Hai bisogno delle specifiche complete?
Scarica il nostro Catalogo prodotti 2025 per disegni dettagliati e parametri tecnici di tutti i componenti dei quadri elettrici.
Richiedi il catalogo
Scarica il nostro Catalogo prodotti 2025 per disegni dettagliati e parametri tecnici di tutti i componenti dei quadri elettrici.
Richiedi il catalogo
Scarica il nostro Catalogo prodotti 2025 per disegni dettagliati e parametri tecnici di tutti i componenti dei quadri elettrici.
Richiedi il catalogo
Understand 50BF initiation, current checks, 52a limitations, retrip and selective backup action, with a commissioning evidence matrix for MV VCB feeders.
A trip command issued to a vacuum circuit breaker tells the breaker’s operating mechanism to open. It does not, by itself, confirm that the main contacts have separated, that the arc has been extinguished, or that fault current has ceased to flow. This distinction is the foundation of breaker-failure protection: a scheme designed to detect when a breaker has received a valid trip but has not successfully interrupted current, and to take selective backup action before the fault damages equipment further or causes a wider outage.
This article explains how that detection works, why current measurement and auxiliary-contact status serve different and complementary roles, how retrip and backup trip are selected and sequenced, how the timing budget is built, and how the scheme is verified through controlled commissioning tests.
When a protection relay determines a fault is present and issues a trip output to a circuit breaker, the expectation is that the breaker will open its main contacts and interrupt current flow within its rated interrupting time. For a medium-voltage vacuum circuit breaker, that interrupting sequence—from trip-coil energization through contact separation and arc extinction—takes a finite and measurable duration. Under most conditions the breaker performs this correctly. Under a subset of conditions it does not.
Breaker failure, as a protective concept, addresses the situation where the breaker has received a legitimate trip command but current continues to flow in the primary circuit. The failure can arise from several physical causes: a mechanically jammed operating mechanism that prevents contact opening, a failed trip coil that never transmits force to the latch, a loss of DC control supply that makes the trip-coil circuit dead, or a main contact failure where contacts part but do not establish sufficient dielectric withstand to prevent current continuation. The failure mode matters for root-cause analysis but not necessarily for the detection logic, which is concerned with the observable result: persistent current after a trip has been commanded.
Without a local breaker-failure scheme, the upstream protection must eventually detect the persistent fault and clear it. That upstream device may be slower by design—it is coordinated to allow the downstream breaker time to operate—and it protects a wider zone. Waiting for upstream protection to clear a local breaker failure means longer fault duration, greater equipment stress, more extensive arc energy, and loss of a larger section of the system than the fault originally required. A correctly coordinated local breaker-failure scheme can reduce that delay by detecting failed clearing and issuing the selected backup action.
The scheme is commonly called a 50BF scheme, referencing the ANSI/IEEE function number for the breaker-failure protective function. Other naming conventions and relay manufacturer designations use terms such as BFI (breaker failure initiation), BFR (breaker failure relay), or describe the current supervision element separately from the timer logic. The current-detection element within the scheme may carry the 50BF designation, or the scheme as a whole may be referred to that way. What is important is that 50BF is not an inherent function built into the vacuum circuit breaker itself. It is a protective relay function that monitors the breaker’s performance from the outside. It is also not a synonym for the primary overcurrent elements 50 or 51, which detect fault current and issue the trip command in the first place. Those primary functions cause the trip; the 50BF scheme evaluates whether the trip succeeded.

A breaker-failure scheme operates using three conceptually distinct inputs, each with a different role and different physical origin.
Breaker Failure Initiation (BFI) is the signal that tells the breaker-failure logic that a trip has been commanded and that the scheme should begin evaluating whether interruption has occurred. BFI is typically derived from the same protection functions that generated the trip output—overcurrent elements, earth-fault elements, differential elements, or other protective functions that are authorized to open the breaker. Not every trip output in a panel will necessarily be mapped to BFI. A scheme may distinguish between eligible initiating functions, whose trips should start the failure timer, and non-eligible functions whose trips either do not warrant failure protection or require separate handling. The mapping of which functions generate BFI is a design decision that must be documented in the protection coordination study, not assumed from relay capability alone.
