{"id":2907,"date":"2026-02-02T06:21:16","date_gmt":"2026-02-02T06:21:16","guid":{"rendered":"https:\/\/xbrele.com\/?p=2907"},"modified":"2026-10-14T12:57:42","modified_gmt":"2026-10-14T12:57:42","slug":"ct-accuracy-classes-metering-protection-guide","status":"publish","type":"post","link":"https:\/\/xbrele.com\/pt\/ct-accuracy-classes-metering-protection-guide\/","title":{"rendered":"Explica\u00e7\u00e3o das classes de precis\u00e3o do transformador de corrente (TC) (0,2\/0,5, 5P\/10P): Medi\u00e7\u00e3o vs. prote\u00e7\u00e3o"},"content":{"rendered":"<p class=\"xbrele-article-updated\"><small>\u00daltima atualiza\u00e7\u00e3o: <time datetime=\"2026-10-14\">October 14, 2026<\/time>.<\/small><\/p>\n\n\n\n<p>Current transformers supply measuring instruments and protection relays with scaled current signals. Metering classes describe measurement accuracy over a specified load-current range; protection classes describe performance under the fault conditions covered by their designation. A metering-class label alone does not establish suitability for protection, and a protection-class label alone does not establish revenue-metering accuracy.<\/p>\n\n\n\n<p>Este guia detalha as designa\u00e7\u00f5es de classe de precis\u00e3o da IEC 61869-2, explica as diferen\u00e7as t\u00e9cnicas entre as classes de medi\u00e7\u00e3o (0,1, 0,2, 0,5) e as classes de prote\u00e7\u00e3o (5P, 10P) e fornece orienta\u00e7\u00f5es pr\u00e1ticas de sele\u00e7\u00e3o para aplica\u00e7\u00f5es de m\u00e9dia tens\u00e3o.<\/p>\n\n\n\n<h2 class=\"wp-block-heading\" id=\"what-are-ct-accuracy-classes\">O que s\u00e3o classes de precis\u00e3o de TC?<\/h2>\n\n\n\n<p>A CT accuracy class defines permissible errors under specified current, burden, frequency and test conditions. For a metering CT, the class number identifies the rated-current ratio-error limit; other test currents have their own limits. In a 5P or 10P designation, the number identifies the composite-error limit at the rated accuracy-limit primary current, not the ratio-error limit at normal load.<\/p>\n\n\n\n<p>Existem dois sistemas de classifica\u00e7\u00e3o distintos. As classes de medi\u00e7\u00e3o (0,1, 0,2, 0,5, 1,0) otimizam a precis\u00e3o em correntes operacionais normais, normalmente de 5% a 120% da corrente nominal. As classes de prote\u00e7\u00e3o (5P, 10P) priorizam o desempenho durante condi\u00e7\u00f5es de falha, mantendo a precis\u00e3o em m\u00faltiplos de corrente que excedem em muito a opera\u00e7\u00e3o normal.<\/p>\n\n\n\n<p>Metering and protection impose different design requirements. A CT may contain separate metering and protection cores, and some designs carry more than one accuracy designation. Select each core using its declared ratings and the connected equipment requirements; neither core size nor material alone proves its accuracy class.<\/p>\n\n\n\n<figure class=\"wp-block-embed is-type-video is-provider-youtube wp-block-embed-youtube wp-embed-aspect-16-9 wp-has-aspect-ratio\"><div class=\"wp-block-embed__wrapper\">\n<iframe title=\"Explica\u00e7\u00e3o das classes de precis\u00e3o de TC: Medi\u00e7\u00e3o 0,2\/0,5 vs. Prote\u00e7\u00e3o 5P\/10P\" width=\"1290\" height=\"726\" src=\"https:\/\/www.youtube.com\/embed\/PVXlrxYOFzA?feature=oembed\" frameborder=\"0\" allow=\"accelerometer; autoplay; clipboard-write; encrypted-media; gyroscope; picture-in-picture; web-share\" referrerpolicy=\"strict-origin-when-cross-origin\" allowfullscreen><\/iframe>\n<\/div><\/figure>\n\n\n\n<h2 class=\"wp-block-heading\" id=\"how-current-transformers-introduce-measurement-errors\">Como os transformadores de corrente introduzem erros de medi\u00e7\u00e3o<\/h2>\n\n\n\n<p>Part of the primary ampere-turns supplies the core excitation rather than the secondary load. The resulting exciting current, together with the secondary circuit impedance, produces ratio error and phase displacement.