u0930\u093f\u0924 \u092f\u094b\u091c\u0928\u093e\u090f\u0901<\/h3>\n<p>IEC 61850 GOOSE \u0938\u0902\u0926\u0947\u0936\u0928 \u0939\u093e\u0930\u094d\u0921\u0935\u093e\u092f\u0930 \u0915\u0928\u0947\u0915\u094d\u0936\u0928 \u0915\u0947 \u092c\u093f\u0928\u093e \u0909\u091a\u094d\u091a-\u0917\u0924\u093f \u0907\u0902\u091f\u0930\u0932\u0949\u0915\u093f\u0902\u0917 \u0938\u0915\u094d\u0937\u092e \u0915\u0930\u0924\u093e \u0939\u0948\u0964   \u0906\u092e \u0905\u0928\u0941\u092a\u094d\u0930\u092f\u094b\u0917\u094b\u0902 \u092e\u0947\u0902 \u0936\u093e\u092e\u093f\u0932 \u0939\u0948\u0902:<\/p>\n<ul>\n<li>\u092b\u0940\u0921\u0930 \u0930\u093f\u0932\u0947 \u0915\u0947 \u092c\u0940\u091a \u0938\u0902\u091a\u093e\u0930 \u0915\u0930\u0928\u0947 \u0935\u093e\u0932\u0940 \u092c\u0938 \u0921\u093f\u092b\u0930\u0947\u0902\u0936\u093f\u092f\u0932 \u092f\u094b\u091c\u0928\u093e\u090f\u0901<\/li>\n<li>\u0930\u093f\u092e\u094b\u091f \u092c\u094d\u0930\u0947\u0915\u0930 \u092c\u0948\u0915\u0905\u092a \u0915\u0947 \u0932\u093f\u090f \u091f\u094d\u0930\u093e\u0902\u0938\u092b\u0930 \u091f\u094d\u0930\u093f\u092a<\/li>\n<li>\u092c\u0947\u0939\u0924\u0930 \u0935\u093f\u0936\u094d\u0935\u0938\u0928\u0940\u092f\u0924\u093e \u0915\u0947 \u0932\u093f\u090f \u0938\u094d\u0935\u091a\u093e\u0932\u093f\u0924 \u0938\u0947\u0915\u094d\u0936\u0928\u0932\u093e\u0907\u091c\u093f\u0902\u0917<\/li>\n<\/ul>\n<h3>\u0918\u091f\u0928\u093e \u0905\u092d\u093f\u0932\u0947\u0916\u0928 \u0914\u0930 \u0935\u093f\u0936\u094d\u0932\u0947\u0937\u0923<\/h3>\n<p>\u0938\u0902\u0916\u094d\u092f\u093e\u0924\u094d\u092e\u0915 \u0930\u093f\u0932\u0947 \u0926\u094b\u0937\u094b\u0924\u094d\u0924\u0930 \u0935\u093f\u0936\u094d\u0932\u0947\u0937\u0923 \u0915\u0947 \u0932\u093f\u090f \u092e\u0939\u0924\u094d\u0935\u092a\u0942\u0930\u094d\u0923 \u0911\u0938\u094d\u0938\u093f\u0932\u094b\u0917\u094d\u0930\u093e\u092b\u0940 \u0914\u0930 \u0918\u091f\u0928\u093e \u0930\u093f\u0915\u0949\u0930\u094d\u0921\u094d\u0938 \u0915\u094b \u0915\u0948\u092a\u094d\u091a\u0930 \u0915\u0930\u0924\u0947 \u0939\u0948\u0902\u0964 \u092f\u0939 \u0921\u0947\u091f\u093e \u091f\u094d\u0930\u093f\u092a \u0932\u0949\u091c\u093f\u0915 \u0915\u0947 \u0938\u0902\u091a\u093e\u0932\u0928 \u0915\u094b \u0938\u0924\u094d\u092f\u093e\u092a\u093f\u0924 \u0915\u0930\u0924\u093e \u0939\u0948 \u0914\u0930 \u0915\u093f\u0938\u0940 \u092d\u0940 \u0938\u092e\u0928\u094d\u0935\u092f \u0935\u093f\u092b\u0932\u0924\u093e\u0913\u0902 \u0915\u0940 \u092a\u0939\u091a\u093e\u0928 \u0915\u0930\u0924\u093e \u0939\u0948\u0964.<\/p>\n<hr \/>\n<h2>\u0927\u093e\u0930\u093e 8: \u0930\u0916\u0930\u0916\u093e\u0935 \u0914\u0930 \u0906\u0935\u0927\u093f\u0915 \u092a\u0930\u0940\u0915\u094d\u0937\u0923 \u0906\u0935\u0936\u094d\u092f\u0915\u0924\u093e\u090f\u0901<\/h2>\n<p>\u0930\u093f\u0932\u0947 \u092a\u094d\u0930\u0923\u093e\u0932\u093f\u092f\u094b\u0902 \u0915\u094b \u0909\u0928\u0915\u0940 \u0938\u0947\u0935\u093e \u0905\u0935\u0927\u093f \u092d\u0930 \u0935\u093f\u0936\u094d\u0935\u0938\u0928\u0940\u092f\u0924\u093e \u0938\u0941\u0928\u093f\u0936\u094d\u091a\u093f\u0924 \u0915\u0930\u0928\u0947 \u0915\u0947 \u0932\u093f\u090f \u0928\u093f\u0930\u0902\u0924\u0930 \u0930\u0916\u0930\u0916\u093e\u0935 \u0915\u0940 \u0906\u0935\u0936\u094d\u092f\u0915\u0924\u093e \u0939\u094b\u0924\u0940 \u0939\u0948\u0964.<\/p>\n<h3>\u0905\u0928\u0941\u0936\u0902\u0938\u093f\u0924 \u092a\u0930\u0940\u0915\u094d\u0937\u0923 \u0905\u0902\u0924\u0930\u093e\u0932<\/h3>\n<p>NFPA 70B \u0914\u0930 \u0909\u0926\u094d\u092f\u094b\u0917 \u0915\u0940 \u092a\u094d\u0930\u0925\u093e \u0915\u0947 \u0906\u0927\u093e\u0930 \u092a\u0930:<\/p>\n<ul>\n<li><strong>\u0907\u0932\u0947\u0915\u094d\u091f\u094d\u0930\u094b\u092e\u0948\u0915\u0947\u0928\u093f\u0915\u0932 \u0930\u093f\u0932\u0947:<\/strong> \u0935\u093e\u0930\u094d\u0937\u093f\u0915 \u092a\u0930\u0940\u0915\u094d\u0937\u0923, \u0938\u092b\u093e\u0908 \u0914\u0930 \u0915\u0948\u0932\u093f\u092c\u094d\u0930\u0947\u0936\u0928<\/li>\n<li><strong>\u0920\u094b\u0938-\u0905\u0935\u0938\u094d\u0925\u093e \u0930\u093f\u0932\u0947:<\/strong> \u0926\u094d\u0935\u093f\u0935\u093e\u0930\u094d\u0937\u093f\u0915 \u0915\u093e\u0930\u094d\u092f\u093e\u0924\u094d\u092e\u0915 \u092a\u0930\u0940\u0915\u094d\u0937\u0923<\/li>\n<li><strong>\u0938\u0902\u0916\u094d\u092f\u093e\u0924\u094d\u092e\u0915 \u0930\u093f\u0932\u0947:<\/strong> \u0938\u094d\u0935-\u0928\u093f\u0917\u0930\u093e\u0928\u0940 \u0938\u0924\u094d\u092f\u093e\u092a\u0928 \u0915\u0947 \u0932\u093f\u090f \u092a\u0930\u0940\u0915\u094d\u0937\u0923\u094b\u0902 \u0915\u094b 3-5 \u0935\u0930\u094d\u0937 \u0915\u0947 \u0905\u0902\u0924\u0930\u093e\u0932 \u0924\u0915 \u0915\u092e \u0915\u0930 \u0926\u0947\u0924\u0940 \u0939\u0948\u0964<\/li>\n<\/ul>\n<h3>\u0926\u0938\u094d\u0924\u093e\u0935\u0947\u091c\u093c\u0940\u0915\u0930\u0923 \u0906\u0935\u0936\u094d\u092f\u0915\u0924\u093e\u090f\u0901<\/h3>\n<p>\u0938\u091f\u0940\u0915 \u0930\u093f\u0915\u0949\u0930\u094d\u0921 \u092c\u0928\u093e\u090f \u0930\u0916\u0947\u0902, \u091c\u093f\u0928\u092e\u0947\u0902 \u0936\u093e\u092e\u093f\u0932 \u0939\u0948\u0902:<br \/>\n\u2013 \u092e\u0942\u0932 \u0930\u093f\u0932\u0947 \u0938\u0947\u091f\u093f\u0902\u0917\u094d\u0938 \u0914\u0930 \u0938\u092e\u0928\u094d\u0935\u092f \u0905\u0927\u094d\u092f\u092f\u0928<br \/>\n\u2013 \u090f\u091c\u093c-\u092c\u093f\u0932\u094d\u091f \u0935\u093e\u092f\u0930\u093f\u0902\u0917 \u0921\u093e\u092f\u0917\u094d\u0930\u093e\u092e<br \/>\n\u2013 \u092a\u0930\u0940\u0915\u094d\u0937\u0923 \u092a\u0930\u093f\u0923\u093e\u092e \u0914\u0930 \u092a\u094d\u0930\u0935\u0943\u0924\u094d\u0924\u093f \u0938\u0902\u092c\u0902\u0927\u0940 \u0921\u0947\u091f\u093e<br \/>\n\u2013 \u0938\u0902\u0916\u094d\u092f\u093e\u0924\u094d\u092e\u0915 \u0930\u093f\u0932\u0947 \u0915\u0947 \u0932\u093f\u090f \u092b\u0930\u094d\u092e\u0935\u0947\u092f\u0930 \u0938\u0902\u0936\u094b\u0927\u0928 \u0907\u0924\u093f\u0939\u093e\u0938<br \/>\n\u2013 \u0915\u093f\u0938\u0940 \u092d\u0940 \u0938\u0902\u091a\u093e\u0932\u0928 \u0915\u0947 \u0932\u093f\u090f \u0918\u091f\u0928\u093e \u0930\u093f\u0915\u0949\u0930\u094d\u0921 \u0935\u093f\u0936\u094d\u0932\u0947\u0937\u0923<\/p>\n<hr \/>\n<h2>\u0905\u0915\u094d\u0938\u0930 \u092a\u0942\u091b\u0947 \u091c\u093e\u0928\u0947 \u0935\u093e\u0932\u0947 \u092a\u094d\u0930\u0936\u094d\u0928<\/h2>\n<h3>\u092a\u094d\u0930\u0936\u094d\u0928 1: \u091c\u092c \u0926\u094b\u0928\u094b\u0902 50 \u0914\u0930 51 \u092b\u0902\u0915\u094d\u0936\u0928 \u0913\u0935\u0930\u0915\u0930\u0902\u091f \u0915\u093e \u092a\u0924\u093e \u0932\u0917\u093e\u0924\u0947 \u0939\u0948\u0902, \u0924\u094b \u0939\u092e\u0947\u0902 \u0926\u094b\u0928\u094b\u0902 \u0915\u0940 \u0906\u0935\u0936\u094d\u092f\u0915\u0924\u093e \u0915\u094d\u092f\u094b\u0902 \u0939\u0948?<\/h3>\n<p>50 (\u0924\u0924\u094d\u0915\u093e\u0932) \u0914\u0930 51 (\u0938\u092e\u092f-\u0905\u0924\u093f\u0915\u094d\u0930\u092e\u0923) \u0915\u093e\u0930\u094d\u092f \u092a\u0942\u0930\u0915 \u092d\u0942\u092e\u093f\u0915\u093e\u090f\u0901 \u0928\u093f\u092d\u093e\u0924\u0947 \u0939\u0948\u0902\u0964 51 \u0924\u0924\u094d\u0935 \u0938\u092e\u092f \u0935\u093f\u0932\u0902\u092c\u094b\u0902 \u0915\u0947 \u0938\u093e\u0925 \u0938\u092e\u0928\u094d\u0935\u093f\u0924 \u0938\u0941\u0930\u0915\u094d\u0937\u093e \u092a\u094d\u0930\u0926\u093e\u0928 \u0915\u0930\u0924\u093e \u0939\u0948, \u091c\u093f\u0938\u0938\u0947 \u0921\u093e\u0909\u0928\u0938\u094d\u091f\u094d\u0930\u0940\u092e \u0909\u092a\u0915\u0930\u0923 \u092a\u0939\u0932\u0947 \u0926\u094b\u0937\u094b\u0902 \u0915\u094b \u0926\u0942\u0930 \u0915\u0930 \u0938\u0915\u0947\u0902 \u0914\u0930 \u091a\u092f\u0928\u0936\u0940\u0932\u0924\u093e \u092c\u0928\u0940 \u0930\u0939\u0947\u0964 50 \u0924\u0924\u094d\u0935 \u0930\u093f\u0932\u0947 \u0938\u094d\u0925\u093e\u0928 \u0915\u0947 \u0928\u093f\u0915\u091f \u0917\u0902\u092d\u0940\u0930 \u0926\u094b\u0937\u094b\u0902 \u0915\u0947 \u0932\u093f\u090f \u0909\u091a\u094d\u091a-\u0917\u0924\u093f \u0938\u0941\u0930\u0915\u094d\u0937\u093e \u092a\u094d\u0930\u0926\u093e\u0928 \u0915\u0930\u0924\u093e \u0939\u0948, \u091c\u0939\u093e\u0901 \u0915\u094d\u0937\u0924\u093f \u0915\u0940 \u0938\u0902\u092d\u093e\u0935\u0928\u093e \u0938\u0930\u094d\u0935\u093e\u0927\u093f\u0915 \u0939\u094b\u0924\u0940 \u0939\u0948 \u0914\u0930 \u0921\u093e\u0909\u0928\u0938\u094d\u091f\u094d\u0930\u0940\u092e \u0909\u092a\u0915\u0930\u0923\u094b\u0902 \u0915\u0947 \u0938\u093e\u0925 \u0938\u092e\u0928\u094d\u0935\u092f \u0938\u0902\u092d\u0935 \u092f\u093e \u0906\u0935\u0936\u094d\u092f\u0915 \u0928\u0939\u0940\u0902 \u0939\u094b\u0924\u093e\u0964 \u092e\u093f\u0932\u0915\u0930 \u092f\u0947 \u092a\u0942\u0930\u094d\u0923 \u0915\u0935\u0930\u0947\u091c \u092a\u094d\u0930\u0926\u093e\u0928 \u0915\u0930\u0924\u0947 \u0939\u0948\u0902: \u0926\u0942\u0930\u0938\u094d\u0925 \u0926\u094b\u0937\u094b\u0902 \u0915\u0947 \u0932\u093f\u090f \u091a\u092f\u0928\u0936\u0940\u0932 \u0938\u0902\u091a\u093e\u0932\u0928 \u0914\u0930 \u0928\u093f\u0915\u091f \u0926\u094b\u0937\u094b\u0902 \u0915\u0947 \u0932\u093f\u090f \u0924\u094d\u0935\u0930\u093f\u0924 \u0938\u0902\u091a\u093e\u0932\u0928\u0964.<\/p>\n<h3>\u092a\u094d\u0930\u0936\u094d\u0928 2: \u092e\u0948\u0902 \u0915\u0948\u0938\u0947 \u0928\u093f\u0930\u094d\u0927\u093e\u0930\u093f\u0924 \u0915\u0930\u0942\u0901 \u0915\u093f \u092e\u0941\u091d\u0947 86 \u0932\u0949\u0915\u0906\u0909\u091f \u0930\u093f\u0932\u0947 \u0915\u093e \u0909\u092a\u092f\u094b\u0917 \u0915\u0930\u0928\u093e \u091a\u093e\u0939\u093f\u090f \u092f\u093e \u0938\u0941\u0930\u0915\u094d\u0937\u093e \u0930\u093f\u0932\u0947 \u0915\u0947 \u0938\u0902\u092a\u0930\u094d\u0915\u094b\u0902 \u0938\u0947 \u0938\u0940\u0927\u0947 \u091f\u094d\u0930\u093f\u092a \u0915\u0930\u0928\u093e \u091a\u093e\u0939\u093f\u090f?