Room cutaway with low intake, warm coil symbols and high exhaust connected by airflow arrows.

Dry-Type Transformer Room Ventilation: Heat Loss, Airflow and Opening Design

Calculate a preliminary heat load and airflow, then check net free openings, fan duty, recirculation and maintenance conditions for a dry-type transformer room.

முக்கியக் குறிப்புகள்

  • Size room ventilation from transformer and concurrent room losses, not nameplate kVA; keep the loss temperature, loading and harmonic assumptions explicit.
  • Use intake-to-exhaust air temperature rise in the room heat balance, then separately verify the cooling air actually reaching the transformer against its OEM limits.
  • Specify net free openings and the full airflow-path resistance, and check bypass, dirty filters and fan failure rather than relying on nominal fan flow alone.

A dry-type transformer does not consume the electrical power flowing through it. It converts voltage and current, delivering useful energy to the connected load. The gap between input power and output power is dissipated as heat, and virtually all of that heat ends up in the air of the room where the transformer is installed. Sizing the room ventilation means calculating how much heat needs to be removed, determining what airflow is required to remove it, designing the opening sizes and positions that allow that airflow, and checking that the layout actually delivers conditioned air to the heat source rather than bypassing it. Each of these steps requires specific assumptions, and the assumptions have to be coordinated before a ventilation brief can be handed to a building services engineer.

This article works through the full chain from rated losses to a ventilation design brief, with explicit attention to what changes between a preliminary estimate and a final design.


Heat Rejected into the Room

The rated kVA figure on a transformer nameplate is the apparent power the transformer can continuously deliver to the load. It is not a measure of heat generation. Heat generation is the difference between input and output power: the electrical losses in the transformer’s magnetic core and its windings. These losses appear as heat in the transformer itself, and that heat is then transferred to the surrounding air.

This distinction matters immediately when thinking about ventilation. For an illustrative transformer with agreed no-load loss P0 = 2 kW and rated-current load loss Pk = 10 kW, the preliminary loss estimate at rated current is 12 kW. That is the thermal contribution to assess, rather than the nameplate kVA. These assumed losses describe no XBRELE model.

A second distinction is equally important: the coil cooling of the transformer is not the same as room ventilation. Many dry-type transformers are built with fans mounted on the coil assembly that circulate air across the windings to increase heat transfer from the windings to air. These fans serve the transformer’s specified cooling duty and may support a higher load for the duration and conditions stated by its manufacturer. They do not remove heat from the room. They transfer heat from the winding surface into the room air more efficiently, which can increase the room heat load if the fans allow a higher operating current, but the fans themselves are part of the transformer’s internal thermal management, not a ventilation system. The room ventilation must remove whatever heat has entered the room air, regardless of how it got there.

Schneider Electric’s substation ventilation guide treats transformer and other room losses together and describes low/high openings for buoyancy-assisted flow. Moisture control also matters: condensation can form when equipment surfaces are colder than the local air’s dew point, including when warm humid air reaches cold equipment. Airflow and temperature changes therefore need to be assessed with the humidity pattern.


Building the Heat-Load Case Before Calculating Airflow

Core-loss, load-loss and room-load blocks each contribute to a heat-load block.
Build the room heat load from concurrent transformer losses and the other heat sources present.

Before converting heat to airflow, the heat load itself must be correctly assembled. This is where engineers most often underestimate the complexity of the preliminary step.

Transformer losses: the starting formula

For a transformer carrying a load expressed as a fraction K of its rated current, the total losses at a fixed reference temperature can be approximated as:

P_total = P0 + K² × Pk

where P0 is no-load loss at the specified voltage and frequency, and Pk is load loss at rated current and its stated reference temperature. Pk includes winding resistance loss and additional eddy/stray losses; it is broader than copper I²R loss alone.

This formula is a useful preliminary approximation based on sinusoidal rated-frequency loading at constant temperature. P0 is essentially constant regardless of load; it represents continuous magnetic cycling losses in the core and runs every hour the transformer is energised, even at no load. Pk scales with the square of the load current because resistive heating in copper is proportional to I².

For a preliminary heat-load estimate, applying this formula with catalogue P0 and Pk values and an expected load factor K gives a usable starting figure. However, several adjustments are required before the estimate becomes a credible design input.