<\/p>\n\n\n\n<p><strong>Erro de propor\u00e7\u00e3o (\u03b5)<\/strong> is the difference between the primary current inferred from the rated ratio and the actual primary current, expressed as a percentage of the actual primary current. With a rated ratio of 1000\/5 A, a secondary reading of 4.98 A at 1000 A primary gives (200 \u00d7 4.98 \u2212 1000) \/ 1000 \u00d7 100 = \u22120.4%. The error varies with current and burden.<\/p>\n\n\n\n<p><strong>Deslocamento de fase (\u03b4)<\/strong>&nbsp;mede a diferen\u00e7a angular entre os fasores de corrente prim\u00e1ria e secund\u00e1ria, expressa em minutos de arco. A transforma\u00e7\u00e3o ideal produz mudan\u00e7a de fase zero; os TCs reais apresentam pequenos deslocamentos devido aos requisitos de corrente de magnetiza\u00e7\u00e3o.<\/p>\n\n\n\n<p>Core material, geometry, turns and excitation characteristics all influence CT performance. Rated output is stated in VA at the rated secondary current. Check the manufacturer\u2019s declared burden range and burden power factor as well as the VA rating: a very small connected burden is not automatically within the metering accuracy guarantee.<\/p>\n\n\n\n<p>The limits apply at the current and burden conditions specified for the class. At rated primary current, Class 0.2 has ratio-error and phase-displacement limits of \u00b10.2% and \u00b110 minutes. For protection classes, the rated-current ratio-error limits are \u00b11% for 5P and \u00b13% for 10P; their respective composite-error limits at the rated accuracy-limit current are 5% and 10%.<\/p>\n\n\n\n\n\n<h2 class=\"wp-block-heading\" id=\"metering-ct-accuracy-classes-0.1-0.2-0.5-and-extended-s-classes\">Classes de precis\u00e3o de CT de medi\u00e7\u00e3o: 0,1, 0,2, 0,5 e classes \u201cS\u201d estendidas<\/h2>\n\n\n\n<p>Metering classes specify ratio-error and phase-displacement limits at several test currents. The table lists the limits at 100% rated current and the covered current range. It does not mean that the rated-current error limit applies unchanged over that entire range; use the full class table and the CT\u2019s declared burden conditions for selection.<\/p>\n\n\n\n<figure class=\"wp-block-table\"><table class=\"has-fixed-layout\"><thead><tr><th>Classe<\/th><th>Erro de propor\u00e7\u00e3o em 100% In<\/th><th>Phase displacement at 100% In<\/th><th>Specified current range<\/th><th>Aplica\u00e7\u00e3o t\u00edpica<\/th><\/tr><\/thead><tbody><tr><td>0.1<\/td><td>\u00b10,1%<\/td><td>\u00b15 min<\/td><td>5-120%<\/td><td>Padr\u00f5es de refer\u00eancia de laborat\u00f3rio<\/td><\/tr><tr><td>0.2<\/td><td>\u00b10,2%<\/td><td>\u00b110 min<\/td><td>5-120%<\/td><td>Medi\u00e7\u00e3o de receita de transmiss\u00e3o<\/td><\/tr><tr><td>0.2S<\/td><td>\u00b10,2%<\/td><td>\u00b110 min<\/td><td>1-120%<\/td><td>Medi\u00e7\u00e3o de receita de carga vari\u00e1vel<\/td><\/tr><tr><td>0.5<\/td><td>\u00b10,5%<\/td><td>\u00b130 min<\/td><td>5-120%<\/td><td>Medi\u00e7\u00e3o de subesta\u00e7\u00e3o de distribui\u00e7\u00e3o<\/td><\/tr><tr><td>0.5S<\/td><td>\u00b10,5%<\/td><td>\u00b130 min<\/td><td>1-120%<\/td><td>Medi\u00e7\u00e3o de receita industrial<\/td><\/tr><tr><td>1.0<\/td><td>\u00b11,0%<\/td><td>\u00b160 min<\/td><td>5-120%<\/td><td>Instrumentos indicadores<\/td><\/tr><\/tbody><\/table><\/figure>\n\n\n\n<p>The \u201cS\u201d suffix identifies metering classes with additional low-current requirements. Classes 0.2S and 0.5S include a 1% rated-current test point, whereas the ordinary classes listed above start at 5%. Error limits differ by test point. Select a class and ratio that cover the expected minimum load and the applicable metering requirements.<\/p>\n\n\n\n<p>For variable-load facilities, compare the expected minimum primary current with the CT rating before choosing between 0.2 and 0.2S. Billing value alone does not define the required class. Include the meter, voltage measurement and wiring in the overall measurement-accuracy assessment.