<\/h3>\n<p>\u091c\u092c \u0907\u0928\u092e\u0947\u0902 \u0938\u0947 \u0915\u094b\u0908 \u092d\u0940 \u0938\u094d\u0925\u093f\u0924\u093f \u0932\u093e\u0917\u0942 \u0939\u094b, \u0924\u094b 86 \u0932\u0949\u0915\u0906\u0909\u091f \u0930\u093f\u0932\u0947 \u0915\u093e \u0909\u092a\u092f\u094b\u0917 \u0915\u0930\u0947\u0902: (1) \u090f\u0915 \u0939\u0940 \u0909\u092a\u0915\u0930\u0923 \u0915\u0940 \u0938\u0941\u0930\u0915\u094d\u0937\u093e \u0915\u0908 \u0938\u0941\u0930\u0915\u094d\u0937\u093e \u0909\u092a\u0915\u0930\u0923 \u0915\u0930\u0924\u0947 \u0939\u0948\u0902 \u0914\u0930 \u0926\u094b\u0937 \u0938\u0902\u0915\u0947\u0924 \u0915\u093e \u0938\u092e\u0947\u0915\u093f\u0924 \u0938\u0902\u0915\u0947\u0924 \u0935\u093e\u0902\u091b\u093f\u0924 \u0939\u0948, (2) \u0926\u094b\u0937 \u091c\u093e\u0902\u091a \u092a\u0942\u0930\u0940 \u0939\u094b\u0928\u0947 \u0924\u0915 \u0938\u094d\u0935\u091a\u093e\u0932\u093f\u0924 \u092a\u0941\u0928\u0903\u092c\u0902\u0926 \u0915\u0930\u0928\u093e \u0905\u0935\u0930\u0941\u0926\u094d\u0927 \u0915\u093f\u092f\u093e \u091c\u093e\u0928\u093e \u091a\u093e\u0939\u093f\u090f, (3) \u0938\u0941\u0930\u0915\u094d\u0937\u093e \u092f\u094b\u091c\u0928\u093e \u0915\u094b \u0926\u094b\u0937 \u0938\u094d\u0935\u0940\u0915\u0943\u0924\u093f \u0915\u0947 \u0932\u093f\u090f \u090f\u0915 \u0938\u094d\u092a\u0937\u094d\u091f \u0911\u092a\u0930\u0947\u091f\u0930 \u0907\u0902\u091f\u0930\u092b\u093c\u0947\u0938 \u0915\u0940 \u0906\u0935\u0936\u094d\u092f\u0915\u0924\u093e \u0939\u0948, \u092f\u093e (4) \u0928\u093f\u092f\u093e\u092e\u0915 \u0906\u0935\u0936\u094d\u092f\u0915\u0924\u093e\u090f\u0902 \u092e\u0948\u0928\u0941\u0905\u0932 \u0930\u0940\u0938\u0947\u091f \u0915\u093e\u0930\u094d\u092f\u0915\u094d\u0937\u092e\u0924\u093e \u0915\u093e \u0905\u0928\u093f\u0935\u093e\u0930\u094d\u092f \u0915\u0930\u0924\u0940 \u0939\u0948\u0902\u0964 \u0921\u093e\u092f\u0930\u0947\u0915\u094d\u091f \u091f\u094d\u0930\u093f\u092a\u093f\u0902\u0917 \u0938\u0930\u0932, \u0917\u0948\u0930-\u092e\u0939\u0924\u094d\u0935\u092a\u0942\u0930\u094d\u0923 \u0905\u0928\u0941\u092a\u094d\u0930\u092f\u094b\u0917\u094b\u0902 \u0915\u0947 \u0932\u093f\u090f \u0909\u092a\u092f\u0941\u0915\u094d\u0924 \u0939\u0948 \u091c\u0939\u093e\u0901 \u0938\u094d\u0935\u091a\u093e\u0932\u093f\u0924 \u092a\u0941\u0928\u0903\u092c\u0902\u0926 \u0915\u0930\u0928\u093e \u0938\u094d\u0935\u0940\u0915\u093e\u0930\u094d\u092f \u0939\u0948 \u0914\u0930 \u0938\u094d\u0925\u093e\u092a\u0928\u093e \u0932\u093e\u0917\u0924 \u090f\u0915 \u092a\u094d\u0930\u093e\u0925\u092e\u093f\u0915 \u091a\u093f\u0902\u0924\u093e \u0915\u093e \u0935\u093f\u0937\u092f \u0939\u0948\u0964.<\/p>\n<h3>Q3: \u092e\u0941\u091d\u0947 \u0930\u093f\u0932\u0947 \u0935\u0915\u094d\u0930\u094b\u0902 \u0915\u0947 \u092c\u0940\u091a \u0915\u094c\u0928 \u0938\u093e \u0938\u092e\u0928\u094d\u0935\u092f \u0938\u092e\u092f \u0905\u0902\u0924\u0930\u093e\u0932 (CTI) \u0909\u092a\u092f\u094b\u0917 \u0915\u0930\u0928\u093e \u091a\u093e\u0939\u093f\u090f?<\/h3>\n<p>\u0909\u092a\u092f\u0941\u0915\u094d\u0924 CTI \u0928\u093f\u092f\u094b\u091c\u093f\u0924 \u0930\u093f\u0932\u0947 \u0914\u0930 \u092c\u094d\u0930\u0947\u0915\u0930 \u0924\u0915\u0928\u0940\u0915\u094b\u0902 \u092a\u0930 \u0928\u093f\u0930\u094d\u092d\u0930 \u0915\u0930\u0924\u093e \u0939\u0948\u0964 \u0906\u0927\u0941\u0928\u093f\u0915 \u0938\u0902\u0916\u094d\u092f\u093e\u0924\u094d\u092e\u0915 \u0930\u093f\u0932\u0947 \u0914\u0930 \u0935\u0948\u0915\u094d\u092f\u0942\u092e \u092c\u094d\u0930\u0947\u0915\u0930\u094b\u0902 \u0915\u0947 \u0932\u093f\u090f, \u0906\u092e\u0924\u094c\u0930 \u092a\u0930 0.20\u20130.25 \u0938\u0947\u0915\u0902\u0921 \u092a\u0930\u094d\u092f\u093e\u092a\u094d\u0924 \u0939\u094b\u0924\u093e \u0939\u0948\u0964 \u091c\u092c \u0907\u0932\u0947\u0915\u094d\u091f\u094d\u0930\u094b\u092e\u0948\u0915\u0947\u0928\u093f\u0915\u0932 \u0930\u093f\u0932\u0947 \u0936\u093e\u092e\u093f\u0932 \u0939\u094b\u0902, \u0924\u094b \u0930\u093f\u0932\u0947 \u0915\u0947 \u0913\u0935\u0930\u091f\u094d\u0930\u0948\u0935\u0932 \u0915\u094b \u0927\u094d\u092f\u093e\u0928 \u092e\u0947\u0902 \u0930\u0916\u0924\u0947 \u0939\u0941\u090f 0.30\u20130.40 \u0938\u0947\u0915\u0902\u0921 \u0915\u093e \u0909\u092a\u092f\u094b\u0917 \u0915\u0930\u0947\u0902\u0964 \u0926\u094b\u0928\u094b\u0902 \u0924\u0915\u0928\u0940\u0915\u094b\u0902 \u0935\u093e\u0932\u0947 \u0936\u094d\u0930\u0943\u0902\u0916\u0932\u093e \u0938\u092e\u0928\u094d\u0935\u092f \u0905\u0927\u094d\u092f\u092f\u0928\u094b\u0902 \u0915\u0947 \u0932\u093f\u090f, \u092c\u0921\u093c\u093e \u092e\u093e\u0928 \u0909\u092a\u092f\u094b\u0917 \u0915\u0930\u0947\u0902\u0964 \u0939\u092e\u0947\u0936\u093e \u0915\u0908 \u0935\u0930\u094d\u0924\u092e\u093e\u0928 \u0938\u094d\u0924\u0930\u094b\u0902 \u092a\u0930 CTI \u0915\u0940 \u092a\u0930\u094d\u092f\u093e\u092a\u094d\u0924\u0924\u093e \u0938\u0924\u094d\u092f\u093e\u092a\u093f\u0924 \u0915\u0930\u0947\u0902, \u0935\u093f\u0936\u0947\u0937 \u0930\u0942\u092a \u0938\u0947 \u0905\u0927\u093f\u0915\u0924\u092e \u0926\u094b\u0937 \u0927\u093e\u0930\u093e \u092a\u0930 \u091c\u0939\u093e\u0901 \u0935\u0915\u094d\u0930 \u092e\u093f\u0932 \u0938\u0915\u0924\u0947 \u0939\u0948\u0902\u0964.