Adjustments from the preliminary estimate to design load

Operating temperature correction. Published P0 and Pk values are stated at a specific reference temperature (which must be identified for the actual dry-type design). Resistance loss rises when operating conductor temperature is above the stated reference and falls when it is below it. Additional losses need their appropriate correction. Use the supplier’s loss calculation for the intended current, temperature, voltage and frequency; do not assume every operating case produces more loss than the reference value.

Harmonic loading. The K² scaling applies to fundamental-frequency sinusoidal current. Non-linear loads, variable speed drives, UPS systems and data-centre equipment introduce harmonic current components. Harmonics affect resistance loss through total RMS current, while winding eddy and other stray losses respond differently to the harmonic spectrum and conductor geometry. An n²-weighted current expression is an approximation used for some winding eddy-loss assessments, not a multiplier for every load-loss component. THD alone omits the distribution among harmonic orders; provide the spectrum and duty to the supplier for an appropriate loss assessment rather than multiplying all Pk by a K-factor.

Fan and auxiliary motors. If the transformer has coil-mounted fans, the fan motor power is an additional room heat contribution. Control panels, cooling fan contactors and any other continuously energised auxiliaries in the room add to the heat load.

Other room equipment. Switchgear panels, metering cubicles, power factor correction capacitors and any other equipment in the same ventilated space contribute their own losses to the room heat load. The ventilation must handle all concurrent heat sources, not just the transformer.

Solar and wall transfer. A room with sun-exposed walls or a roof will have an additional conductive and radiative heat gain that varies with season and time of day. South- or west-facing exposures in summer can add kilowatts of heat gain that have nothing to do with the electrical installation.

Establishing the design case

The design heat load is the worst credible concurrent case: the transformer at the expected maximum load factor (the actual duty may differ from rated current), all auxiliary equipment running, and the peak seasonal ambient condition. Because P0 runs continuously, the transformer should be assumed energised even at minimum load. The seasonal worst case for heat removal is usually the hottest day of the year, combined with the highest electrical load. These may or may not coincide; for a commercial building, peak air conditioning load and peak electrical transformer load often do occur together.

For a real project, obtain agreed no-load and load losses with their voltage, frequency, current and reference-temperature conditions, together with the intended harmonic profile, enclosure and cooling configuration. The catalogue page at xbrele.com/power-distribution-transformers/dry-type-transformer/ is the starting point for requesting project-specific loss data.


Converting Heat Load into Required Airflow

Thermometers at a low room inlet and high room outlet, beside a warm heat-source block.
The room heat-balance temperature rise is outlet air minus inlet air; it is separate from winding temperature rise.

Once the room heat load P (in watts) is established, the required volumetric airflow follows from a sensible heat balance on the room air.

The energy balance

The room behaves as a steady-state heat exchanger. Cool air enters at inlet temperature T_in, absorbs heat from all sources in the room, and leaves at exhaust temperature T_out. The power removed by the airflow is:

P = ρ × cp × Qv × ΔT

where: – P is the total room heat load in watts (W) – ρ is the air density in kilograms per cubic metre (kg/m³) – cp is the specific heat of air at constant pressure in joules per kilogram-kelvin (J/kg·K) – Qv is the volumetric flow rate in cubic metres per second (m³/s) – ΔT = T_out − T_in is the temperature rise of the air between intake and exhaust, in kelvin (K)

Rearranging for the required flow rate:

Qv = P / (ρ × cp × ΔT)

Critical distinction: ΔT is not winding temperature rise

The ΔT in this formula is the temperature difference between the exhaust air leaving the room and the inlet air entering the room. It is the rise in room air temperature across the ventilated space, not the winding temperature rise of the transformer. Winding temperature rise describes the thermal gradient between the winding conductor and the surrounding air; it is an insulation and thermal-class specification of the transformer itself. Room air can be significantly cooler than the winding surface while still being unacceptably hot for inlet air to the transformer. These are two separate design parameters that must not be conflated.