Current supervision is the ongoing measurement of whether fault current is still present in the primary circuit. The most common implementation uses a current threshold element—the 50BF element—that monitors current magnitude via the same current transformers used for primary protection. If current remains above the pickup threshold after BFI is received and the timer expires, the scheme declares failure and issues backup outputs. This element derives current evidence from the CT secondary measurements, so correct CT location, mapping and signal quality matter. It does not directly observe whether the contacts are open or closed; it observes the consequence of that state.
Breaker status (52a) is the signal from the breaker’s auxiliary contact that indicates the mechanical position of the operating mechanism. The 52a contact is normally closed when the breaker is in the closed position and opens when the operating mechanism travels to the open position. It provides feedback about mechanism movement, not about contact interruption directly.

The critical engineering limitation is that 52a status and successful current interruption are not the same thing. The 52a contact reflects the mechanical state of the breaker mechanism as reported through the auxiliary contact linkage. That linkage can disagree with the actual state of the main contacts in several ways. An auxiliary contact can fail mechanically and report open when the main contacts have not moved. The operating mechanism can travel to the open position—changing the 52a state—while a main contact is physically stuck, a weld from an earlier interruption holds one pole, or a component failure means the main contact displacement is insufficient to establish interruption-grade dielectric clearance. In all these cases, the 52a contact may indicate the breaker is open while current continues to flow.
This is why protection engineers generally treat 52a as a corroborating signal rather than definitive interruption proof, and why current supervision remains the primary evidence of failure in most medium-voltage feeder applications. The SEL paper on advances in breaker-failure protection notes explicitly that 52a can indicate open while main contacts remain closed, and it warns against over-reliance on status feedback for current interruption evidence.
The scheme logic combining these two signals is application-specific rather than universal. A simple scheme may require both the timer expiry and current above threshold to assert backup action. A scheme covering low-current protection trips—such as a transformer mechanical protection trip with primary current below the failure detector threshold—may need an explicitly supervised 52a path. A manual or local mechanical opening does not automatically initiate breaker-failure protection; initiation eligibility follows the approved scheme. There is no single AND/OR logic that applies to all installations. The scheme designer must work from the specific current levels, the CT ratios and accuracy, the breaker type, and the load conditions.
CT limitations also affect the quality of current evidence. A CT that is saturating during a close-in fault will have distorted secondary current output, potentially causing the current element to drop out momentarily even though primary current continues. A lost or incorrectly mapped current channel can remove or distort that evidence. CT secondary circuits should not be described or treated as fused voltage-transformer circuits. These conditions affect how the scheme behaves and need to be considered during design and commissioning verification.

The scheme can provide an optional earlier retrip stage and a later selective backup stage if failed-clearing evidence persists. Their timing and qualification are separate design choices.
Retrip is an optional first action where the scheme issues a second trip command to the failed breaker itself, typically through a different output path or a second trip coil if one is fitted. The rationale for retrip is that some failure modes are recoverable with a second attempt. If the initial trip failed because of a momentary lapse in control-circuit continuity, a DC disturbance that prevented sufficient trip-coil energization, or a relay output that did not make reliable contact, a second trip command may succeed where the first did not. Retrip is therefore useful for failures of the trip initiation path, not for mechanical failures of the breaker mechanism. If the mechanism is jammed, the latch is broken, or the contacts are welded, a second trip command to the same coil does the same thing the first did, which is nothing useful.
Where a second trip coil is provided—some MV breakers allow dual trip coils operated from separate DC supplies—the retrip can target the second coil and thereby address failures of the first coil circuit. This extends the recovery capability to include coil failures. However, this only works if the second coil and its DC supply are genuinely independent. If both coils share the same DC bus or the same fuse, a loss of that DC supply defeats both. The independence of the second trip path—separate DC source, separate fuses, separate wiring routed separately—must be assessed in the project design, not assumed because two trip coils are physically present.
Backup trip is the action taken to remove all sources of current feeding the fault zone when the failed breaker cannot be cleared locally. This requires tripping adjacent breakers, upstream breakers, or remote breakers—any device that feeds current into the zone containing the failed breaker—until the persistent fault is de-energized. The selection of which breakers must be tripped is not a matter of tripping everything in sight. That approach would cause wider outages than necessary and is a failure of scheme selectivity. The correct selection comes from analyzing the network topology: specifically, which sources feed current through the fault zone.