<\/p>\n\n\n\n<p><strong>Instrument security factor (FS)<\/strong> describes the overcurrent behavior specified for a metering core at rated burden. FS5 and FS10 are common declared ratings, but the accuracy class alone does not prescribe a universal saturation multiple. Reducing the connected burden can increase the current at which the core saturates. Verify FS and the meter\u2019s withstand capability rather than assuming every metering CT saturates at 2\u20135 times rated current.<\/p>\n\n\n\n\n\n<hr class=\"wp-block-separator has-alpha-channel-opacity\"\/>\n\n\n\n<blockquote class=\"wp-block-quote is-layout-flow wp-block-quote-is-layout-flow\">\n<p><strong>Metering CT selection checks<\/strong><\/p>\n\n\n\n<ul class=\"wp-block-list\">\n<li>Compare the expected minimum load with the class test points and the CT ratio.<\/li>\n\n\n\n<li>Verify the complete connected burden is within the CT\u2019s declared metering accuracy range.<\/li>\n\n\n\n<li>Obtain the selected meter\u2019s actual input burden; verify accuracy at the resulting total burden.<\/li>\n\n\n\n<li>Solicite certificados de teste de f\u00e1brica que mostrem os erros reais medidos, n\u00e3o apenas a conformidade com a classe<\/li>\n<\/ul>\n<\/blockquote>\n\n\n\n<hr class=\"wp-block-separator has-alpha-channel-opacity\"\/>\n\n\n\n<h2 class=\"wp-block-heading\" id=\"protection-ct-accuracy-classes-decoding-5p-and-10p-designations\">Classes de precis\u00e3o de TC de prote\u00e7\u00e3o: Decodifica\u00e7\u00e3o das designa\u00e7\u00f5es 5P e 10P<\/h2>\n\n\n\n<p>As classes de prote\u00e7\u00e3o seguem um sistema de nota\u00e7\u00e3o diferente que reflete sua fun\u00e7\u00e3o principal: medi\u00e7\u00e3o precisa da corrente de falta. A designa\u00e7\u00e3o \u201c5P20\u201d codifica tr\u00eas par\u00e2metros essenciais para a coordena\u00e7\u00e3o do rel\u00e9.<\/p>\n\n\n\n<h3 class=\"wp-block-heading\" id=\"nomenclature-breakdown\"><strong>Detalhamento da nomenclatura:<\/strong><\/h3>\n\n\n\n<ul class=\"wp-block-list\">\n<li><strong>5<\/strong>\u00a0= Limite de erro composto (m\u00e1ximo de 5%)<\/li>\n\n\n\n<li><strong>P<\/strong>\u00a0= Designa\u00e7\u00e3o da classe de prote\u00e7\u00e3o<\/li>\n\n\n\n<li><strong>20<\/strong> = rated accuracy limit factor at rated burden; the specified composite-error limit is checked at 20 times rated primary current<\/li>\n<\/ul>\n\n\n\n<figure class=\"wp-block-table\"><table class=\"has-fixed-layout\"><thead><tr><th>Classe<\/th><th>Erro composto na ALF<\/th><th>Valores comuns de ALF<\/th><th>Aplica\u00e7\u00e3o t\u00edpica<\/th><\/tr><\/thead><tbody><tr><td>5P<\/td><td>\u22645%<\/td><td>10, 15, 20, 30<\/td><td>Overcurrent protection; verify each relay application<\/td><\/tr><tr><td>10P<\/td><td>\u226410%<\/td><td>10, 15, 20<\/td><td>Overcurrent protection where the scheme accepts 10P<\/td><\/tr><\/tbody><\/table><\/figure>\n\n\n\n<p>O <strong>accuracy limit factor (ALF)<\/strong> is the rated accuracy-limit primary current divided by the rated primary current. A 1000\/5 A, 5P20 CT has a rated accuracy-limit current of 20,000 A at its rated burden. This is a defined steady-state error test condition, not a sharp physical saturation threshold or a guarantee of transient performance.<\/p>\n\n\n\n<p>For a 5P20 CT, the composite error must not exceed 5% at 20 times rated primary current under the specified test conditions and rated burden. Composite error includes waveform distortion and is not a signed \u00b15% ratio-error band. DC offset, remanent flux and the required operating time can impose additional CT requirements.<\/p>\n\n\n\n<p><strong>Initial steady-state screening:<\/strong> if the scheme requires class accuracy at the maximum symmetrical through-fault current, compare the effective ALF at the actual burden with that fault-current multiple.<\/p>\n\n\n\n<p>Required effective ALF \u2265 Maximum symmetrical through-fault current \u00f7 CT rated primary current<\/p>\n\n\n\n<p>For a 12.5 kA symmetrical fault and a 500\/5 A CT, the fault-current multiple is 12,500 \/ 500 = 25.