Hai bisogno delle specifiche complete?
Scarica il nostro Catalogo prodotti 2025 per disegni dettagliati e parametri tecnici di tutti i componenti dei quadri elettrici.
Richiedi il catalogo
Scarica il nostro Catalogo prodotti 2025 per disegni dettagliati e parametri tecnici di tutti i componenti dei quadri elettrici.
Richiedi il catalogo
Scarica il nostro Catalogo prodotti 2025 per disegni dettagliati e parametri tecnici di tutti i componenti dei quadri elettrici.
Richiedi il catalogo

A 12 kV vacuum circuit breaker arrived at a cement plant in the Andes, installed at 2,800 meters elevation. Six months later, it failed during routine switching—not from manufacturing defect, but from flashover across insulation surfaces that performed flawlessly during factory testing at sea level.
The root cause: inadequate Basic Impulse Level for combined high-altitude and cement dust stress. Standard 75 kV BIL, sufficient at 1,000 meters in clean air, could not withstand transient overvoltages when air density dropped 30% and pollution coated every exposed surface.
Insulation coordination prevents exactly this failure mode. It matches equipment dielectric strength to actual voltage stresses—accounting for where equipment operates, not just what voltage it carries. BIL quantifies transient overvoltage withstand capability, expressed as peak kilovolts for a standardized lightning impulse waveform.
Three factors dominate medium-voltage BIL selection: altitude (air density reduction), pollution severity (surface contamination), and cable system characteristics (surge impedance matching). This guide delivers practical selection methods for each, with IEC-based calculations and decision tables engineers can apply directly to procurement specifications.
For foundational understanding of vacuum circuit breaker operating principles, the linked resource covers arc extinction mechanisms and contact design that influence insulation requirements.
Basic Impulse Level defines the peak voltage magnitude that electrical equipment must withstand during transient overvoltage events, particularly lightning strikes and switching surges. For medium-voltage systems between 3.6 kV and 36 kV, BIL ratings typically range from 40 kV to 170 kV—representing a 5:1 to 6:1 ratio between impulse withstand and nominal operating voltage.
The physics centers on the voltage-time relationship during impulse events. A standard lightning impulse rises to peak in 1.2 microseconds and decays to 50% in 50 microseconds (the 1.2/50 μs waveform defined by IEC 60060-1). This rapid voltage spike stresses insulation differently than continuous power frequency voltage.
Three voltage stress categories require coordination:
| Stress Type | Durata | Typical Magnitude | Source |
|---|---|---|---|
| Power frequency | Continuous | 1.0 × rated voltage | Normal operation |
| Temporary overvoltage | Seconds to minutes | 1.2–1.5 × rated voltage | Fault clearing, load rejection |
| Transient overvoltage | Microsecondi | 3–12 × rated voltage | Lightning, switching |
According to IEC 60071-1 (Insulation coordination—Part 1: Definitions, principles, and rules), standard BIL values follow a preferred series. For Um = 36 kV systems, the standard BIL is 170 kV, while Um = 12 kV systems typically require BIL ratings of 75 kV or 95 kV depending on neutral grounding configuration and expected overvoltage severity.
Dielectric withstand capability depends on three interconnected factors: insulation material breakdown strength (typically 20–40 kV/mm for XLPE cables), geometric configuration determining electric field distribution, and environmental conditions including atmospheric pressure.

Standard BIL Ratings for Medium-Voltage Equipment:
| Tensione nominale (kV) | Standard BIL Options (kV peak) |
|---|---|
| 3.6 | 20, 40 |
| 7.2 | 40, 60 |
| 12 | 60, 75, 95 |
| 17.5 | 75, 95 |
| 24 | 95, 125, 145 |
| 36 | 145, 170 |
Selection between options depends on system grounding method, lightning exposure frequency, and—critically—site environmental factors that reduce effective dielectric strength.
Air density decreases with elevation, reducing dielectric strength proportionally. At sea level (1,013 hPa), standard air provides baseline insulation capacity. As altitude increases, molecules spread farther apart, and breakdown voltage drops. Equipment rated at 75 kV BIL at sea level may effectively provide only 60 kV BIL at 3,000 meters without correction.
The correction becomes mandatory above 1,000 meters per IEC 60071-2. The formula:
K_a = e^(H/8150)
Where K_a equals the altitude correction factor and H represents altitude in meters.