A worked illustrative example

Consider a project scenario with the following assumed values:

  • Total room heat load: P = 12 000 W (12 kW), comprising transformer losses and ancillary equipment at the worst concurrent case
  • Air density: ρ = 1.2 kg/m³ (appropriate for air at approximately sea level and moderate temperature; density falls at altitude and at higher inlet temperatures)
  • Specific heat of air: cp = 1005 J/kg·K
  • Acceptable air temperature rise across the room: ΔT = 10 K (inlet at, say, 35 °C, exhaust at 45 °C)

Applying the formula:

Qv = 12 000 / (1.2 × 1005 × 10) = 12 000 / 12 060 ≈ 0.995 m³/s

Converting to cubic metres per hour: 0.995 × 3600 ≈ 3 582 m³/h

These numbers are illustrative for this assumed scenario and do not represent a rating for any XBRELE product or a standard installation requirement. Every assumption must be justified for the actual project:

  • The choice of ΔT = 10 K is a design decision. A smaller ΔT requires more airflow for the same heat load; a larger ΔT reduces airflow but means exhaust air is hotter, which affects whether the transformer inlet air remains within acceptable limits.
  • Air density at 1.2 kg/m³ is reasonable at sea level and around 20 °C. Sites above 1000 m have meaningfully lower density, which increases the required volumetric flow for the same mass-flow heat removal.
  • If the inlet air temperature is already at the upper end of the transformer’s permitted inlet range, a ΔT of 10 K may push exhaust air to a temperature that recirculates back to the inlet and raises it further, compounding the problem.

Recirculation and hot inlets

A common error in preliminary calculations is to assume that inlet air temperature equals ambient outdoor air temperature. If the inlet opening is positioned close to the exhaust, or if the exhaust air escapes into a space that feeds back into the inlet, the effective inlet temperature is higher than ambient. The energy balance holds regardless, but the calculated heat rise remains P/(ρ cp Qv), while the actual cooling air reaching the transformer is warmer. If an independently justified room or exhaust-temperature limit remains fixed, the allowable ΔT becomes smaller and more flow may be needed. If inlet air entering the room is already warm because it has picked up heat from an adjacent space or from exhaust recirculation, the ventilation system is working against a reduced temperature budget. This is a layout problem as much as a calculation problem, and it must be resolved before the opening and fan sizes are finalised.


Turning Airflow into Opening and Fan Requirements

Front view of a louvre gross face and enlarged open passages between its blades.
The louvre face includes solid blades; the net free area is the open passage available for airflow.

Having established a required volumetric flow rate, the next step is to design the openings and, where natural buoyancy is insufficient, the mechanical fans. This is where the gap between preliminary estimates and engineered design is widest.

Net free area versus gross louvre face

A ventilation opening is typically covered by a louvre, grille, mesh or damper. The gross face area is the total wall area occupied by the opening. The net free area — sometimes called the free air area — is the actual unobstructed area through which air can flow. For a typical louvre with inclined blades, the net free area is substantially less than the gross face. An illustrative louvre with a free-area ratio of 50% has 0.5 m² of net free flow area for each 1 m² of gross face area. At the same design velocity, the actual volume flow through a 1 m² louvre with 50% free area is half what it would be through an open 1 m² hole.

This matters because the air velocity through the net free area is what determines both the volume flow and the pressure drop across the opening. If the design is based on the gross area, the actual air velocity through the blades is double the assumed value, the restriction can be substantially greater. Under a fixed loss coefficient and the same flow, a velocity-squared approximation gives four times the pressure loss; the actual delivered flow is determined by the fan/system or buoyancy balance.

For design purposes, the gross louvre face area must be derived from the required net free area, not the other way around. If net free area of, say, 0.5 m² is required at the inlet, and the louvre has a 50% free-area ratio, the gross face area of that louvre must be 1.0 m². This distinction applies equally to inlet and exhaust openings.

Full airflow path resistance

The pressure loss through the ventilation system is not just the inlet opening and the outlet opening. It is the sum of all resistances along the complete air path: inlet louvre, any ductwork or bends, the transformer enclosure (if the air is routed through it), the room space, any filters, the exhaust louvre, and any dampers. Fans must be selected to deliver the required flow rate against the total system resistance at the design operating point, not against the opening resistance alone.

Filters deserve particular attention. A clean filter has a low, known pressure drop. A dirty filter — one that has accumulated dust over weeks or months between maintenance visits — may have a pressure drop several times higher than the clean value. The fan must deliver the required airflow against the dirty-filter resistance, not the clean-filter resistance. Specifying a fan that just meets flow requirements with a clean filter means the system will be underperforming for most of its operational life.

