Demander un devis pour des composants et équipements haute tension

Faites-nous part de vos besoins (tension nominale, modèle, quantité et destination) et notre équipe XBR Electric vous préparera un devis détaillé dans les 24 heures.
Démonstration du formulaire de contact
Technical diagram showing transformer dissolved gas analysis fault patterns and maintenance decision flow

DGA Gas Pattern Interpretation Field Guide for Transformers

Dissolved gas analysis (DGA) is the primary diagnostic tool for detecting developing faults inside oil-filled transformers before they progress to catastrophic failure. This guide covers how to read gas patterns, apply ratio methods, assign action tiers, collect valid samples, and embed DGA into a structured maintenance program. It also addresses procurement decisions that determine whether a transformer can be monitored cost-effectively throughout its service life.


Quick Diagnosis: Gas Pattern vs. Fault Type

Before working through ratio methods or action thresholds, match the dominant gas pattern to a probable fault type using the table below. This is the first filter applied when a new lab result arrives.

Symptom (Dominant Gas Pattern)Premier testCause première probableAction suivante
H2 only or H2 + CH4 (small); low C2H2Check moisture in oil; review breather conditionPartial discharge (PD) in moisture-contaminated oilSchedule offline PD testing; shorten sampling interval to monthly
CH4 + C2H6 elevated; negligible C2H2Review load history and cooling system logsThermal fault below 300 deg C; stray flux or overheated oilInspect cooling fans and radiators; check load against nameplate
C2H4 dominant + CH4; low C2H2Calculate C2H4/C2H6 ratio; check LTC operation countThermal fault 300-700 deg C; circulating currents or bad contactsReduce load; plan inspection outage within 60 days
C2H4 + C2H2 elevated; high H2Apply Duval Triangle; check rate of changeThermal fault above 700 deg C; severe hotspot with arcing componentAccelerate outage; resample within 72 hours
C2H2 dominant + H2; C2H4 presentConfirm with IEC 60599 ratios; check tap changer oil separatelyHigh-energy arc; internal flashover or tap changer faultConsider immediate de-energization
CO + CO2 rising with hydrocarbonsMeasure CO/CO2 ratio; order furan analysisCellulose degradation combined with thermal faultAssess moisture content; schedule furan sampling
CO + CO2 only; H2 minimalReview long-term load historyNormal aging or overloaded paper insulationTrend review; no immediate electrical action required

Key principle: Acetylene above 1-2 ppm in a sealed transformer with no recent through-fault record is the single most reliable indicator demanding expedited response, regardless of other gas levels. Rate of change is often the earlier warning signal; a methane reading that doubled in four weeks carries more urgency than the same reading stable for six months.

Outils et sources d'acceptation

Before interpreting any DGA result, verify that sampling equipment, laboratory methods, and reference standards meet the criteria below. A flawed sample cannot be corrected analytically downstream.

Instrument or SourceFunctional RoleCritère d'acceptation
Glass syringe (60-100 mL, gas-tight, luer-lock)Reference oil sample collectionLeak-tested before field trip; used within certified service life; borosilicate glass only
Stainless steel pressurized cylinder (250 mL)Long-transit or elevated-pressure samplingBall-valve closure; rated for site pressure; sample held <=30 days
Gas chromatograph with TCD/FID (GC-TCD/FID)Resolve all nine key gases per IEC 60567ISO/IEC 17025 accredited laboratory; calibrated with certified standard gas mixture
Portable GC (on-site triage)Immediate rate-of-change triageCalibrated within 30 days; operator holds documented competency; confirm with fixed-lab split sample
Online multi-gas DGA monitorContinuous trend detection between manual samplesFactory recalibration within 12-18 months; alarm setpoints defined in program documentation
Photoacoustic analyzer (lab)Routine surveillance gas reportingNot used for ratio calculations when individual gas values are below 10 ppm
Buchholz relay with gas collection chamberProtection event capture; gross fault detectionCalibrated and functionally tested before dispatch; gas volume and color recorded on trip
IEC 60599Ratio method reference and fault zone boundariesCurrent edition; apply for regulatory reporting and boundary-case ratio interpretation
IEEE C57.104Action threshold levels 1-4; TDCG limitsCurrent edition; apply for individual gas and TDCG threshold decisions
OEM transformer manualEquipment-specific baseline and cooling dataFactory acceptance DGA result required as first reference point in trend history
Spécification du projetSite-specific alarm levels and response obligationsContractual action tiers must match or exceed IEEE C57.104 minimums
Transformer oil sampling and DGA test equipment layout with acceptance checkpoints
Core DGA sampling tools, laboratory equipment, and standards references used before interpretation begins.