For a typical MV feeder breaker in a radial distribution system, the backup trip often targets only the upstream bus section breaker or incomer, since the feeder breaker is the only path forward and there is no backfeed from the feeder side. For a breaker in a ring or meshed network, or in a substation with multiple incomers, multiple transfer connections, or embedded generation, the analysis is more complex. Each source that can feed current into the failed breaker’s zone must be interrupted. A source outside that zone—a feeder on a different bus section not connected to the fault path—should not be tripped, as that would cause unnecessary loss of supply.
This topology-based selection must be documented in the protection design and implemented in the relay logic or in the scheme’s output routing. It may involve direct wiring from the breaker-failure relay to adjacent breaker trip coils, transfer trip via communication channels to remote breakers, or bus-zone protection schemes that perform zone-based backup isolation. Each of these paths—wiring, communications, relay outputs—must be verified independently. A transfer trip path that is wired but whose communication link is not tested has not been verified.
Lockout and auto-reclose functions interact with backup trip and require deliberate design decisions. After a backup trip clears a breaker failure, automatic reclosure is generally not appropriate without inspection, since the failed breaker’s condition is unknown. Lockout relay (86) operation to block reclosure is common. These choices are application-specific and must be coordinated with the system’s operational philosophy.

The breaker-failure timer is not simply a delay chosen to be longer than the breaker’s rated interrupting time. It is built from a sum of time components, each of which must be understood and accounted for in the scheme’s total timing design.
The starting reference matters. In schemes where BFI starts the timer at the moment the initiating protection function picks up and issues the trip, the timer begins before the trip coil has even had a chance to operate. In schemes where BFI is derived from a confirmed trip output—with the timer starting after the trip command is verified—the reference point is different. In sealed-initiation schemes, the BFI is latched so that even if the initiating protection element resets before the timer expires, the timer continues running. In non-sealed schemes, loss of the initiating condition resets the timer. The SEL busbar and breaker-failure paper distinguishes these variants and shows that seal-in behavior changes both the scheme’s resilience and its exposure to spurious operation. These differences must be explicitly designed rather than inferred from default relay settings.
Working forward from the start reference, the timer must at minimum exceed the maximum time the breaker could legitimately take to interrupt. That maximum includes the full tolerance range of the breaker’s interrupting time under its rated operating conditions. Beyond that, the timer must add time for the current-detection element to reset after current is actually interrupted. A current element does not drop out instantaneously; it has a dropout delay, a filter time, and a processing cycle. If the current element is still indicating current during its dropout transient while the breaker has already successfully interrupted, the scheme should not declare failure. The timer must be long enough that successful interruption is unambiguously reflected in the current element’s output before the timer expires.
Additional contributions to the timing budget come from relay processing cycles, input scanning times, output contact operation delays, and any communications paths in the scheme. Each of these adds uncertainty to the actual elapsed time between a real event and the scheme’s response. Practical timing design therefore includes a margin that accounts for these uncertainties, so that the scheme does not operate on successful clearing and does not delay excessively on genuine failure.
After the timer expires and the backup trip output is issued, more time elapses before fault clearing is complete. The backup relay’s output must operate, travel through any transfer-trip communication path if the target breaker is remote, energize the target breaker’s trip coil, and allow that backup breaker to interrupt. If BFI and the primary trip share the same time reference, total fault-clearing time is the sum of primary protection operating time, the breaker-failure timer, backup output and communication delays, and backup-breaker interrupting time. Where BFI is established later, also include the trip-to-BFI initiation or transmission delay. Build all intervals on one documented reference so that delayed confirmed-trip initiation is neither omitted nor counted twice. This total determines the actual fault energy exposure during the event and is the figure that matters for equipment withstand and arc-flash hazard assessment.
No specific timer values, current thresholds, or calculation constants are appropriate here because they depend on the specific relay model, CT class and ratio, breaker rated interrupting time, communication technology, and system protection coordination study. These values must come from the project’s relay settings documentation and protection coordination engineer.
The following matrix summarizes the inputs, evidence paths, logic qualification, expected actions, and test requirements for a breaker-failure scheme on an MV VCB feeder. It is intended as a fillable working document for design review and commissioning, not as a relay settings record. Protection logic, relay settings, and scheme parameters are owned by the project’s relay and coordination engineer.