<\/p>\n\n\n\n<p>At rated burden, 5P20 alone does not demonstrate the above 25-times screening requirement; a 5P30 rating would cover that steady-state multiple. Final selection still requires the relay manufacturer\u2019s criteria, actual secondary burden, fault duration and transient assessment. Some protection functions tolerate partial CT saturation, so this screening rule is not a universal relay-sizing formula.<\/p>\n\n\n\n<p>Protection CT selection also involves excitation characteristics, secondary winding resistance and short-time thermal and dynamic ratings. A 5P or 10P designation does not replace these checks. For differential or transient duties, the relay manufacturer may specify PX, PR or a transient class, or give a calculation for an acceptable P-class CT.<\/p>\n\n\n\n\n\n<h2 class=\"wp-block-heading\" id=\"metering-vs-protection-ct-side-by-side-comparison\">CT de medi\u00e7\u00e3o vs. CT de prote\u00e7\u00e3o: compara\u00e7\u00e3o lado a lado<\/h2>\n\n\n\n<p>The following comparison summarizes the different performance specifications. Individual CTs can have additional ratings beyond the class names shown.<\/p>\n\n\n\n<figure class=\"wp-block-table\"><table class=\"has-fixed-layout\"><thead><tr><th>Par\u00e2metro<\/th><th>TC de medi\u00e7\u00e3o<\/th><th>Prote\u00e7\u00e3o CT<\/th><\/tr><\/thead><tbody><tr><td><strong>Fun\u00e7\u00e3o prim\u00e1ria<\/strong><\/td><td>Faturamento de receitas, monitoramento de energia<\/td><td>Detec\u00e7\u00e3o de falhas, opera\u00e7\u00e3o de rel\u00e9<\/td><\/tr><tr><td><strong>Faixa de precis\u00e3o<\/strong><\/td><td>1-120% de classifica\u00e7\u00e3o (classe S)<\/td><td>Rated error limit at ALF \u00d7 rated current and rated burden<\/td><\/tr><tr><td><strong>Especifica\u00e7\u00e3o de erro<\/strong><\/td><td>Erro de propor\u00e7\u00e3o + deslocamento de fase<\/td><td>Rated-current ratio error and composite error at ALF<\/td><\/tr><tr><td><strong>Comportamento de satura\u00e7\u00e3o<\/strong><\/td><td>Specified by FS and burden; not by metering class alone<\/td><td>Specified accuracy-limit and transient characteristics<\/td><\/tr><tr><td><strong>Projeto principal<\/strong><\/td><td>Design depends on accuracy, burden and FS<\/td><td>Design depends on burden, fault and transient duty<\/td><\/tr><tr><td><strong>Classes t\u00edpicas<\/strong><\/td><td>0,2, 0,2S, 0,5, 0,5S, 1,0<\/td><td>5P10, 5P20, 10P10, 10P15<\/td><\/tr><tr><td><strong>Dispositivos conectados<\/strong><\/td><td>Medidores de kWh, analisadores de energia<\/td><td>Rel\u00e9s de prote\u00e7\u00e3o, registradores de falhas<\/td><\/tr><\/tbody><\/table><\/figure>\n\n\n\n<p>A saturated CT produces a distorted secondary waveform. Depending on the relay function and settings, this can delay operation or affect differential stability. The magnitude and timing of the effect must be assessed for the actual protection scheme; they cannot be inferred from the metering class alone.<\/p>\n\n\n\n<p>Separate cores allow the metering burden and protection burden to be specified and tested independently when both functions are needed.<\/p>\n\n\n\n<h2 class=\"wp-block-heading\" id=\"burden-effects-and-practical-selection-considerations\">Efeitos do \u00f4nus e considera\u00e7\u00f5es pr\u00e1ticas sobre a sele\u00e7\u00e3o<\/h2>\n\n\n\n<p>Connected burden affects the voltage the CT must develop and therefore its accuracy and saturation behavior. Include the relay or meter input and the complete secondary wiring circuit. Keep the metering burden within its declared accuracy range, and calculate protection performance at the actual burden.<\/p>\n\n\n\n<h3 class=\"wp-block-heading\" id=\"burden-components-include\"><strong>Os componentes do \u00f4nus incluem:<\/strong><\/h3>\n\n\n\n<ul class=\"wp-block-list\">\n<li>Instrument burden: use the selected meter, relay or transducer input data.<\/li>\n\n\n\n<li>Carga de chumbo: resist\u00eancia do cabo secund\u00e1rio (significativa para longas dist\u00e2ncias)<\/li>\n\n\n\n<li>Connection burden: include terminals and test switches using their actual resistance.