<\/p>\n<h3>Q4: \u0915\u094d\u092f\u093e \u091c\u093c\u094b\u0928 \u0938\u0947\u0932\u0947\u0915\u094d\u091f\u093f\u0935 \u0907\u0902\u091f\u0930\u0932\u0949\u0915\u093f\u0902\u0917 (ZSI) \u0909\u091a\u093f\u0924 \u0938\u092e\u092f \u0938\u092e\u0928\u094d\u0935\u092f \u0915\u0940 \u091c\u0917\u0939 \u0932\u0947 \u0938\u0915\u0924\u093e \u0939\u0948?<\/h3>\n<p>\u0928\u0939\u0940\u0902\u0964 ZSI \u0938\u092e\u092f \u0938\u092e\u0928\u094d\u0935\u092f \u0915\u094b \u092c\u0922\u093c\u093e\u0924\u093e \u0939\u0948, \u0932\u0947\u0915\u093f\u0928 \u0907\u0938\u0947 \u092a\u094d\u0930\u0924\u093f\u0938\u094d\u0925\u093e\u092a\u093f\u0924 \u0928\u0939\u0940\u0902 \u0915\u0930\u0924\u093e\u0964 \u092f\u094b\u091c\u0928\u093e \u0915\u094b \u091a\u092f\u0928\u0936\u0940\u0932\u0924\u093e \u092c\u0928\u093e\u090f \u0930\u0916\u0928\u0940 \u091a\u093e\u0939\u093f\u090f, \u092d\u0932\u0947 \u0939\u0940 ZSI \u0938\u0902\u091a\u093e\u0930 \u0935\u093f\u092b\u0932 \u0939\u094b \u091c\u093e\u090f\u0964 ZSI \u0915\u094b \u090f\u0915 \u092a\u094d\u0930\u0926\u0930\u094d\u0936\u0928 \u0938\u0902\u0935\u0930\u094d\u0927\u0928 \u0915\u0947 \u0930\u0942\u092a \u092e\u0947\u0902 \u092e\u093e\u0928\u0947\u0902, \u091c\u094b \u092c\u0938 \u0926\u094b\u0937\u094b\u0902 \u0915\u0947 \u0932\u093f\u090f \u0905\u092a\u0938\u094d\u091f\u094d\u0930\u0940\u092e \u0930\u093f\u0932\u0947 \u0938\u0902\u091a\u093e\u0932\u0928 \u0915\u094b \u0924\u0947\u091c\u093c \u092c\u0928\u093e\u0924\u093e \u0939\u0948, \u0938\u093e\u0925 \u0939\u0940 \u092c\u0948\u0915\u0905\u092a \u0938\u0941\u0930\u0915\u094d\u0937\u093e \u0915\u094d\u0937\u092e\u0924\u093e \u0915\u094b \u092c\u0928\u093e\u090f \u0930\u0916\u0924\u093e \u0939\u0948\u0964 \u0939\u092e\u0947\u0936\u093e \u0906\u0927\u093e\u0930 \u0938\u092e\u0928\u094d\u0935\u092f \u092f\u094b\u091c\u0928\u093e \u0915\u094b \u092c\u093f\u0928\u093e ZSI \u0915\u0947 \u0938\u0939\u0940 \u0922\u0902\u0917 \u0938\u0947 \u0915\u093e\u0930\u094d\u092f \u0915\u0930\u0928\u0947 \u0915\u0947 \u0932\u093f\u090f \u0921\u093f\u091c\u093c\u093e\u0907\u0928 \u0915\u0930\u0947\u0902, \u092b\u093f\u0930 \u0935\u093f\u0936\u093f\u0937\u094d\u091f \u0926\u094b\u0937 \u0938\u094d\u0925\u093e\u0928\u094b\u0902 \u0915\u0947 \u0932\u093f\u090f \u092a\u094d\u0930\u0926\u0930\u094d\u0936\u0928 \u092e\u0947\u0902 \u0938\u0941\u0927\u093e\u0930 \u0939\u0947\u0924\u0941 ZSI \u091c\u094b\u0921\u093c\u0947\u0902\u0964.<\/p>\n<h3>Q5: \u092e\u0948\u0902 \u0930\u0947\u0938\u093f\u0938\u094d\u091f\u0947\u0902\u0938-\u0917\u094d\u0930\u093e\u0909\u0902\u0921\u0947\u0921 \u0938\u093f\u0938\u094d\u091f\u092e \u092e\u0947\u0902 50N\/51N \u0924\u0924\u094d\u0935\u094b\u0902 \u0915\u094b \u0915\u0948\u0938\u0947 \u0938\u0947\u091f \u0915\u0930\u0942\u0901?<\/h3>\n<p>\u092a\u094d\u0930\u0924\u093f\u0930\u094b\u0927-\u0917\u094d\u0930\u093e\u0909\u0902\u0921\u0947\u0921 \u092a\u094d\u0930\u0923\u093e\u0932\u093f\u092f\u094b\u0902 \u092e\u0947\u0902, \u0905\u0927\u093f\u0915\u0924\u092e \u0917\u094d\u0930\u093e\u0909\u0902\u0921 \u092b\u0949\u0932\u094d\u091f \u0915\u0930\u0902\u091f \u0928\u094d\u092f\u0942\u091f\u094d\u0930\u0932 \u0917\u094d\u0930\u093e\u0909\u0902\u0921\u093f\u0902\u0917 \u0930\u0947\u091c\u093f\u0938\u094d\u091f\u0930 (NGR) \u0926\u094d\u0935\u093e\u0930\u093e \u0938\u0940\u092e\u093f\u0924 \u0939\u094b\u0924\u093e \u0939\u0948\u0964 \u0909\u091a\u094d\u091a-\u092a\u094d\u0930\u0924\u093f\u0930\u094b\u0927 \u0926\u094b\u0937\u094b\u0902 \u0915\u0947 \u092a\u094d\u0930\u0924\u093f \u0938\u0902\u0935\u0947\u0926\u0928\u0936\u0940\u0932\u0924\u093e \u0938\u0941\u0928\u093f\u0936\u094d\u091a\u093f\u0924 \u0915\u0930\u0928\u0947 \u0915\u0947 \u0932\u093f\u090f, \u0905\u0938\u0902\u0924\u0941\u0932\u093f\u0924 \u0932\u094b\u0921 \u0938\u094d\u0925\u093f\u0924\u093f\u092f\u094b\u0902 \u0915\u0947 \u0916\u093f\u0932\u093e\u092b \u0938\u0941\u0930\u0915\u094d\u0937\u093e \u092c\u0928\u093e\u090f \u0930\u0916\u0924\u0947 \u0939\u0941\u090f, 51N \u092a\u093f\u0915\u0905\u092a \u0915\u094b NGR \u0915\u0930\u0902\u091f \u0930\u0947\u091f\u093f\u0902\u0917 \u0915\u0947 10-25% \u092a\u0930 \u0938\u0947\u091f \u0915\u0930\u0947\u0902\u0964 50N \u092a\u093f\u0915\u0905\u092a \u0915\u094b \u0905\u0927\u093f\u0915\u0924\u092e \u0917\u094d\u0930\u093e\u0909\u0902\u0921 \u092b\u0949\u0932\u094d\u091f \u0915\u0930\u0902\u091f \u0915\u0947 50-80% \u092a\u0930 \u0938\u0947\u091f \u0915\u093f\u092f\u093e \u091c\u093e\u0928\u093e \u091a\u093e\u0939\u093f\u090f\u0964 \u0938\u092e\u092f \u0938\u092e\u0928\u094d\u0935\u092f \u0920\u094b\u0938 \u0930\u0942\u092a \u0938\u0947 \u0917\u094d\u0930\u093e\u0909\u0902\u0921\u0947\u0921 \u092a\u094d\u0930\u0923\u093e\u0932\u093f\u092f\u094b\u0902 \u0915\u0940 \u0924\u0941\u0932\u0928\u093e \u092e\u0947\u0902 \u0915\u092e \u092e\u0939\u0924\u094d\u0935\u092a\u0942\u0930\u094d\u0923 \u0939\u0948 \u0915\u094d\u092f\u094b\u0902\u0915\u093f \u0938\u092d\u0940 \u0917\u094d\u0930\u093e\u0909\u0902\u0921 \u092b\u0949\u0932\u094d\u091f \u0938\u094d\u0925\u093e\u0928 \u0915\u0940 \u092a\u0930\u0935\u093e\u0939 \u0915\u093f\u090f \u092c\u093f\u0928\u093e \u0938\u092e\u093e\u0928 \u0927\u093e\u0930\u093e \u092a\u0930\u093f\u092e\u093e\u0923 \u0909\u0924\u094d\u092a\u0928\u094d\u0928 \u0915\u0930\u0924\u0947 \u0939\u0948\u0902, \u0932\u0947\u0915\u093f\u0928 \u092f\u0926\u093f \u0915\u0908 \u0909\u092a\u0915\u0930\u0923 \u0936\u094d\u0930\u0943\u0902\u0916\u0932\u093e \u092e\u0947\u0902 \u0939\u0948\u0902 \u0924\u094b \u091a\u092f\u0928\u093e\u0924\u094d\u092e\u0915 51N \u0938\u092e\u0928\u094d\u0935\u092f \u0905\u092d\u0940 \u092d\u0940 \u0906\u0935\u0936\u094d\u092f\u0915 \u0939\u0948\u0964.