Pre-Calculated Altitude Correction Factors:
| Altitude (m) | Correction Factor K_a | Effective BIL Reduction |
|---|---|---|
| 1,000 | 1.00 (reference) | 0% |
| 1,500 | 1.06 | 6% |
| 2,000 | 1.13 | 13% |
| 2,500 | 1.20 | 20% |
| 3,000 | 1.28 | 28% |
| 3,500 | 1.36 | 36% |
| 4,000 | 1.45 | 45% |
Practical application: A 12 kV VCB destined for a 2,500 m site requires BIL of at least 75 × 1.20 = 90 kV. Select the next standard rating: 95 kV BIL.
Two implementation options exist for altitude compensation. First, specify higher BIL class equipment—95 kV instead of 75 kV for the same voltage rating. Second, request extended creepage and clearance distances proportionally increased. Most produttori di interruttori automatici sottovuoto offer altitude-rated variants. Specify installation altitude on RFQ documents—retrofitting costs far more than correct initial specification.
[Expert Insight: Altitude Selection]
- Sites above 2,000 m should default to next-higher BIL class regardless of calculation results
- Dry, low-humidity high-altitude environments experience faster voltage recovery after partial discharges
- Combined altitude and pollution effects compound—apply both corrections sequentially
- Request manufacturer altitude test certificates for installations above 3,000 m
Surface contamination—salt spray, cement dust, industrial particulates, agricultural chemicals—creates conductive paths when combined with moisture. IEC 60815 defines four pollution severity levels based on environmental exposure:
| Pollution Level | Descrizione | Typical Environments |
|---|---|---|
| I – Light | Minimal industrial pollution, no salt | Rural areas, low traffic density |
| II – Medium | Moderate industrial or traffic exposure | Suburban zones, light industrial |
| III – Heavy | Dense industrial activity, coastal 1–10 km | Heavy manufacturing, near coastline |
| IV – Very Heavy | Conductive dust, direct salt spray, chemicals | Cement plants, coastal facilities, chemical processing |
Creepage distance—the surface path length between live parts and ground—must increase with pollution severity:
| Pollution Level | Minimum Creepage (mm/kV) |
|---|---|
| I – Light | 16 |
| II – Medium | 20 |
| III – Heavy | 25 |
| IV – Very Heavy | 31 |
Calculation example: 12 kV equipment in Level III environment requires minimum creepage of (12 ÷ √3) × 25 = 173 mm.

Indoor equipment in properly sealed, climate-controlled switchgear rooms typically qualifies for Pollution Level I or II. However, field experience reveals that poorly ventilated indoor spaces—particularly in mining and cement operations—accumulate contamination over 5–10 years that creates surface tracking paths. Assess actual air quality rather than assuming indoor automatically means clean.
Per outdoor versus indoor VCB selection, pollution level determination significantly affects both initial equipment cost and long-term reliability.
High-altitude sites frequently coincide with severe pollution—mining operations at 3,500 m, cement plants in mountain valleys, remote industrial facilities far from grid infrastructure. Both derating factors compound.
Sequential application method:
Worked example: 24 kV outdoor VCB at 3,500 m elevation in a cement plant (Pollution Level IV):
Combined Selection Decision Matrix:
| Site Condition | Azione raccomandata |
|---|---|
| ≤1,000 m, Pollution I–II | Standard BIL, standard creepage |
| 1,000–2,000 m, Pollution I–II | Next higher BIL class |
| >2,000 m, any pollution | Calculate exact K_a, specify altitude-rated equipment |
| Pollution III–IV, any altitude | Extended creepage insulators, consider silicone housing |
| Combined high altitude + high pollution | Both corrections applied, manufacturer consultation required |
Silicone rubber insulator housings outperform porcelain in Level III and IV environments due to hydrophobic surface properties that cause water to bead rather than form conductive films.
[Expert Insight: Harsh Environment Deployment]
- Field failure data shows combined altitude-pollution effects account for 60%+ of insulation failures above 2,000 m
- Silicone housings maintain hydrophobicity for 15–20 years; porcelain requires periodic cleaning
- Specify pollution level in procurement documents—manufacturers cannot guess site conditions
- Regular insulation resistance testing (annually minimum) catches degradation before failure
Power cables present different insulation coordination challenges than air-insulated equipment. XLPE and EPR cables have higher dielectric constant (ε_r ≈ 2.3–3.5), lower surge impedance (20–50 Ω versus 300–400 Ω for overhead lines), and minimal BIL margin beyond rated values.
Standard Cable BIL Ratings:
| Cable Rated Voltage U₀/U (kV) | BIL (kV peak) |
|---|---|
| 3.6/6 | 60 |
| 6/10 | 75 |
| 8.7/15 | 95 |
| 12/20 | 125 |
| 18/30 | 170 |
When traveling waves encounter impedance discontinuity—cable-to-overhead line junction, open cable termination—voltage reflection occurs. At an open end, voltage can theoretically double. Cable terminations and switchgear connected to cables experience higher transient stresses than equipment in purely overhead-line systems.