<\/li>\n<\/ul>\n\n\n\n<p><strong>Lead burden calculation for a separate outgoing and return pair:<\/strong><br>Lead VA = I<sub>secondary<\/sub>\u00b2 \u00d7 R<sub>loop<\/sub> = I<sub>secondary<\/sub>\u00b2 \u00d7 2 \u00d7 R<sub>one-way<\/sub><\/p>\n\n\n\n<p>Example: a 50 m one-way run with a measured or calculated one-way resistance of 0.35 \u03a9 has a 0.70 \u03a9 loop. At 5 A, its burden is 25 \u00d7 0.70 = 17.5 VA; at 1 A, it is 0.70 VA. Use the cable resistance at the design temperature and the actual return-circuit arrangement.<\/p>\n\n\n\n<p>Isso explica por que os secund\u00e1rios de 1 A s\u00e3o adequados para cabos longos - a carga \u00e9 reduzida em 25 vezes em compara\u00e7\u00e3o com os secund\u00e1rios de 5 A para cabos id\u00eanticos.<\/p>\n\n\n\n<p><strong>Lista de verifica\u00e7\u00e3o de sele\u00e7\u00e3o:<\/strong><\/p>\n\n\n\n<ul class=\"wp-block-list\">\n<li>Obtain maximum and minimum fault currents and the relay operating-time requirements.<\/li>\n\n\n\n<li>\u00a0Soma da carga total, incluindo a resist\u00eancia do chumbo<\/li>\n\n\n\n<li>Verify the declared burden conditions for metering and the effective ALF for protection.<\/li>\n\n\n\n<li>Include credible future fault levels and transient duty using the relay manufacturer\u2019s calculation method.<\/li>\n\n\n\n<li>Choose the metering class and ratio to cover the actual load range and project requirements.<\/li>\n<\/ul>\n\n\n\n\n\n<hr class=\"wp-block-separator has-alpha-channel-opacity\"\/>\n\n\n\n<blockquote class=\"wp-block-quote is-layout-flow wp-block-quote-is-layout-flow\">\n<p><strong>Protection CT specification checks<\/strong><\/p>\n\n\n\n<ul class=\"wp-block-list\">\n<li>For auto-reclosing, assess remanence, fault duration and the required operating cycle.<\/li>\n\n\n\n<li>For differential protection, follow the selected relay\u2019s CT ratio and saturation requirements.<\/li>\n\n\n\n<li>Use the relay\u2019s actual input burden and the complete wiring burden when calculating effective ALF.<\/li>\n\n\n\n<li>Request excitation curves and secondary winding resistance when required by the protection calculation.<\/li>\n<\/ul>\n<\/blockquote>\n\n\n\n<hr class=\"wp-block-separator has-alpha-channel-opacity\"\/>\n\n\n\n<h2 class=\"wp-block-heading\" id=\"dual-core-cts-and-switchgear-integration\">CTs de n\u00facleo duplo e integra\u00e7\u00e3o de pain\u00e9is de distribui\u00e7\u00e3o<\/h2>\n\n\n\n<p>A maioria das instala\u00e7\u00f5es de m\u00e9dia tens\u00e3o exige medi\u00e7\u00e3o e prote\u00e7\u00e3o de cada alimentador. Os TCs de n\u00facleo duplo (ou m\u00faltiplos n\u00facleos) resolvem esse problema incorporando n\u00facleos magn\u00e9ticos separados enrolados no mesmo condutor prim\u00e1rio.<\/p>\n\n\n\n<p>Illustrative dual-core specification, subject to the actual meter, relay and wiring calculations:<\/p>\n\n\n\n<ul class=\"wp-block-list\">\n<li>N\u00facleo 1: classe 0,5S, carga de 10 VA (medi\u00e7\u00e3o de receita)<\/li>\n\n\n\n<li>N\u00facleo 2: 5P20, carga de 30 VA (rel\u00e9s de prote\u00e7\u00e3o)<\/li>\n<\/ul>\n\n\n\n<p>Specify and verify the accuracy and burden of each core separately. Confirm metering FS, protection performance, insulation level and the assembly\u2019s thermal and dynamic withstand ratings. Separate cores do not remove the need to coordinate the complete secondary circuits.<\/p>\n\n\n\n<p>Integra\u00e7\u00e3o com <a href=\"https:\/\/xbrele.com\/pt\/vacuum-circuit-breaker\/\">disjuntores a v\u00e1cuo de m\u00e9dia tens\u00e3o<\/a> requires a common system fault study. ALF is a dimensionless ratio and cannot be compared directly with a breaker breaking-current rating in kA. Evaluate the CT against the maximum through-fault current, its primary rating, actual burden and relay requirements. Separately verify the CT short-time\/dynamic withstand ratings and the breaker interrupting duty. Ask the <a href=\"https:\/\/xbrele.com\/pt\/switchgear-parts\/\">fabricantes de componentes<\/a> for the data needed to complete those checks.