For information on XBRELE vacuum circuit breakers, including available configurations and control interface options, see the XBRELE vacuum circuit breaker catalogue. For project-specific documentation, configuration requirements, or technical review, contact XBRELE directly via the project inquiry page.
| Test Case | Input Condition | Physical Source | Logic Qualification | Expected Action | Test Evidence Required |
|---|---|---|---|---|---|
| Healthy clear | Fault present, primary protection trips, breaker opens successfully | CT current drops below 50BF threshold before timer expires; 52a opens | Healthy clearing removes the failure qualification and resets or blocks escalation according to the logic | No backup trip; scheme resets | Confirm no backup output operated; record timer/reset behavior and the designed current/status response |
| Persistent current after trip | Fault present, trip commanded, breaker fails to interrupt | CT current remains above threshold; 52a may or may not change | Timer expires with current above threshold | Backup trip to selected adjacent/upstream breakers | Confirm backup outputs operated; verify correct breakers targeted per zone design; confirm lockout if applicable |
| Low-current status trip | Eligible protective trip at low current, below current-element pickup; ordinary manual or no-load switching is not automatically eligible | 52a is primary evidence; current element may not register | Scheme relies on 52a not opening within timer window | Backup trip via status path if scheme is designed for this; otherwise no action from current path | Verify status logic is explicitly designed and tested; confirm current element correctly shows no pickup; test status timer independently |
| 52a contradiction | Current element shows clear (no current); 52a remains closed after timer | 52a auxiliary contact or linkage has not operated | Current evidence contradicts status | Scheme should follow current evidence if scheme logic is current-supervised; but status contradiction should be alarmed | Test correct scheme response to discrepancy; verify alarm output for 52a failure to open; document which signal governs |
| CT channel loss | CT secondary circuit open or short; current element has no valid input | Current evidence absent | Scheme cannot confirm clear or failure on current path | Depends on scheme design: may require status fallback or alarm only | Test scheme behavior with CT input removed under controlled injection; verify alarm output; confirm no spurious backup trip |
| BFI disappears before timer (non-sealed scheme) | Initiating protection element resets before timer expires | BFI signal drops before timer expiry | Non-sealed scheme resets timer | No backup trip | Confirm timer reset occurs and backup outputs do not operate; verify scheme resets correctly |
| BFI seal-in (sealed scheme) | Initiating protection resets before timer, but BFI is latched | Latched BFI remains asserted | Timer continues despite loss of initiating signal | Scheme continues to timer expiry; backup trip if current still present | Confirm latch holds; confirm backup trip occurs if current is still present; verify latch resets appropriately after clearing |
| Spurious BFI with current below threshold | BFI asserted without an eligible trip; current element below threshold | Current below pickup; 52a as defined by the test | Timer may start but current element should not confirm failure | No backup trip (current supervision blocks output) | Inject BFI without fault current; confirm timer starts but backup outputs do not operate; verify current supervision is active |
| Retrip successful | Breaker failed on first trip; retrip via second path operates mechanism | Current drops after retrip; 52a opens; CT current clears | Record whether retrip clears before the selective backup decision and whether escalation resets as designed | Retrip clears fault; backup trip may or may not have been issued depending on timing | Verify retrip output operated; confirm current dropped; confirm whether backup trip also operated; document retrip path independence |
| Selected backup outputs | Backup trip needed; zone contains multiple sources | Multiple breakers feed fault zone | Zone map identifies all source breakers; non-zone breakers excluded | Only zone-identified breakers trip | Verify each targeted breaker trips on backup output; verify non-zone breakers do not trip; test each output path independently |
A spurious BFI while normal load current is above the detector threshold is a different security case. Current supervision alone may not block escalation in that condition. Review eligible initiation, routing, seal-in/reset and any status supervision against the actual design, and test that case where applicable.
All tests must be conducted under a formally approved, isolated test plan. No test involves creating a live primary fault or instructing the scheme to operate on a live energized feeder. Current injection tests use secondary injection from a relay test set into isolated CT circuits. Trip and backup outputs must be tested against their actual wired targets under isolated conditions with the primary circuit de-energized and tagged out per the site’s safety rules. No test bypasses active protection on a live circuit. The commissioning plan is developed by the project’s protection engineer and reviewed against the site’s safety management system before work begins.