Natural convection: buoyancy is geometry-dependent

In the absence of mechanical fans, ventilation depends on the buoyancy of warm air. Warmer air is less dense; it rises and exits through high-level openings, drawing cooler air in through low-level openings. The driving pressure available from buoyancy is proportional to the height difference between inlet and outlet openings and to the temperature difference between the internal and external air. Greater height separation and higher internal temperature both increase the buoyancy driving force.

The airflow delivered by natural convection depends on this driving pressure and on the total resistance of the airflow path, exactly as for a mechanical system. Because the driving pressure is small (typically a few Pascals for typical room geometries and temperature differences), natural ventilation is sensitive to opening resistance. Reducing free area increases resistance; the resulting flow reduction depends on the complete pressure-flow balance.

Simplified opening rules carry specific assumptions. Schneider Electric FAQ FA358662 defines net inlet/outlet areas excluding grille blockage and opening height, with stated conditions of 20 °C annual-average ambient, altitude no greater than 1000 m and an unobstructed path. Its worked example is an oil-filled Minera with losses referenced to 75 °C. Those conditions do not establish the required opening area for a different dry-type room. Use an applicable OEM method or a validated airflow model incorporating the actual heat load, height, resistance, air properties and service conditions; coordinate the final design with the room designer.

Mechanical fans: selection and redundancy

Where natural convection is insufficient — either because the available height is small, the internal-to-external temperature difference is limited, or the heat load is high — mechanical fans are needed. Fan selection requires:

Duty point. The fan must deliver the required airflow (m³/h) against the system total pressure (Pa) at the worst operating condition, which is the dirty-filter, maximum-heat-load case.

System curve. Pressure drop in the system scales approximately with the square of flow rate. The fan’s characteristic curve (flow versus pressure) must intersect the system curve at or above the required flow rate.

Redundancy. A single fan failure in a room containing a large transformer can lead to rapid thermal overload. Many installations use two fans in parallel or duty-standby arrangements. The redundancy strategy must be coordinated with the transformer’s OEM thermal limits and alarm/trip settings.

Inlet conditions. A fan mounted immediately behind a louvre with high resistance may be starved of inlet air. The fan static pressure must be matched to the system resistance, including the inlet approach loss.

Enclosure matching. If the transformer is in an IP-rated enclosure, the enclosure’s own ventilation openings become part of the system resistance. The enclosure airflow path must be matched to the external room ventilation to avoid a mismatch where the room has sufficient flow but the enclosure is the bottleneck.


Checking the Room Layout and Failure Cases

Two room sections compare high-level airflow bypass with a low-to-high path around the heat source.
Total flow can bypass the equipment; inspect the route that brings replacement air to the heat source.

A ventilation system that is correctly sized on paper can still fail to cool the transformer if the air does not follow the intended path through the room.

Short-circuit airflow

A high-level inlet close to a high-level exhaust can let fresh air pass directly between openings while cooler replacement air barely reaches the transformer. That internal bypass is different from external recirculation, where discharged warm air returns to the room intake. Either can leave the heat source poorly served despite a satisfactory total-flow measurement.

A low inlet with a high exhaust near the heat source generally favours a useful buoyancy-assisted route. The actual positions must be checked against partitions, enclosure openings and equipment arrangement: their height alone does not prove that the cool air reaches the transformer.

Guiding the airflow path

In rooms with complex geometry, partitions, cable trays or multiple items of equipment, the natural airflow path may still bypass the transformer even with low-level inlet and high-level exhaust. Baffles, plenums or directed ductwork can guide air through the heat source rather than around it. The investment in guiding is usually modest but the thermal improvement can be substantial.

As an example scenario: a room initially has both inlet and exhaust positioned at high level, with a short distance between them. Fan capacity tests may show adequate total flow. But thermal measurements show the transformer running hot because most of the air travels directly from inlet to exhaust along the high zone, while the heat source sits at floor level. Relocating the inlet to low level, or adding a baffle that forces incoming air downward before it rises through the heat source, can improve the heat-removal path. Recalculate the resistance after the change and verify delivered airflow and local inlet temperatures; a baffle may also change the fan duty.

Room versus coil fans

As noted earlier, fans mounted on the transformer coil assembly are thermal management devices for the transformer, not room ventilation devices. If a transformer is specified in AN/AF cooling mode (natural air cooling / forced air cooling), the AF mode fans support the manufacturer’s declared load and duration by improving internal heat transfer. They do not exhaust hot air from the room. The room ventilation system must still remove all the transformer losses from the room air, and when the coil fans are running, those fan motors themselves add to the room heat load.