<\/p>\n\n\n\n<p>Ao especificar TCs para novas instala\u00e7\u00f5es, forne\u00e7a os seguintes dados ao seu fornecedor:<\/p>\n\n\n\n<ul class=\"wp-block-list\">\n<li>N\u00edvel m\u00e1ximo de falha do sistema (kA)<\/li>\n\n\n\n<li>Faixa de corrente de carga (m\u00ednima a m\u00e1xima)<\/li>\n\n\n\n<li>Dist\u00e2ncia do cabo at\u00e9 os pain\u00e9is de medi\u00e7\u00e3o\/rel\u00e9<\/li>\n\n\n\n<li>Modelos espec\u00edficos de medidores e rel\u00e9s com dados de carga<\/li>\n<\/ul>\n\n\n\n<h2 class=\"wp-block-heading\" id=\"common-ct-specification-errors-and-how-to-avoid-them\">Erros comuns de especifica\u00e7\u00e3o de CT e como evit\u00e1-los<\/h2>\n\n\n\n<p>Review the following specification errors before purchasing or replacing a CT.<\/p>\n\n\n\n<h3 class=\"wp-block-heading\" id=\"error-1-using-metering-ct-for-protection\"><strong>Erro 1: Uso do TC de medi\u00e7\u00e3o para prote\u00e7\u00e3o<\/strong><\/h3>\n\n\n\n<p>A metering class alone does not verify fault-current performance. <strong>Solu\u00e7\u00e3o:<\/strong> select a core with the protection characteristics required by the relay scheme and verify its performance at the actual burden, through-fault current and required operating time.<\/p>\n\n\n\n<h3 class=\"wp-block-heading\" id=\"error-2-ignoring-lead-burden-in-total-burden-calculation\"><strong>Erro 2: Ignorar a carga de chumbo no c\u00e1lculo da carga total<\/strong><\/h3>\n\n\n\n<p>Long secondary circuits can add substantial burden, particularly at 5 A. <strong>Solu\u00e7\u00e3o:<\/strong> calculate the complete loop resistance at the design temperature. Compare 1 A and 5 A options using the actual cable and compatible relay inputs; cable length alone is not a universal selection threshold.<\/p>\n\n\n\n<h3 class=\"wp-block-heading\" id=\"error-3-mismatched-cts-in-differential-protection\"><strong>Erro 3: TCs incompat\u00edveis na prote\u00e7\u00e3o diferencial<\/strong><\/h3>\n\n\n\n<p>Different saturation behavior can produce unwanted differential current during an external fault. <strong>Solu\u00e7\u00e3o:<\/strong> use the relay manufacturer\u2019s ratio-compensation, excitation, winding-resistance and stability requirements. Transformer differential schemes may use different primary CT ratios; identical ratios and knee-point voltages are not a universal requirement.<\/p>\n\n\n\n<h3 class=\"wp-block-heading\" id=\"error-4-overlooking-remanent-flux-in-auto-reclose-schemes\"><strong>Erro 4: Fluxo remanescente n\u00e3o considerado em esquemas de fechamento autom\u00e1tico<\/strong><\/h3>\n\n\n\n<p>Remanent flux can change CT saturation during a subsequent fault or reclosing sequence. <strong>Solu\u00e7\u00e3o:<\/strong> assess the specified operating cycle, system time constant and relay requirements. Select suitable remanence or transient performance where required; a blanket 50% ALF increase is not a verified substitute.<\/p>\n\n\n\n<p>Compreens\u00e3o <a href=\"https:\/\/xbrele.com\/pt\/vacuum-circuit-breaker-ratings\/\">classifica\u00e7\u00f5es do disjuntor a v\u00e1cuo<\/a> helps establish the switching duty. CT accuracy selection is a separate calculation based on the actual through-fault duty and protection scheme, while CT thermal\/dynamic withstand must also cover the clearing duty.<\/p>\n\n\n\n<h2 class=\"wp-block-heading\" id=\"frequently-asked-questions\">Perguntas frequentes<\/h2>\n\n\n\n<h3 class=\"wp-block-heading\" id=\"what-does-5p20-mean-on-a-current-transformer-nameplate\"><strong>O que significa 5P20 na placa de identifica\u00e7\u00e3o de um transformador de corrente?<\/strong><\/h3>\n\n\n\n<p>5P20 specifies a protection CT with a composite-error limit of 5% at a rated accuracy-limit current of 20 times rated primary current, at rated burden and the specified test conditions. For a 400\/5 A CT this test current is 8,000 A. It does not identify an exact saturation threshold or guarantee performance for every transient waveform.