How to Map Fault Types from DGA Gas Ratios

Raw gas concentrations tell you what is present. Gas ratios tell you why it is there.

The Core Ratio Logic

Rogers Ratio Method

IEC 60599 Ratio Method

Duval Triangle Method

Side-by-Side Comparison

CritèreRatios de RogersIEC 60599Triangle de Duval
Can return undefined resultOuiOuiNon
Handles mixed faultsPauvreModéréMieux
Requires C2H2 > 0 for full accuracyYes (R2 fails)Yes (ratio 1 fails)Non
Uses H2 in fault mappingYes (R1)OuiNon
Standards referenceIEC 60599 / IEEE C57.104IEC 60599IEC 60599
Best use caseSingle-mechanism, clear faultRegulatory reportingTrending, mixed faults
Risk at low gas concentrationsÉlevéÉlevéModéré

Applying the Ratios to a Field Decision

Comparison diagram of Rogers ratios, IEC 60599 ratios, and Duval Triangle for transformer fault mapping
Ratio methods and Duval plotting are used together to classify transformer fault mechanisms with higher confidence.

Action Thresholds: When Do DGA Results Require Immediate Response?

DGA gas pattern interpretation produces value only when it connects to a clear decision. The tiered action system below reflects IEC 60599 guidance and IEEE C57.104 limits for power transformers rated 69 kV and above.

Tiered Action Table

TierLabelTrigger ConditionsAction requiseTime Frame
1Normal – Continue MonitoringAll gases below Level 1 limits; ROC stable; no fault ratio flagMaintain standard sampling intervalNo urgency
2Caution – Increase SamplingAny gas between Level 1 and Level 2; ROC >10% per month on any key gas; single ratio flag without corroborating gas riseShorten sampling to monthly; review load history; inspect coolingDans les 30 jours
3Warning – Load Reduction and InvestigationAny gas exceeds Level 2; C2H2 >3 ppm with rising trend; multiple gases rising simultaneously; two or more ratio flags consistent with same fault typeReduce load to nameplate; schedule offline inspection within 60 days; increase sampling to weeklyWithin 7 days
4Critical – Immediate De-energizationC2H2 >35 ppm with rapid ROC; H2 >1,800 ppm; CO >1,500 ppm combined with acetylene; any gas doubling in <30 days; Duval plotting in D2 zoneRemove from service; do not re-energize without internal inspection and engineering sign-offImmédiate

IEEE C57.104 Level 1 and Level 2 Reference Values (ppm dissolved in mineral oil)

GazLevel 1 (Caution Entry)Level 2 (Warning Entry)
Hydrogen (H2)100700
Methane (CH4)120400
Ethylene (C2H4)50200
Ethane (C2H6)65150
Acetylene (C2H2)335
Monoxyde de carbone (CO)350900
Carbon dioxide (CO2)2,50010,000
Total Combustible Gas (TCG)7201,920

Field Decision Sequence

Step 1 – Screen absolute concentrations. If any gas exceeds Level 2, assign Tier 3 before proceeding. If acetylene exceeds 35 ppm or any gas has doubled since the last sample, assign Tier 4 and stop further analysis pending shutdown.
Step 2 – Calculate rate of change. A ROC exceeding 1 ppm/day for acetylene or 10 ppm/day for hydrogen warrants a minimum Tier 3 assignment regardless of absolute concentration.

Conditions That Override Standard Thresholds


Field Scenario: Thermal Fault at LTC Interface – 132/33 kV Autotransformer

Field context: A 63 MVA autotransformer commissioned in 2007 averages 28 tap change operations per day. A DGA sample was taken six weeks after an unscheduled sample triggered by a protection relay transient. Oil temperature runs 5-8 deg C above the unit’s benchmark due to increased throughput.
Measured gas concentrations (ppm):

GazCurrent SamplePrevious Sample (6 weeks prior)
H29578
CH4310205
C2H2149
C2H4480310
C2H6190140
LE CO420390
CO23,9003,600

Diagnostic : C2H4 is dominant and increasing at approximately 28 ppm per week. The C2H4/C2H6 ratio of 2.53 is consistent with localized oil temperatures above 500 deg C. The C2H2/C2H4 ratio of 0.029 indicates low-energy arcing at tap changer contacts as a plausible contributor given the high operation count. Duval Triangle coordinates place the sample in the T2-T3 zone trending toward T3. CO trend is relatively flat, indicating cellulose is not the primary fault material at this stage. This result is Tier 3: load reduction and investigation required within seven days.

