Нужны полные технические характеристики?
Загрузите наш каталог продукции 2025 года, чтобы ознакомиться с подробными чертежами и техническими параметрами всех компонентов распределительного устройства.
Получить каталог
Загрузите наш каталог продукции 2025 года, чтобы ознакомиться с подробными чертежами и техническими параметрами всех компонентов распределительного устройства.
Получить каталог
Загрузите наш каталог продукции 2025 года, чтобы ознакомиться с подробными чертежами и техническими параметрами всех компонентов распределительного устройства.
Получить каталог
Calculate a preliminary heat load and airflow, then check net free openings, fan duty, recirculation and maintenance conditions for a dry-type transformer room.
A dry-type transformer does not consume the electrical power flowing through it. It converts voltage and current, delivering useful energy to the connected load. The gap between input power and output power is dissipated as heat, and virtually all of that heat ends up in the air of the room where the transformer is installed. Sizing the room ventilation means calculating how much heat needs to be removed, determining what airflow is required to remove it, designing the opening sizes and positions that allow that airflow, and checking that the layout actually delivers conditioned air to the heat source rather than bypassing it. Each of these steps requires specific assumptions, and the assumptions have to be coordinated before a ventilation brief can be handed to a building services engineer.
This article works through the full chain from rated losses to a ventilation design brief, with explicit attention to what changes between a preliminary estimate and a final design.
The rated kVA figure on a transformer nameplate is the apparent power the transformer can continuously deliver to the load. It is not a measure of heat generation. Heat generation is the difference between input and output power: the electrical losses in the transformer’s magnetic core and its windings. These losses appear as heat in the transformer itself, and that heat is then transferred to the surrounding air.
This distinction matters immediately when thinking about ventilation. For an illustrative transformer with agreed no-load loss P0 = 2 kW and rated-current load loss Pk = 10 kW, the preliminary loss estimate at rated current is 12 kW. That is the thermal contribution to assess, rather than the nameplate kVA. These assumed losses describe no XBRELE model.
A second distinction is equally important: the coil cooling of the transformer is not the same as room ventilation. Many dry-type transformers are built with fans mounted on the coil assembly that circulate air across the windings to increase heat transfer from the windings to air. These fans serve the transformer’s specified cooling duty and may support a higher load for the duration and conditions stated by its manufacturer. They do not remove heat from the room. They transfer heat from the winding surface into the room air more efficiently, which can increase the room heat load if the fans allow a higher operating current, but the fans themselves are part of the transformer’s internal thermal management, not a ventilation system. The room ventilation must remove whatever heat has entered the room air, regardless of how it got there.
Schneider Electric’s substation ventilation guide treats transformer and other room losses together and describes low/high openings for buoyancy-assisted flow. Moisture control also matters: condensation can form when equipment surfaces are colder than the local air’s dew point, including when warm humid air reaches cold equipment. Airflow and temperature changes therefore need to be assessed with the humidity pattern.

Before converting heat to airflow, the heat load itself must be correctly assembled. This is where engineers most often underestimate the complexity of the preliminary step.
For a transformer carrying a load expressed as a fraction K of its rated current, the total losses at a fixed reference temperature can be approximated as:
P_total = P0 + K² × Pk
where P0 is no-load loss at the specified voltage and frequency, and Pk is load loss at rated current and its stated reference temperature. Pk includes winding resistance loss and additional eddy/stray losses; it is broader than copper I²R loss alone.
This formula is a useful preliminary approximation based on sinusoidal rated-frequency loading at constant temperature. P0 is essentially constant regardless of load; it represents continuous magnetic cycling losses in the core and runs every hour the transformer is energised, even at no load. Pk scales with the square of the load current because resistive heating in copper is proportional to I².
For a preliminary heat-load estimate, applying this formula with catalogue P0 and Pk values and an expected load factor K gives a usable starting figure. However, several adjustments are required before the estimate becomes a credible design input.
Operating temperature correction. Published P0 and Pk values are stated at a specific reference temperature (which must be identified for the actual dry-type design). Resistance loss rises when operating conductor temperature is above the stated reference and falls when it is below it. Additional losses need their appropriate correction. Use the supplier’s loss calculation for the intended current, temperature, voltage and frequency; do not assume every operating case produces more loss than the reference value.
Harmonic loading. The K² scaling applies to fundamental-frequency sinusoidal current. Non-linear loads, variable speed drives, UPS systems and data-centre equipment introduce harmonic current components. Harmonics affect resistance loss through total RMS current, while winding eddy and other stray losses respond differently to the harmonic spectrum and conductor geometry. An n²-weighted current expression is an approximation used for some winding eddy-loss assessments, not a multiplier for every load-loss component. THD alone omits the distribution among harmonic orders; provide the spectrum and duty to the supplier for an appropriate loss assessment rather than multiplying all Pk by a K-factor.
Fan and auxiliary motors. If the transformer has coil-mounted fans, the fan motor power is an additional room heat contribution. Control panels, cooling fan contactors and any other continuously energised auxiliaries in the room add to the heat load.
Other room equipment. Switchgear panels, metering cubicles, power factor correction capacitors and any other equipment in the same ventilated space contribute their own losses to the room heat load. The ventilation must handle all concurrent heat sources, not just the transformer.
Solar and wall transfer. A room with sun-exposed walls or a roof will have an additional conductive and radiative heat gain that varies with season and time of day. South- or west-facing exposures in summer can add kilowatts of heat gain that have nothing to do with the electrical installation.
The design heat load is the worst credible concurrent case: the transformer at the expected maximum load factor (the actual duty may differ from rated current), all auxiliary equipment running, and the peak seasonal ambient condition. Because P0 runs continuously, the transformer should be assumed energised even at minimum load. The seasonal worst case for heat removal is usually the hottest day of the year, combined with the highest electrical load. These may or may not coincide; for a commercial building, peak air conditioning load and peak electrical transformer load often do occur together.
For a real project, obtain agreed no-load and load losses with their voltage, frequency, current and reference-temperature conditions, together with the intended harmonic profile, enclosure and cooling configuration. The catalogue page at xbrele.com/power-distribution-transformers/dry-type-transformer/ is the starting point for requesting project-specific loss data.