Enclosure restrictions

A ventilated transformer enclosure has openings in its casing; the IP code alone does not define its airflow or cooling arrangement. These openings must be accessible to the room airflow. Placing a transformer enclosure hard against a wall, covering its ventilation slots with cable trays, or positioning it in a corner where room airflow cannot reach the enclosure openings will restrict the transformer’s own heat dissipation even if the room ventilation is otherwise adequate. The room layout must allow airflow to reach, surround and exit the enclosure.

Condensation and contaminant tradeoffs

Ventilation openings bring outdoor air into the room. Outdoor air carries humidity, dust, insects and other contaminants. Condensation is possible where surface temperature falls below the local dew point; assess shutdowns, cold equipment and incoming humid air together. Filters reduce particulate ingress but add to the system resistance and require maintenance. In dusty, high-humidity or coastal environments, the tradeoff between ventilation adequacy and contamination protection is a genuine design decision that affects both the thermal design and the maintenance schedule.

Fire and smoke dampers, where required by local building regulations, add further resistance and must be in the open position for the ventilation system to function. Their position feedback and control must be coordinated with the ventilation control. These requirements are determined by the responsible building services and fire safety engineers for the specific installation and jurisdiction.

Fan failure and blocked inlet response

If a mechanical fan fails or an inlet becomes partially blocked, the airflow through the room drops. The transformer’s thermal protection (winding temperature sensors, thermistors or thermocouples) must be coordinated with the OEM’s thermal limits and the project protection study. Fan/airflow failure indication may reveal the problem before a winding-temperature alarm, but neither signal guarantees sufficient intervention time. The transformer’s loading limit under degraded ventilation is set by the OEM based on the specific unit’s thermal design; a universal derating figure does not apply across all units, enclosures and room configurations.


Issuing a Ventilation Design Brief

A ventilation design brief is the document that connects the electrical engineer’s transformer selection to the building services engineer’s room design. It should be specific enough to allow the ventilation engineer to size openings, fans and controls without having to make guesses about the transformer or the room.

The following table organises the inputs and outputs that should appear in a coordinated brief.

Brief SectionRequired Input from Electrical TeamOutput for Ventilation Design
Heat loadAgreed P0 and Pk at stated reference temperature, load factor K, harmonic spectrum and operating duty, auxiliary equipment losses, fan motor powerTotal room heat load P (W) at worst concurrent case
Duty and reference temperatureExpected operating load factor range, seasonal peak, continuous or intermittent dutyHeat load range; maximum and minimum heat load cases
Ambient and altitudeSite altitude (m above sea level), outdoor design dry-bulb temperature (summer peak and annual average), humidity rangeAir density for calculations; inlet design temperature
Maximum inlet temperatureOEM-specified maximum continuous inlet air temperature for the transformer at rated cooling classVerify air at each transformer cooling intake against OEM ambient/inlet conditions; select the separate room heat-rise case
Room geometryPlan dimensions, ceiling height, positions of transformer, switchgear and other equipment, available wall positions for openingsAirflow path options; inlet/exhaust height difference available
Opening free areaNet free area required (from Qv and design inlet/outlet velocity)Gross louvre area = net free area ÷ free-area ratio; specified for inlet and outlet separately
System resistance and fan dutyResistance of louvres, filters (clean and dirty), enclosure, ductwork and exhaust; redundancy requirementFan duty point (Qv at total Pa); standby arrangement; motor power
Enclosure and airflow matchingTransformer enclosure type, enclosure ventilation slot positions and effective areaRoom layout must expose enclosure openings to airflow; clearances specified
Control and alarm coordinationTransformer winding temperature sensor outputs; alarm and trip setpointsFan start/stop logic; alarm on fan failure; inlet damper control
Access and maintenanceFilter change interval; fan service access requirementFilter location and access clear of live parts; scheduled maintenance interval
Commissioning measurementMethod statement for verifying delivered airflow at realistic loadMeasurement points, instruments and pass criteria; thermal survey protocol

For a project using XBRELE cast-resin dry-type transformers, the agreed loss data, cooling class, enclosure type and maximum inlet temperature should be obtained directly from the product team. The catalogue page at xbrele.com/power-distribution-transformers/dry-type-transformer/ provides the product range and reference data starting point. Specific project data — including confirmed loss values at operating temperature, enclosure ventilation area and thermal alarm settings — should be discussed with XBRELE before the ventilation brief is issued to building services.