Protection strategies:
Short cable runs (<50 m) exhibit near-lumped capacitance behavior with reduced wave reflection concern. Long cable feeders (>200 m) require distributed parameter analysis for surge coordination. For underground distribution networks with mixed cable/overhead sections, place surge arresters at every cable-line junction.
Il Lista di controllo VCB RFQ includes cable coordination requirements that procurement specialists should verify before finalizing specifications.
Step 1: Determine System Voltage Class
Identify maximum system voltage (U_m) per local grid standards and equipment location within the network.
Step 2: Select Base BIL
Choose standard BIL from IEC 60071-1 tables for the voltage class. Effectively grounded systems permit lower BIL; ungrounded or resistance-grounded systems require higher ratings.
Step 3: Calculate Altitude Correction
Apply K_a = e^(H/8150) for installations above 1,000 m. Round up to next standard BIL value.
Step 4: Determine Pollution Severity
Assess site environment using IEC 60815 criteria. When uncertain, select one level higher than initial assessment.
Step 5: Calculate Minimum Creepage
Multiply phase-to-ground voltage by creepage factor for pollution level.
Step 6: Map Equipment Coordination Chain
Verify BIL ratings across: Transformer (highest) → Switchgear (intermediate) → Cables (protected by arresters) → Surge arresters (protective level below all equipment BIL).
Step 7: Specify Surge Arrester Protective Levels
Arrester residual voltage must remain 15–20% below protected equipment BIL under maximum discharge current.
Step 8: Document Complete Specifications
Include altitude, pollution level, required BIL, creepage distance, and arrester coordination in procurement documents.
The protective margin calculation follows: Margin (%) = [(BILequipment − Vprotective level) ÷ Vprotective level] × 100. For lightning impulse protection, IEC 60071-2 recommends minimum margins of 15–25% depending on installation criticality and altitude correction factors.
Failure Pattern 1: Altitude Underestimation
Equipment specified for sea-level performance fails at high-altitude mines or mountain facilities. The 28% BIL reduction at 3,000 m exceeds standard design margins. Switching flashover occurs during normal operations, not just fault conditions.
Prevenzione: Always document installation altitude on procurement specifications. Request altitude-rated equipment or next-higher BIL class.
Failure Pattern 2: Pollution Creep
Clean-room assumptions for indoor switchgear ignore ventilation realities. Dust infiltration over 5–10 years creates surface tracking paths that appear suddenly after extended rain or humidity events.
Prevenzione: Conduct annual insulation resistance testing. Establish cleaning schedules for dusty environments. Consider sealed switchgear designs for Level III+ locations.
Failure Pattern 3: Cable Termination Neglect
Surge arresters installed at transformer terminals but missing at cable-switchgear junctions. The cable termination—weakest insulation link—fails during switching transients rather than lightning events.
Prevenzione: Install surge arresters at every cable termination. Verify arrester energy rating matches expected surge duty.
Commissioning Verification Checklist:
Proper insulation coordination translates environmental reality into equipment specifications. BIL selection without altitude correction guarantees eventual failure at elevation. Ignoring pollution severity invites surface tracking and flashover. Dismissing cable surge impedance characteristics leaves terminations vulnerable.
Critical specification elements for procurement documents:
Standards to reference: IEC 60071-1/2 (insulation coordination), IEC 60815 (pollution classification), IEC 62271-1 (high-voltage switchgear), IEEE C62.82.1 (North American applications).
Manufacturer consultation matters for challenging sites. Custom altitude ratings, extended creepage options, and silicone housing upgrades require application engineering support beyond standard catalog offerings.
XBRELE provides altitude-rated vacuum circuit breakers tested to 4,000 m elevation, pollution-resistant designs with silicone housings for Level IV environments, and technical specification assistance for complex insulation coordination requirements. Contact our engineering team for insulation coordination review on your next medium-voltage project.
Riferimento esterno: IEC 60071-1 Insulation Coordination Standard — International Electrotechnical Commission official technical documentation.
Q: What is the difference between BIL and power frequency withstand voltage?
A: BIL measures resistance to fast transient surges lasting microseconds, while power frequency withstand tests sustained voltage stress at 50/60 Hz for one minute—equipment must pass both tests, as each evaluates different insulation failure mechanisms.
Q: At what altitude does insulation derating become mandatory?
A: IEC standards require altitude correction above 1,000 meters; at 2,000 m the correction factor reaches 1.13, meaning equipment needs approximately 13% higher BIL than sea-level ratings to maintain equivalent protection.
Q: Can indoor switchgear ignore pollution level requirements?
A: Not reliably—poorly ventilated indoor spaces, especially in industrial facilities handling powders or located near coastal areas, can accumulate contamination over years that creates tracking paths during high-humidity conditions.
Q: How do I determine the correct pollution level for my installation site?
A: Evaluate proximity to pollution sources (coastline distance, industrial emissions, agricultural activity), local climate patterns (humidity, rainfall frequency), and historical contamination data from nearby installations; when assessment is uncertain, select one level higher than initial estimate.
Q: Why do cable terminations fail more frequently than other insulation points?
A: Cable terminations experience voltage doubling from surge reflection at impedance mismatches between cable (20–50 Ω) and connected equipment (300+ Ω), making them the weakest coordinated link unless protected by properly rated surge arresters.
Q: Should I specify altitude-rated equipment or use extended creepage for high-altitude sites?
A: Altitude-rated equipment with higher BIL class is generally preferred above 2,000 m because it addresses both internal and external insulation simultaneously; extended creepage alone only improves external surface performance while leaving internal insulation margins unchanged.
Q: How often should insulation resistance be tested in harsh environments?
A: Annual testing represents minimum practice for Pollution Level III and IV environments, with quarterly testing recommended for cement plants, coastal facilities, and other locations where contamination accumulates rapidly between cleaning cycles.