<\/p>\n<h3>Q6: \u0905\u0902\u0921\u0930\u0935\u094b\u0932\u094d\u091f\u0947\u091c (27) \u0938\u0941\u0930\u0915\u094d\u0937\u093e \u092f\u094b\u091c\u0928\u093e\u0913\u0902 \u092e\u0947\u0902 \u0928\u0941\u0915\u0940\u0938 \u091f\u094d\u0930\u093f\u092a \u0915\u093e \u0915\u094d\u092f\u093e \u0915\u093e\u0930\u0923 \u0939\u094b\u0924\u093e \u0939\u0948?<\/h3>\n<p>\u0938\u093e\u092e\u093e\u0928\u094d\u092f \u0915\u093e\u0930\u0923\u094b\u0902 \u092e\u0947\u0902 \u0936\u093e\u092e\u093f\u0932 \u0939\u0948\u0902: (1) \u0938\u092e\u092f \u0935\u093f\u0932\u0902\u092c \u0938\u0947\u091f\u093f\u0902\u0917\u094d\u0938 \u091c\u094b \u092e\u094b\u091f\u0930 \u0938\u094d\u091f\u093e\u0930\u094d\u091f\u093f\u0902\u0917 \u092f\u093e \u0932\u094b\u0921 \u0938\u094d\u0935\u093f\u091a\u093f\u0902\u0917 \u0915\u0947 \u0926\u094c\u0930\u093e\u0928 \u0938\u093e\u092e\u093e\u0928\u094d\u092f \u0935\u094b\u0932\u094d\u091f\u0947\u091c \u0905\u0938\u094d\u0925\u093f\u0930\u0924\u093e\u0913\u0902 \u0915\u094b \u092a\u093e\u0930 \u0915\u0930\u0928\u0947 \u0915\u0947 \u0932\u093f\u090f \u092c\u0939\u0941\u0924 \u0915\u092e \u0939\u094b\u0924\u0940 \u0939\u0948\u0902, (2) \u092a\u093f\u0915\u0905\u092a \u0938\u0947\u091f\u093f\u0902\u0917\u094d\u0938 \u091c\u094b \u0938\u093e\u092e\u093e\u0928\u094d\u092f \u0935\u094b\u0932\u094d\u091f\u0947\u091c \u0909\u0924\u093e\u0930-\u091a\u0922\u093c\u093e\u0935 \u0915\u0947 \u0938\u093e\u092a\u0947\u0915\u094d\u0937 \u092c\u0939\u0941\u0924 \u0905\u0927\u093f\u0915 \u0939\u094b\u0924\u0940 \u0939\u0948\u0902, (3) \u0905\u092a\u0930\u094d\u092f\u093e\u092a\u094d\u0924 VT \u092d\u093e\u0930 \u0917\u0923\u0928\u093e\u090f\u0902 \u091c\u094b \u0935\u094b\u0932\u094d\u091f\u0947\u091c \u092e\u093e\u092a\u0928 \u0924\u094d\u0930\u0941\u091f\u093f\u092f\u094b\u0902 \u0915\u093e \u0915\u093e\u0930\u0923 \u092c\u0928\u0924\u0940 \u0939\u0948\u0902, (4) \u0905\u092a\u0938\u094d\u091f\u094d\u0930\u0940\u092e \u0935\u094b\u0932\u094d\u091f\u0947\u091c \u0930\u0947\u0917\u0941\u0932\u0947\u091f\u0930 \u092f\u093e \u091f\u0948\u092a \u091a\u0947\u0902\u091c\u0930\u094d\u0938 \u0915\u0947 \u0938\u093e\u0925 \u0938\u092e\u0928\u094d\u0935\u092f \u0915\u0940 \u0915\u092e\u0940, \u0914\u0930 (5) \u0905\u0928\u0941\u091a\u093f\u0924 VT \u0926\u094d\u0935\u093f\u0924\u0940\u092f\u0915 \u0935\u093e\u092f\u0930\u093f\u0902\u0917 \u091c\u094b \u0935\u094b\u0932\u094d\u091f\u0947\u091c \u0921\u094d\u0930\u0949\u092a \u0909\u0924\u094d\u092a\u0928\u094d\u0928 \u0915\u0930\u0924\u0940 \u0939\u0948\u0964 \u0906\u092e \u0938\u092e\u093e\u0927\u093e\u0928\u094b\u0902 \u092e\u0947\u0902 2-5 \u0938\u0947\u0915\u0902\u0921 \u0915\u0940 \u0938\u092e\u092f \u0926\u0947\u0930\u0940 \u0914\u0930 80-85% \u0928\u093e\u092e\u092e\u093e\u0924\u094d\u0930 \u0935\u094b\u0932\u094d\u091f\u0947\u091c \u0915\u0940 \u092a\u093f\u0915\u0905\u092a \u0938\u0947\u091f\u093f\u0902\u0917\u094d\u0938 \u0936\u093e\u092e\u093f\u0932 \u0939\u094b\u0924\u0940 \u0939\u0948\u0902, \u0939\u093e\u0932\u093e\u0902\u0915\u093f \u0935\u093f\u0936\u093f\u0937\u094d\u091f \u0905\u0928\u0941\u092a\u094d\u0930\u092f\u094b\u0917\u094b\u0902 \u0915\u0947 \u0932\u093f\u090f \u0905\u0932\u0917-\u0905\u0932\u0917 \u092e\u093e\u0928\u094b\u0902 \u0915\u0940 \u0906\u0935\u0936\u094d\u092f\u0915\u0924\u093e \u0939\u094b \u0938\u0915\u0924\u0940 \u0939\u0948\u0964.<\/p>\n<h3>Q7: \u0938\u0902\u0916\u094d\u092f\u093e\u0924\u094d\u092e\u0915 \u0930\u093f\u0932\u0947 \u0932\u0949\u0915\u0906\u0909\u091f \u092b\u093c\u0902\u0915\u094d\u0936\u0928 \u0915\u094b \u0906\u0902\u0924\u0930\u093f\u0915 \u0930\u0942\u092a \u0938\u0947 \u0914\u0930 \u092c\u093e\u0939\u0930\u0940 86 \u0921\u093f\u0935\u093e\u0907\u0938\u094b\u0902 \u0915\u0947 \u0938\u093e\u0925 \u0915\u0948\u0938\u0947 \u0938\u0902\u092d\u093e\u0932\u0924\u0947 \u0939\u0948\u0902?