Before finalizing a breaker-failure scheme design for an MV VCB feeder, verify the following with the project protection engineer and equipment suppliers:
For vacuum circuit breaker configuration information and to request documentation for a specific project, visit the Interruttore sottovuoto XBRELE pagina or submit a project data package via the contact page.
No. The 52a auxiliary contact reflects the mechanical position of the breaker’s operating mechanism as transmitted through the auxiliary contact linkage. When the mechanism travels to the open position, the 52a contact changes state. However, that change does not guarantee that all three main contacts have separated with sufficient distance to prevent current continuation, nor does it confirm that arc extinction has occurred. A contact that is physically stuck or welded on one pole, or that has insufficient travel due to a component failure, may leave that pole conducting while the mechanism reports open and the 52a changes state. Additionally, the 52a linkage itself can fail—a worn or broken cam, a misadjusted contact, or a failed auxiliary switch block—reporting open when the mechanism has not moved. This is why protection engineers treat 52a as corroborating evidence of mechanism movement rather than proof of electrical interruption, and why current measurement through CTs remains the primary evidence of whether fault current is still flowing.
The primary 50 and 51 elements detect fault current in the protected feeder and issue the trip command to the breaker. They are the fault-detection and trip-initiation functions. The 50BF element—or the breaker-failure scheme more broadly—evaluates whether the trip that was commanded actually resulted in current interruption. It is a supervision function that monitors the breaker’s response, not a fault-detection function that monitors the power system directly. A relay can have both a 50 element that initiates the trip and a 50BF element that monitors whether the breaker responded to that trip. These are distinct functions with distinct settings, distinct logic, and distinct outputs. Asserting 50BF as a protection function does not replace or duplicate the primary 50/51 elements; it depends on the approved eligible initiating protection functions, which may include 50/51 as well as other functions selected by the scheme designer. The common numerical designation creates a naming proximity that can mislead, but the functions serve entirely different purposes in the scheme.
No, and using a generic timer value without calculating it from the specific installation’s parameters is a design error. The timer must be set to exceed the sum of the breaker’s maximum rated interrupting time and the current element’s maximum dropout and filter time, plus margins for relay processing uncertainty. Each of these contributions is specific to the relay model, the breaker model, and the CT class. A breaker with a relatively long rated interrupting time requires a longer timer than a faster breaker. A current element with a longer dropout filter requires more margin. A sealed-initiation scheme has different constraints than a non-sealed one. The protection coordination study must calculate the timer explicitly, document the components of the calculation, and show that the resulting setting satisfies both the minimum (long enough to avoid operating on successful clearing) and maximum (short enough to limit backup fault duration to acceptable equipment withstand levels) constraints. Copying a timer value from another project, another relay type, or a training example is not an acceptable substitute for this calculation.
Retrip is a supplement to backup trip, not a replacement for it. Retrip addresses failure modes in the trip initiation path—a failed relay output, an intermittent control circuit, a first coil that did not operate—by providing a second attempt through an independent path. If the second path is genuinely independent (separate DC supply, separate wiring, separate coil), retrip can recover from trip-path failures that backup trip from an adjacent breaker cannot address more selectively. However, retrip does nothing for mechanical failures: a jammed mechanism, a broken latch, or a welded contact will not respond to a second trip command on a second coil. In these cases, the failed breaker still cannot interrupt, and backup trip from adjacent or upstream breakers is required to remove all current sources from the fault zone. A scheme that includes only retrip without backup trip outputs leaves the system exposed to the most serious failure modes, which are precisely those where the breaker’s mechanism has failed rather than its control path. The two functions are complementary and both need to be designed, tested, and verified.
First identify whether the protective trip is intended to initiate the failure scheme. A transformer mechanical-protection trip, for example, can require opening when the primary current is below the current detector threshold. The approved scheme may then use a supervised 52a path to detect failure to open. Define its timer, initiating functions, signal supervision and response to disagreement explicitly. A manual local opening or maintenance operation is not automatically an eligible failure initiation, and no-current commissioning should verify the designed distinction.