Autotransformer LTC interface fault scenario with rising ethylene and acetylene trend highlighted
Example field case showing a thermal fault at the LTC interface trending toward a higher-severity condition.

Sampling Procedures and Measurement Acceptance Criteria

Accurate DGA gas pattern interpretation depends entirely on the quality of the oil sample entering the laboratory. A flawed sample introduces measurement error that no analytical method can correct downstream.

Sampling Point Selection and Pre-Sample Purge

Procedural Controls That Directly Affect DGA Results

Control PointAction requiseConsequence of Omission
Air exclusion during syringe fillFill syringe while submerged in oil flow; no air bubblesOxygen and nitrogen dilution; artificially lowered fault gas ratios
Syringe over-pressurization preventionBack-plunge slightly after fill to seat at 5-10 mL headspaceDissolved gas escapes if syringe barrel pressure drops below saturation
Label and chain of custodyRecord transformer ID, MVA rating, voltage class, load at sampling, oil temperature, date and timeMisattributed results; false trending
Transport temperatureKeep samples between 5 deg C and 25 deg CFreezing fractures glass syringes; heat above 35 deg C accelerates gas loss
Maximum holding time before analysisGlass syringe: <=72 hours; stainless cylinder: <=30 daysProgressive hydrogen loss from glass after 72 hours documented in CIGRE TB 771

Measurement Acceptance Criteria Before Result Use

1. Oxygen-to-nitrogen ratio check. In sealed-tank transformers, O2/N2 should be approximately 0.3-0.5. A ratio above 0.5 indicates air contamination; reject the sample and resample.
2. Moisture correlation. Verify that dissolved water (ppm by Karl Fischer) is plausible for the insulation class and temperature history. A value above oil saturation at the measured temperature suggests a gross sampling error or seal breach.


Integrating DGA into a Transformer Maintenance Program

A DGA result without a defined response path has limited maintenance value. The interpretation becomes actionable only when embedded in a program that specifies who reviews results, at what frequency, against which thresholds, and with what escalation authority.

Program Structure: Four Functional Layers

LayerFonctionTypical Owner
SamplingCollect oil samples at defined intervalsField technician
AnalyseRun chromatographic tests, generate gas concentrationsLaboratory or on-site monitor
InterprétationApply ratio methods, compare to thresholds, classify fault typeEngineer or diagnostic specialist
ActionAuthorize load reduction, inspection, or outageAsset manager or operations lead

Sampling Frequency Decision Logic

TDCG Levels and Program Responses

TDCG LevelConcentration Range (ppm)Program Response
Level 1Below 720Continue normal sampling interval; no action required
Level 2720-1,920Increase sampling frequency; review individual gas trends; apply Duval Triangle
Level 31,921-4,630Sample every 1-4 weeks; prepare contingency plan; consider load reduction if trend is rising
Level 4Above 4,630Consider immediate de-energization; consult engineering before next energization

Where Programs Break Down

Interpretation without context. A gas concentration reviewed without previous sample history, load profile, or transformer age produces unreliable conclusions; interpreters must have access to the full DGA history.
Action authority gaps. If the engineer who interprets the result cannot authorize a load reduction or outage, and the person who can does not receive the interpretation, the program stalls. Define the escalation path explicitly, including who receives the report and within what timeframe.

Workflow diagram linking DGA sampling, analysis, interpretation, and maintenance action in a transformer program
A structured DGA program depends on clear handoff from sampling and analysis to interpretation and action authority.

Specifying DGA-Ready Transformers and Requesting Supplier Diagnostic Support

Effective DGA gas pattern interpretation begins before a transformer is energized. Procurement decisions at the specification stage determine whether a unit can be monitored cost-effectively throughout its service life.

What to Specify at the Procurement Stage

Oil sampling valve placement. Require at minimum one bottom-mounted sampling valve and one top-oil valve, both rated for syringe or vacuum-bottle extraction without de-energizing. Reject sampling valves located above oil level for critical assets due to air ingress risk.
Buchholz relay and gas collection. For units above 1 MVA, specify a Buchholz relay with a gas collection chamber that permits syringe extraction, positioned on the pipe run between tank and conservator.