<\/h3>\n<p>\u0938\u0902\u0916\u094d\u092f\u093e\u0924\u094d\u092e\u0915 \u0930\u093f\u0932\u0947 \u0906\u0902\u0924\u0930\u093f\u0915 \u0930\u0942\u092a \u0938\u0947 \u0932\u0949\u091c\u093f\u0915\u0932 \u0932\u0949\u0915\u0906\u0909\u091f \u092b\u093c\u0902\u0915\u094d\u0936\u0928 \u0932\u093e\u0917\u0942 \u0915\u0930 \u0938\u0915\u0924\u0947 \u0939\u0948\u0902, \u091c\u094b \u090f\u0915 \u0932\u0948\u091a\u094d\u0921 \u091f\u094d\u0930\u093f\u092a \u0938\u094d\u0925\u093f\u0924\u093f \u092c\u0928\u093e\u090f \u0930\u0916\u0924\u0947 \u0939\u0948\u0902 \u091c\u093f\u0938\u0947 \u0930\u093f\u0932\u0947 HMI \u092f\u093e \u0938\u0902\u091a\u093e\u0930 \u0907\u0902\u091f\u0930\u092b\u093c\u0947\u0938 \u0915\u0947 \u092e\u093e\u0927\u094d\u092f\u092e \u0938\u0947 \u092e\u0948\u0928\u094d\u092f\u0941\u0905\u0932 \u0930\u0940\u0938\u0947\u091f \u0915\u0940 \u0906\u0935\u0936\u094d\u092f\u0915\u0924\u093e \u0939\u094b\u0924\u0940 \u0939\u0948\u0964 \u0939\u093e\u0932\u093e\u0901\u0915\u093f, \u092e\u0939\u0924\u094d\u0935\u092a\u0942\u0930\u094d\u0923 \u0905\u0928\u0941\u092a\u094d\u0930\u092f\u094b\u0917\u094b\u0902 \u0915\u0947 \u0932\u093f\u090f \u092c\u093e\u0939\u0930\u0940 86 \u0921\u093f\u0935\u093e\u0907\u0938\u094b\u0902 \u0915\u094b \u092a\u094d\u0930\u093e\u0925\u092e\u093f\u0915\u0924\u093e \u0926\u0940 \u091c\u093e\u0924\u0940 \u0939\u0948 \u0915\u094d\u092f\u094b\u0902\u0915\u093f \u0935\u0947 \u092a\u094d\u0930\u0926\u093e\u0928 \u0915\u0930\u0924\u0947 \u0939\u0948\u0902: (1) \u092c\u094d\u0930\u0947\u0915\u0930 \u0915\u094d\u0932\u094b\u091c \u0938\u0930\u094d\u0915\u093f\u091f \u0915\u0940 \u0939\u093e\u0930\u094d\u0921\u0935\u093e\u092f\u0930\u094d\u0921, \u092b\u0947\u0932-\u0938\u0947\u092b \u092c\u094d\u0932\u0949\u0915\u093f\u0902\u0917, (2) \u0926\u0943\u0936\u094d\u092f\u092e\u093e\u0928 \u0932\u0915\u094d\u0937\u094d\u092f \u0927\u094d\u0935\u091c \u091c\u094b \u0930\u093f\u0932\u0947 \u092a\u0942\u091b\u0924\u093e\u091b \u0915\u0940 \u0906\u0935\u0936\u094d\u092f\u0915\u0924\u093e \u0928\u0939\u0940\u0902 \u0930\u0916\u0924\u0947, (3) \u090f\u0915 \u0928\u093f\u0936\u094d\u091a\u093f\u0924 \u092e\u0948\u0928\u0941\u0905\u0932 \u0930\u0940\u0938\u0947\u091f \u0915\u094d\u0930\u093f\u092f\u093e \u091c\u094b \u0911\u092a\u0930\u0947\u091f\u0930 \u0915\u0940 \u0938\u094d\u0935\u0940\u0915\u0943\u0924\u093f \u0915\u094b \u092c\u093e\u0927\u094d\u092f \u0915\u0930\u0924\u0940 \u0939\u0948, \u0914\u0930 (4) \u0930\u093f\u0932\u0947 \u092a\u093e\u0935\u0930 \u0938\u092a\u094d\u0932\u093e\u0908 \u0915\u0940 \u0909\u092a\u0932\u092c\u094d\u0927\u0924\u093e \u0938\u0947 \u0938\u094d\u0935\u0924\u0902\u0924\u094d\u0930\u0924\u093e\u0964 \u0915\u0908 \u0938\u0941\u0935\u093f\u0927\u093e\u090f\u0901 \u0926\u094b\u0928\u094b\u0902 \u0915\u093e \u0909\u092a\u092f\u094b\u0917 \u0915\u0930\u0924\u0940 \u0939\u0948\u0902: \u092a\u094d\u0930\u0925\u092e-\u092a\u0902\u0915\u094d\u0924\u093f \u0938\u0941\u0930\u0915\u094d\u0937\u093e \u0915\u0947 \u0932\u093f\u090f \u0906\u0902\u0924\u0930\u093f\u0915 \u0932\u0949\u091c\u093f\u0915\u0932 \u0932\u0949\u0915\u0906\u0909\u091f \u0914\u0930 \u092c\u0948\u0915\u0905\u092a \u0924\u0925\u093e \u0928\u093f\u092f\u093e\u092e\u0915 \u0905\u0928\u0941\u092a\u093e\u0932\u0928 \u0915\u0947 \u0932\u093f\u090f \u092c\u093e\u0939\u0930\u0940 86 \u0921\u093f\u0935\u093e\u0907\u0938\u0964.<\/p>\n<hr \/>\n<h2>\u0928\u093f\u0937\u094d\u0915\u0930\u094d\u0937: \u092e\u0941\u0916\u094d\u092f \u092c\u093f\u0902\u0926\u0941<\/h2>\n<p>\u090f\u092e\u0935\u0940 \u092a\u0948\u0928\u0932\u094b\u0902 \u092e\u0947\u0902 \u092a\u094d\u0930\u092d\u093e\u0935\u0940 \u0930\u093f\u0932\u0947 \u091f\u094d\u0930\u093f\u092a \u0932\u0949\u091c\u093f\u0915 \u0921\u093f\u091c\u093c\u093e\u0907\u0928 \u0915\u0947 \u0932\u093f\u090f \u0915\u0908 \u0938\u0941\u0930\u0915\u094d\u0937\u093e \u0915\u093e\u0930\u094d\u092f\u094b\u0902 \u0915\u094b \u090f\u0915 \u0938\u092e\u0928\u094d\u0935\u093f\u0924 \u092f\u094b\u091c\u0928\u093e \u092e\u0947\u0902 \u0935\u094d\u092f\u0935\u0938\u094d\u0925\u093f\u0924 \u0930\u0942\u092a \u0938\u0947 \u090f\u0915\u0940\u0915\u0943\u0924 \u0915\u0930\u0928\u093e \u0906\u0935\u0936\u094d\u092f\u0915 \u0939\u0948\u0964 \u092e\u0942\u0932\u092d\u0942\u0924 \u0938\u093f\u0926\u094d\u0927\u093e\u0902\u0924\u094b\u0902 \u092e\u0947\u0902 \u0936\u093e\u092e\u093f\u0932 \u0939\u0948\u0902:<\/p>\n<ol>\n<li><strong>\u092a\u0930\u0924\u0926\u093e\u0930 \u0938\u0941\u0930\u0915\u094d\u0937\u093e:<\/strong> \u0917\u0924\u093f \u0914\u0930 \u091a\u092f\u0928\u093e\u0924\u094d\u092e\u0915\u0924\u093e \u0926\u094b\u0928\u094b\u0902 \u092a\u094d\u0930\u093e\u092a\u094d\u0924 \u0915\u0930\u0928\u0947 \u0915\u0947 \u0932\u093f\u090f \u0924\u093e\u0924\u094d\u0915\u093e\u0932\u093f\u0915 (50\/50N) \u0914\u0930 \u0938\u092e\u092f-\u0935\u093f\u0932\u0902\u092c\u093f\u0924 (51\/51N) \u0918\u091f\u0915\u094b\u0902 \u0915\u094b \u0938\u0902\u092f\u094b\u091c\u093f\u0924 \u0915\u0930\u0947\u0902\u0964.<\/li>\n<li><strong>\u0938\u092e\u0928\u094d\u0935\u093f\u0924 \u0905\u092d\u093f\u092f\u093e\u0928:<\/strong> \u092f\u0939 \u0938\u0941\u0928\u093f\u0936\u094d\u091a\u093f\u0924 \u0915\u0930\u0928\u0947 \u0915\u0947 \u0932\u093f\u090f \u0915\u093f \u090a\u092a\u0930\u0940 \u0909\u092a\u0915\u0930\u0923\u094b\u0902 \u0915\u0947 \u0938\u0902\u091a\u093e\u0932\u0928 \u0938\u0947 \u092a\u0939\u0932\u0947 \u0921\u093e\u0909\u0928\u0938\u094d\u091f\u094d\u0930\u0940\u092e \u0930\u093f\u0932\u0947 \u0926\u094b\u0937\u094b\u0902 \u0915\u094b \u0926\u0942\u0930 \u0915\u0930 \u0932\u0947\u0902, \u0915\u094d\u0930\u092e\u093f\u0915 \u0909\u092a\u0915\u0930\u0923\u094b\u0902 \u0915\u0947 \u092c\u0940\u091a \u092a\u0930\u094d\u092f\u093e\u092a\u094d\u0924 \u0938\u092e\u092f \u0905\u0902\u0924\u0930\u093e\u0932 \u092c\u0928\u093e\u090f \u0930\u0916\u0947\u0902\u0964.