<\/p>\n\n\n\n<h3 class=\"wp-block-heading\" id=\"can-a-0-5-class-metering-ct-feed-protection-relays\"><strong>Um TC de medi\u00e7\u00e3o de classe 0,5 pode alimentar rel\u00e9s de prote\u00e7\u00e3o?<\/strong><\/h3>\n\n\n\n<p>Do not assume that a Class 0.5 metering core is suitable for protection. Its class establishes metering accuracy under specified conditions, not the fault-current performance required by a relay. Use a core whose declared protection characteristics have been checked against the particular relay scheme.<\/p>\n\n\n\n<h3 class=\"wp-block-heading\" id=\"when-should-i-specify-0-2s-instead-of-standard-0-2-class\"><strong>Quando devo especificar 0,2S em vez da classe 0,2 padr\u00e3o?<\/strong><\/h3>\n\n\n\n<p>Consider 0.2S when accurate measurement is required at low load, especially between 1% and 5% of rated CT current. The required class also depends on the utility or project metering specification. Check the limits at each current test point and the declared burden range; 0.2S does not mean \u00b10.2% at every current.<\/p>\n\n\n\n<h3 class=\"wp-block-heading\" id=\"how-does-burden-affect-protection-ct-performance\"><strong>Como a carga afeta o desempenho do CT de prote\u00e7\u00e3o?<\/strong><\/h3>\n\n\n\n<p>A lower external burden generally increases the effective ALF of a P-class CT, but winding resistance must be included. For mainly resistive burdens, ALF<sub>actual<\/sub> \u2248 ALF<sub>classificado<\/sub> \u00d7 (R<sub>ct<\/sub> + R<sub>rated burden<\/sub>) \/ (R<sub>ct<\/sub> + R<sub>actual burden<\/sub>). Therefore, halving external burden does not generally double ALF. Use manufacturer data for the actual circuit and transient duty.<\/p>\n\n\n\n<h3 class=\"wp-block-heading\" id=\"what-is-knee-point-voltage-and-why-does-it-matter\"><strong>O que \u00e9 a tens\u00e3o do ponto de joelho e por que ela \u00e9 importante?<\/strong><\/h3>\n\n\n\n<p>Knee-point voltage characterizes the bend in the secondary excitation curve. The IEC convention uses the point at which a 10% voltage increase produces a 50% increase in exciting current. It is particularly relevant when specifying PX-type CTs. Apply the relay manufacturer\u2019s knee-point, excitation-current and winding-resistance requirements; a simple voltage comparison does not establish suitability for every protection scheme.<\/p>\n\n\n\n<h2 class=\"wp-block-heading\" id=\"how-do-iec-and-ieee-ct-accuracy-standards-differ\"><strong>Quais s\u00e3o as diferen\u00e7as entre os padr\u00f5es de precis\u00e3o de CT da IEC e do IEEE?<\/strong><\/h2>\n\n\n\n<p>IEC 61869-2 includes metering classes such as 0.2 and 0.5 and protection classes such as 5P, 10P and PX. IEEE C57.13 uses a different set of designations, including voltage-based relaying classes such as C100 and C200. The test conditions and burden definitions differ. Specify the standard required by the project and compare the full ratings rather than treating the class names as direct equivalents.<\/p>\n\n\n\n<h3 class=\"wp-block-heading\" id=\"what-accuracy-class-suits-capacitor-bank-switching-applications\"><strong>Qual classe de precis\u00e3o \u00e9 adequada para aplica\u00e7\u00f5es de comuta\u00e7\u00e3o de banco de capacitores?<\/strong><\/h3>\n\n\n\n<p>A capacitor bank can need phase overcurrent, earth-fault and sensitive unbalance protection, each with different measurement duties. Select CT ratio, accuracy, burden and transient performance from the bank configuration, expected unbalance level and relay instructions. A universal 5P10 or 0.5 recommendation cannot establish suitability for all capacitor banks.