To submit a project brief or request loss and enclosure data for a specific transformer size and cooling class, use the contact route at xbrele.com/contact/.


அடிக்கடி கேட்கப்படும் கேள்விகள்

Does the rated kVA determine how many air changes per hour are needed?

No. The rated kVA is the transformer’s output capacity, not its heat output. Units with different ratings, loading and loss designs can have similar heat loads; a larger unit is not automatically the larger room heat source at its actual duty. Air changes per hour is a ventilation metric that depends on room volume, which is not directly related to transformer losses. The correct starting point is the actual watt losses at the operating load factor, not a rule based on kVA rating or air changes.

Do the fans mounted on the transformer coil assembly ventilate the room?

No. Coil-mounted fans circulate air across the transformer’s own windings to improve heat transfer from conductor to air. They are part of the transformer’s thermal rating system; AF (forced-air) cooling may support a higher declared duty than AN (natural-air), subject to the manufacturer’s rating, duration and service conditions. But the heat still enters the room. The room ventilation must remove it. Coil fans also add their own motor heat to the room load. Treating coil fans as room ventilation is a design error that leads to undersized room ventilation.

What if the outdoor ambient temperature is close to the transformer’s maximum permitted inlet air temperature?

Check the temperature of the air actually entering the transformer’s cooling path, including any local warming and recirculation. The room heat-balance ΔT is exhaust minus room intake; it is not the difference between outdoor temperature and the OEM’s maximum permitted cooling-air temperature. Clean air at the specified OEM limit can still cool a transformer within its declared loading and cooling conditions. The design must prevent that air being warmed beyond the applicable limit before reaching the unit and must reject the room losses along a validated path. If outdoor air itself exceeds the permitted intake condition and there is no cooler air source, increasing ventilation alone cannot reduce intake temperature below outdoor temperature. Then evaluate active cooling or an OEM-approved change of duty.

Can a simplified natural-ventilation opening area formula be applied universally to dry-type transformers?

No. Simplified natural-ventilation formulas, such as the one documented in Schneider Electric’s FAQ FA358662, are derived for specific conditions: a stated annual-average ambient temperature, an altitude limit, a specific loss reference temperature and an absence of obstructions. The example in that document applies to an oil-filled transformer with losses evaluated at 75 °C. Applying the same coefficient to a dry-type cast-resin transformer without adjusting for its different operating temperatures, geometry and loss profile does not establish that the opening is adequate. The opening area formula is an approximation that collapses a physical model (buoyancy driving pressure versus opening resistance) into a single coefficient valid only within its stated scope. Outside that scope, the engineer must either return to the physical model, obtain a validated formula specific to the transformer type and room configuration, or confirm the opening sizes through commissioning measurements at representative load.

எக்ஸ்பிஆர்இஎல்இ-யின் சந்தைப்படுத்தல் இயக்குனர் ஹன்னா ஜு
ஹன்னா

ஹன்னா XBRELE-இல் நிர்வாகி மற்றும் தொழில்நுட்ப உள்ளடக்க ஒருங்கிணைப்பாளராக உள்ளார். அவர் MV/HV சுவிட்ச்கியர், வெற்றிட உடைப்பான், காண்டாக்டர்கள், இடையூறு செயலிகள் மற்றும் டிரான்ஸ்ஃபார்மர்கள் ஆகியவற்றில் இணையதள அமைப்பு, தயாரிப்பு ஆவணங்கள் மற்றும் வலைப்பதிவு உள்ளடக்கத்தை மேற்பார்வையிடுகிறார். உலகளாவிய வாடிக்கையாளர்கள் நம்பிக்கையுடன் தொழில்நுட்ப மற்றும் கொள்முதல் முடிவுகளை எடுக்க உதவும் வகையில், தெளிவான, நம்பகமான மற்றும் பொறியாளர்களுக்கு ஏற்ற தகவல்களை வழங்குவதே அவரது முக்கிய நோக்கமாகும்.

கட்டுரைகள்: 189