<\/li>\n<li><strong>\u0915\u0947\u0902\u0926\u094d\u0930\u0940\u0915\u0943\u0924 \u092f\u093e\u0924\u094d\u0930\u093e \u0924\u0930\u094d\u0915:<\/strong> \u0938\u0941\u0930\u0915\u094d\u0937\u093e \u0906\u0909\u091f\u092a\u0941\u091f \u0915\u094b \u0938\u092e\u0947\u0915\u093f\u0924 \u0915\u0930\u0928\u0947, \u0926\u094b\u0937 \u0938\u094d\u0935\u0940\u0915\u0943\u0924\u093f \u0938\u0941\u0928\u093f\u0936\u094d\u091a\u093f\u0924 \u0915\u0930\u0928\u0947, \u0914\u0930 \u0917\u0902\u092d\u0940\u0930 \u0926\u094b\u0937\u094b\u0902 \u0915\u0947 \u092c\u093e\u0926 \u0938\u094d\u0935\u091a\u093e\u0932\u093f\u0924 \u092a\u0941\u0928\u0903\u092c\u0902\u0926 \u0939\u094b\u0928\u0947 \u0915\u094b \u0930\u094b\u0915\u0928\u0947 \u0915\u0947 \u0932\u093f\u090f \u0932\u0949\u0915\u0906\u0909\u091f \u0930\u093f\u0932\u0947 (86) \u0915\u093e \u0909\u092a\u092f\u094b\u0917 \u0915\u0930\u0947\u0902\u0964.<\/li>\n<li><strong>\u0935\u094b\u0932\u094d\u091f\u0947\u091c \u0938\u0941\u0930\u0915\u094d\u0937\u093e \u090f\u0915\u0940\u0915\u0930\u0923:<\/strong> \u0935\u0930\u094d\u0924\u092e\u093e\u0928-\u0906\u0927\u093e\u0930\u093f\u0924 \u0924\u0924\u094d\u0935\u094b\u0902 \u0926\u094d\u0935\u093e\u0930\u093e \u092a\u0924\u093e \u0928\u0939\u0940\u0902 \u0932\u0917\u093e\u0908 \u091c\u093e \u0938\u0915\u0928\u0947 \u0935\u093e\u0932\u0940 \u0938\u094d\u0925\u093f\u0924\u093f\u092f\u094b\u0902 \u0938\u0947 \u0938\u0941\u0930\u0915\u094d\u0937\u093e \u0915\u0947 \u0932\u093f\u090f \u0905\u0902\u0921\u0930\u0935\u094b\u0932\u094d\u091f\u0947\u091c (27) \u0914\u0930 \u0913\u0935\u0930\u0935\u094b\u0932\u094d\u091f\u0947\u091c (59) \u092b\u093c\u0902\u0915\u094d\u0936\u0928 \u0936\u093e\u092e\u093f\u0932 \u0915\u0930\u0947\u0902\u0964.<\/li>\n<li><strong>\u092a\u0930\u0940\u0915\u094d\u0937\u0923 \u0914\u0930 \u092a\u094d\u0930\u092e\u093e\u0923\u0940\u0915\u0930\u0923:<\/strong> \u0915\u0920\u094b\u0930 \u0915\u092e\u0940\u0936\u0928\u093f\u0902\u0917 \u0914\u0930 \u0906\u0935\u0927\u093f\u0915 \u0930\u0916\u0930\u0916\u093e\u0935 \u092f\u0939 \u0938\u0941\u0928\u093f\u0936\u094d\u091a\u093f\u0924 \u0915\u0930\u0924\u0947 \u0939\u0948\u0902 \u0915\u093f \u091f\u094d\u0930\u093f\u092a \u0932\u0949\u091c\u093f\u0915 \u092e\u0948\u092a \u092a\u0942\u0930\u0947 \u0938\u093f\u0938\u094d\u091f\u092e \u091c\u0940\u0935\u0928\u091a\u0915\u094d\u0930 \u092e\u0947\u0902 \u0938\u0939\u0940 \u0922\u0902\u0917 \u0938\u0947 \u0915\u093e\u0930\u094d\u092f \u0915\u0930\u0947\u0964.<\/li>\n<li><strong>\u0926\u0938\u094d\u0924\u093e\u0935\u0947\u091c\u093c\u0940\u0915\u0930\u0923:<\/strong> \u0938\u092e\u0938\u094d\u092f\u093e \u0928\u093f\u0935\u093e\u0930\u0923 \u0914\u0930 \u092d\u0935\u093f\u0937\u094d\u092f \u0915\u0947 \u0938\u0902\u0936\u094b\u0927\u0928\u094b\u0902 \u092e\u0947\u0902 \u0938\u0939\u093e\u092f\u0924\u093e \u0915\u0947 \u0932\u093f\u090f \u0938\u0947\u091f\u093f\u0902\u0917\u094d\u0938, \u0935\u093e\u092f\u0930\u093f\u0902\u0917 \u0914\u0930 \u092a\u0930\u0940\u0915\u094d\u0937\u0923 \u092a\u0930\u093f\u0923\u093e\u092e\u094b\u0902 \u0915\u093e \u0938\u091f\u0940\u0915 \u0930\u093f\u0915\u0949\u0930\u094d\u0921 \u092c\u0928\u093e\u090f \u0930\u0916\u0947\u0902\u0964.<\/li>\n<\/ol>\n<p>\u0909\u091a\u093f\u0924 \u0930\u0942\u092a \u0938\u0947 \u0921\u093f\u091c\u093c\u093e\u0907\u0928 \u0914\u0930 \u0915\u092e\u0940\u0936\u0928 \u0915\u0940 \u0917\u0908 \u0930\u093f\u0932\u0947 \u091f\u094d\u0930\u093f\u092a \u0932\u0949\u091c\u093f\u0915 \u092e\u0947\u0902 \u0915\u093f\u092f\u093e \u0917\u092f\u093e \u0928\u093f\u0935\u0947\u0936 \u092c\u0947\u0939\u0924\u0930 \u0909\u092a\u0915\u0930\u0923 \u0938\u0941\u0930\u0915\u094d\u0937\u093e, \u0915\u092e \u0921\u093e\u0909\u0928\u091f\u093e\u0907\u092e \u0914\u0930 \u092c\u0922\u093c\u0940 \u0939\u0941\u0908 \u0915\u0930\u094d\u092e\u091a\u093e\u0930\u0940 \u0938\u0941\u0930\u0915\u094d\u0937\u093e \u0915\u0947 \u092e\u093e\u0927\u094d\u092f\u092e \u0938\u0947 \u0932\u093e\u092d \u092a\u094d\u0930\u0926\u093e\u0928 \u0915\u0930\u0924\u093e \u0939\u0948\u0964 \u091c\u0948\u0938\u0947-\u091c\u0948\u0938\u0947 \u0938\u0941\u0930\u0915\u094d\u0937\u093e \u0924\u0915\u0928\u0940\u0915 \u0921\u093f\u091c\u093f\u091f\u0932 \u0938\u0902\u091a\u093e\u0930 \u0914\u0930 \u0909\u0928\u094d\u0928\u0924 \u0935\u093f\u0936\u094d\u0932\u0947\u0937\u0923 \u0915\u0947 \u0938\u093e\u0925 \u0935\u093f\u0915\u0938\u093f\u0924 \u0939\u094b\u0924\u0940 \u091c\u093e \u0930\u0939\u0940 \u0939\u0948, \u0938\u092e\u0928\u094d\u0935\u092f \u0914\u0930 \u0907\u0902\u091f\u0930\u0932\u0949\u0915\u093f\u0902\u0917 \u0915\u0947 \u092f\u0947 \u092e\u094c\u0932\u093f\u0915 \u0938\u093f\u0926\u094d\u0927\u093e\u0902\u0924 \u0935\u093f\u0936\u094d\u0935\u0938\u0928\u0940\u092f \u092a\u093e\u0935\u0930 \u0938\u093f\u0938\u094d\u091f\u092e \u0938\u0902\u091a\u093e\u0932\u0928 \u0915\u0947 \u0932\u093f\u090f \u0905\u0928\u093f\u0935\u093e\u0930\u094d\u092f \u092c\u0928\u0947 \u0939\u0941\u090f \u0939\u0948\u0902\u0964.