Evaluating Supplier Diagnostic Capability

CritèreMinimum Acceptable Evidence
Laboratory accreditationISO/IEC 17025 accreditation with DGA listed in scope
Sampling personnel qualificationTechnicians certified to IEC 60567 sampling procedure or equivalent documented training
Turnaround timeWritten commitment: routine results within 5 business days; urgent flag results within 24 hours
Interpretation serviceNamed process for escalation beyond raw numbers: ratios applied, trend context reviewed
Reporting formatStructured report including trend comparison, ratio analysis, and recommended action tier
Equipment traceabilityCalibration records for gas chromatograph available on request

Retrofitting DGA Capability on Existing Units


Références techniques connexes XBRELE

Utilisez ces références XBRELE pour relier la décision sur le terrain au produit correct, au test et au flux de travail de l'approvisionnement : Page produit XBRELE, Gamme de disjoncteurs à vide XBRELE, Guide de notation de la VCB, Liste de contrôle pour l'acceptation du TFA/TSA par le VCB, XBRELE power distribution transformer range.

Contexte des normes

Pour le contexte de la méthode externe, comparez la procédure du site avec la procédure publique. Page des normes IEEE C37.09 et appliquer le manuel de l'équipementier et les spécifications du projet pour l'équipement fourni.

Outils et sources d'acceptation

Instrument / SourceAcceptance RoleRisk if Missing
OEM manualDefines model-specific limit, test current, and inspection toleranceGeneric limits can create false pass or false alarm
Spécification du projetDefines site acceptance source, reporting format, insulation test level, and maintenance intervalResults may pass technically but fail contractually
Contact resistance tester / micro-ohmmeterMeasures micro-ohm contact condition under controlled currentMultimeter readings cannot support alarm-limit decisions
Rapport d'essai d'acceptation en usineProvides serial-number baseline and test conditionNo valid comparison point for site trending

Exemple de champ

Field example: during a service inspection, one phase measured outside its commissioning baseline while the other two phases remained stable. The team repeated the measurement with verified leads, checked timing and contact travel, and used the measured divergence to separate a contact-pressure problem from a generic surface-cleaning issue. The corrective action was documented in the troubleshooting chart so the next DGA sample, inspection note, and maintenance record could be compared against the same fault map.

Foire aux questions

What is the most important single gas to monitor in a transformer DGA result?

Acetylene (C2H2) carries the highest diagnostic weight because it is only produced in significant quantities by high-energy electrical discharges. Any confirmed detection above 1-2 ppm in a sealed transformer with no recent through-fault history warrants investigation.

How often should DGA sampling be performed on a critical power transformer?

Sampling frequency should be risk-stratified rather than uniform. A new transformer with no fault history typically requires annual sampling.

Can DGA be performed on dry-type transformers?

No. DGA applies specifically to oil-filled transformers because the diagnostic gases are produced by thermal and electrical decomposition of insulating oil and oil-impregnated cellulose.

What does a high CO/CO2 ratio indicate, and when is it alarming?

A CO/CO2 ratio below 0.1 is consistent with normal background paper aging. Ratios above 0.3 indicate active cellulose degradation involving thermal mechanisms.

Why do ratio methods sometimes give contradictory or undefined results?

Ratio methods fail at low absolute gas concentrations because small laboratory measurement uncertainties produce large swings in computed ratio values. They also fail when multiple fault types are active simultaneously.

What sampling errors most commonly invalidate a DGA result?

The three most common invalidating errors are: air contamination during syringe filling, which depresses fault gas concentrations and raises the O2/N2 ratio above 0.5; exceeding the 72-hour holding time for glass syringes, which causes measurable hydrogen loss; and drawing the sample from the top of the tank or the conservator rather than the bottom drain valve, which underreports heavier fault gases. Any result showing an O2/N2 ratio above 0.5 in a sealed-tank transformer should be rejected and a fresh sample collected before any maintenance decision is made.

How should DGA results be interpreted differently for a transformer with an on-load tap changer sharing oil with the main tank?

An OLTC sharing oil with the main tank introduces a persistent C2H2 background from normal contact arcing during tap changes. This background must be established as a unit-specific baseline rather than compared directly to standard IEEE or IEC tables.

Hannah Zhu, directrice marketing de XBRELE
Hannah

Hannah est administratrice et coordinatrice du contenu technique chez XBRELE. Elle supervise la structure du site Web, la documentation des produits et le contenu du blog sur les appareillages de commutation MT/HT, les disjoncteurs à vide, les contacteurs, les interrupteurs et les transformateurs. Son objectif est de fournir des informations claires, fiables et faciles à comprendre pour les ingénieurs afin d'aider les clients du monde entier à prendre des décisions techniques et d'achat en toute confiance.

Articles: 153