<\/p>\n\n\n\n<hr class=\"wp-block-separator has-alpha-channel-opacity\"\/>\n\n\n\n<p><em>Para obter suporte para a especifica\u00e7\u00e3o de TC de acordo com os requisitos do seu painel de distribui\u00e7\u00e3o, entre em contato com a equipe de engenharia da XBRELE por meio de <a href=\"https:\/\/xbrele.com\/pt\/contact\/\">a p\u00e1gina de contato t\u00e9cnico<\/a>. Fornecemos solu\u00e7\u00f5es integradas que combinam&nbsp;<a href=\"https:\/\/xbrele.com\/pt\/what-is-a-vacuum-interrupter\/\">tecnologia de interruptor a v\u00e1cuo<\/a>&nbsp;com transformadores de instrumentos devidamente coordenados para um desempenho confi\u00e1vel de medi\u00e7\u00e3o e prote\u00e7\u00e3o, incluindo <a href=\"https:\/\/xbrele.com\/pt\/transformer-protection-vcb-inrush-coordination-mistakes\/\">verifica\u00e7\u00f5es de coordena\u00e7\u00e3o de rel\u00e9s<\/a> para alimentadores de transformadores.<\/em><\/p>\n\n\n\n<p><strong>Technical references:<\/strong> <a href=\"https:\/\/webstore.iec.ch\/en\/publication\/6050\" target=\"_blank\" rel=\"noopener\">IEC 61869-2:2012 \u2014 inductive current transformers<\/a>; <a href=\"https:\/\/library.e.abb.com\/public\/194811e319ce2bb7c2256f9e00324a2f\/applicationCT_accuracylimitfactorENa.pdf\" target=\"_blank\" rel=\"noopener\">ABB \u2014 calculation of actual accuracy limit factor<\/a>; <a href=\"https:\/\/library.e.abb.com\/public\/eb71e99b34df40fac2256f230034b639\/applicationCTreqENa.pdf\" target=\"_blank\" rel=\"noopener\">ABB \u2014 CT requirements for non-directional overcurrent protection<\/a>; <a href=\"https:\/\/techdoc.relays.protection-control.abb\/r\/615-series-Technical-Manual\/5.0-FP1-IEC\/en-US\/Current-transformer-requirements-for-transformer-differential-protection?contentId=IOsDImuRMieCseqaGT6Irw\" target=\"_blank\" rel=\"noopener\">ABB \u2014 transformer differential CT requirements<\/a>. The ABB application notes explain calculation methods; final selection must use the applicable project standard and the selected relay\u2019s current instructions.<\/p>\n\n\n\n<hr class=\"wp-block-separator has-alpha-channel-opacity\"\/>","protected":false},"excerpt":{"rendered":"<p>Understand CT accuracy classes 0.2S, 0.5S, 5P and 10P, including rated burden, effective ALF and checks for metering and protection applications.<\/p>","protected":false},"author":3,"featured_media":4294,"comment_status":"open","ping_status":"open","sticky":false,"template":"","format":"standard","meta":{"_gspb_post_css":"\/* XBRELE: keep the image-free article hero readable. *\/\nbody.postid-2907 #main > .hero-section[data-type=\"type-2\"] {\n  background-color: var(--theme-palette-color-4, #080c0e);\n  --theme-text-color: #e6eef1;\n}\nbody.postid-2907 #main > .hero-section[data-type=\"type-2\"] .page-description {\n  color: var(--theme-text-color);\n}\n","footnotes":""},"categories":[27],"tags":[],"class_list":["post-2907","post","type-post","status-publish","format-standard","has-post-thumbnail","hentry","category-switchgear-parts-knowledge"],"blocksy_meta":[],"_links":{"self":[{"href":"https:\/\/xbrele.com\/pt\/wp-json\/wp\/v2\/posts\/2907","targetHints":{"allow":["GET"]}}],"collection":[{"href":"https:\/\/xbrele.com\/pt\/wp-json\/wp\/v2\/posts"}],"about":[{"href":"https:\/\/xbrele.com\/pt\/wp-json\/wp\/v2\/types\/post"}],"author":[{"embeddable":true,"href":"https:\/\/xbrele.com\/pt\/wp-json\/wp\/v2\/users\/3"}],"replies":[{"embeddable":true,"href":"https:\/\/xbrele.com\/pt\/wp-json\/wp\/v2\/comments?post=2907"}],"version-history":[{"count":5,"href":"https:\/\/xbrele.com\/pt\/wp-json\/wp\/v2\/posts\/2907\/revisions"}],"predecessor-version":[{"id":4291,"href":"https:\/\/xbrele.com\/pt\/wp-json\/wp\/v2\/posts\/2907\/revisions\/4291"}],"wp:featuredmedia":[{"embeddable":true,"href":"https:\/\/xbrele.com\/pt\/wp-json\/wp\/v2\/media\/4294"}],"wp:attachment":[{"href":"https:\/\/xbrele.com\/pt\/wp-json\/wp\/v2\/media?parent=2907"}],"wp:term":[{"taxonomy":"category","embeddable":true,"href":"https:\/\/xbrele.com\/pt\/wp-json\/wp\/v2\/categories?post=2907"},{"taxonomy":"post_tag","embeddable":true,"href":"https:\/\/xbrele.com\/pt\/wp-json\/wp\/v2\/tags?post=2907"}],"curies":[{"name":"wp","href":"https:\/\/api.w.org\/{rel}","templated":true}]}}