<\/p>\n<hr \/>\n<p><em>\u0938\u0902\u0930\u0915\u094d\u0937\u0923\u093e\u0924\u094d\u092e\u0915 \u0930\u093f\u0932\u0947\u0907\u0902\u0917 \u092a\u0930 \u0905\u0924\u093f\u0930\u093f\u0915\u094d\u0924 \u0924\u0915\u0928\u0940\u0915\u0940 \u0938\u0902\u0938\u093e\u0927\u0928\u094b\u0902 \u0915\u0947 \u0932\u093f\u090f, IEEE \u092a\u093e\u0935\u0930 \u0938\u093f\u0938\u094d\u091f\u092e \u0930\u093f\u0932\u0947\u0907\u0902\u0917 \u0914\u0930 \u0928\u093f\u092f\u0902\u0924\u094d\u0930\u0923 \u0938\u092e\u093f\u0924\u093f (PSRCC) \u0935\u094d\u092f\u093e\u092a\u0915 \u092e\u093e\u0928\u0915 \u0914\u0930 \u091f\u094d\u092f\u0942\u091f\u094b\u0930\u093f\u092f\u0932 \u092f\u0939\u093e\u0901 \u092c\u0928\u093e\u090f \u0930\u0916\u0924\u0940 \u0939\u0948\u0964 <a href=\"https:\/\/www.pes-psrc.org\/\" target=\"_blank\" rel=\"noopener\">\u0906\u0908\u0908\u0908\u0908 \u092a\u0940\u0908\u090f\u0938 \u092a\u0940\u090f\u0938\u0906\u0930\u0938\u0940\u0938\u0940<\/a>.<\/em><\/p>\n<hr \/>\n<h2>\u0938\u0902\u092c\u0902\u0927\u093f\u0924 \u0924\u0915\u0928\u0940\u0915\u0940 \u0938\u0902\u0938\u093e\u0927\u0928<\/h2>\n<ul>\n<li><a href=\"https:\/\/xbrele.com\/hi\/vacuum-contactor\/\">\u0935\u0948\u0915\u094d\u092f\u0942\u092e \u0915\u0949\u0928\u094d\u091f\u0948\u0915\u094d\u091f\u0930 \u0909\u0924\u094d\u092a\u093e\u0926 \u0905\u0935\u0932\u094b\u0915\u0928<\/a><\/li>\n<li><a href=\"https:\/\/xbrele.com\/hi\/vacuum-circuit-breaker\/\">\u0935\u0948\u0915\u094d\u092f\u0942\u092e \u0938\u0930\u094d\u0915\u093f\u091f \u092c\u094d\u0930\u0947\u0915\u0930 \u092a\u094b\u0930\u094d\u091f\u092b\u094b\u0932\u093f\u092f\u094b<\/a><\/li>\n<li><a href=\"https:\/\/xbrele.com\/hi\/power-distribution-transformers\/\">\u0935\u093f\u0926\u094d\u092f\u0941\u0924 \u0935\u093f\u0924\u0930\u0923 \u091f\u094d\u0930\u093e\u0902\u0938\u092b\u093e\u0930\u094d\u092e\u0930 \u0938\u092e\u093e\u0927\u093e\u0928<\/a><\/li>\n<li><a href=\"https:\/\/xbrele.com\/hi\/switchgear-parts\/\">\u0938\u094d\u0935\u093f\u091a\u0917\u093f\u092f\u0930 \u0915\u0947 \u092a\u0941\u0930\u094d\u091c\u0947 \u0914\u0930 \u0907\u0928\u094d\u0938\u0941\u0932\u0947\u0936\u0928 \u0915\u0947 \u0918\u091f\u0915<\/a><\/li>\n<li><a href=\"https:\/\/xbrele.com\/hi\/switchgear-parts\/contact-box\/\">\u090f\u092a\u0949\u0915\u094d\u0938\u0940 \u0938\u0902\u092a\u0930\u094d\u0915 \u092c\u0949\u0915\u094d\u0938 \u0918\u091f\u0915 \u0935\u093f\u0935\u0930\u0923<\/a><\/li>\n<li><a href=\"https:\/\/webstore.iec.ch\/en\/publication\/99635\" target=\"_blank\" rel=\"noopener\">IEC 62271-100 \u092a\u094d\u0930\u0915\u093e\u0936\u0928 \u092a\u0943\u0937\u094d\u0920<\/a><\/li>\n<\/ul>","protected":false},"excerpt":{"rendered":"<p>A Comprehensive Technical Guide to Protective Relay Coordination and Interlocking Schemes Introduction In medium voltage (MV) electrical distribution systems, protective relays serve as the critical first line of defense against electrical faults, equipment damage, and personnel hazards. Understanding how these relays interlock and communicate through trip logic maps is fundamental to designing, commissioning, and maintaining [&hellip;]<\/p>\n","protected":false},"author":3,"featured_media":3680,"comment_status":"open","ping_status":"open","sticky":false,"template":"","format":"standard","meta":{"_gspb_post_css":"","footnotes":""},"categories":[27],"tags":[],"class_list":["post-3685","post","type-post","status-publish","format-standard","has-post-thumbnail","hentry","category-switchgear-parts-knowledge"],"blocksy_meta":[],"_links":{"self":[{"href":"https:\/\/xbrele.com\/hi\/wp-json\/wp\/v2\/posts\/3685","targetHints":{"allow":["GET"]}}],"collection":[{"href":"https:\/\/xbrele.com\/hi\/wp-json\/wp\/v2\/posts"}],"about":[{"href":"https:\/\/xbrele.com\/hi\/wp-json\/wp\/v2\/types\/post"}],"author":[{"embeddable":true,"href":"https:\/\/xbrele.com\/hi\/wp-json\/wp\/v2\/users\/3"}],"replies":[{"embeddable":true,"href":"https:\/\/xbrele.com\/hi\/wp-json\/wp\/v2\/comments?post=3685"}],"version-history":[{"count":7,"href":"https:\/\/xbrele.com\/hi\/wp-json\/wp\/v2\/posts\/3685\/revisions"}],"predecessor-version":[{"id":3818,"href":"https:\/\/xbrele.com\/hi\/wp-json\/wp\/v2\/posts\/3685\/revisions\/3818"}],"wp:featuredmedia":[{"embeddable":true,"href":"https:\/\/xbrele.com\/hi\/wp-json\/wp\/v2\/media\/3680"}],"wp:attachment":[{"href":"https:\/\/xbrele.com\/hi\/wp-json\/wp\/v2\/media?parent=3685"}],"wp:term":[{"taxonomy":"category","embeddable":true,"href":"https:\/\/xbrele.com\/hi\/wp-json\/wp\/v2\/categories?post=3685"},{"taxonomy":"post_tag","embeddable":true,"href":"https:\/\/xbrele.com\/hi\/wp-json\/wp\/v2\/tags?post=3685"}],"curies":[{"name":"\u0921\u092c\u094d\u0932\u094d\u092f\u0942\u092a\u0940","href":"https:\/\/api.w.org\/{rel}","templated":true}]}}