Once the room heat load P (in watts) is established, the required volumetric airflow follows from a sensible heat balance on the room air.
The room behaves as a steady-state heat exchanger. Cool air enters at inlet temperature T_in, absorbs heat from all sources in the room, and leaves at exhaust temperature T_out. The power removed by the airflow is:
P = ρ × cp × Qv × ΔT
where: – P is the total room heat load in watts (W) – ρ is the air density in kilograms per cubic metre (kg/m³) – cp is the specific heat of air at constant pressure in joules per kilogram-kelvin (J/kg·K) – Qv is the volumetric flow rate in cubic metres per second (m³/s) – ΔT = T_out − T_in is the temperature rise of the air between intake and exhaust, in kelvin (K)
Rearranging for the required flow rate:
Qv = P / (ρ × cp × ΔT)
The ΔT in this formula is the temperature difference between the exhaust air leaving the room and the inlet air entering the room. It is the rise in room air temperature across the ventilated space, not the winding temperature rise of the transformer. Winding temperature rise describes the thermal gradient between the winding conductor and the surrounding air; it is an insulation and thermal-class specification of the transformer itself. Room air can be significantly cooler than the winding surface while still being unacceptably hot for inlet air to the transformer. These are two separate design parameters that must not be conflated.
Consider a project scenario with the following assumed values:
Applying the formula:
Qv = 12 000 / (1.2 × 1005 × 10) = 12 000 / 12 060 ≈ 0.995 m³/s
Converting to cubic metres per hour: 0.995 × 3600 ≈ 3 582 m³/h
These numbers are illustrative for this assumed scenario and do not represent a rating for any XBRELE product or a standard installation requirement. Every assumption must be justified for the actual project:
A common error in preliminary calculations is to assume that inlet air temperature equals ambient outdoor air temperature. If the inlet opening is positioned close to the exhaust, or if the exhaust air escapes into a space that feeds back into the inlet, the effective inlet temperature is higher than ambient. The energy balance holds regardless, but the calculated heat rise remains P/(ρ cp Qv), while the actual cooling air reaching the transformer is warmer. If an independently justified room or exhaust-temperature limit remains fixed, the allowable ΔT becomes smaller and more flow may be needed. If inlet air entering the room is already warm because it has picked up heat from an adjacent space or from exhaust recirculation, the ventilation system is working against a reduced temperature budget. This is a layout problem as much as a calculation problem, and it must be resolved before the opening and fan sizes are finalised.

Having established a required volumetric flow rate, the next step is to design the openings and, where natural buoyancy is insufficient, the mechanical fans. This is where the gap between preliminary estimates and engineered design is widest.
A ventilation opening is typically covered by a louvre, grille, mesh or damper. The gross face area is the total wall area occupied by the opening. The net free area — sometimes called the free air area — is the actual unobstructed area through which air can flow. For a typical louvre with inclined blades, the net free area is substantially less than the gross face. An illustrative louvre with a free-area ratio of 50% has 0.5 m² of net free flow area for each 1 m² of gross face area. At the same design velocity, the actual volume flow through a 1 m² louvre with 50% free area is half what it would be through an open 1 m² hole.
This matters because the air velocity through the net free area is what determines both the volume flow and the pressure drop across the opening. If the design is based on the gross area, the actual air velocity through the blades is double the assumed value, the restriction can be substantially greater. Under a fixed loss coefficient and the same flow, a velocity-squared approximation gives four times the pressure loss; the actual delivered flow is determined by the fan/system or buoyancy balance.
For design purposes, the gross louvre face area must be derived from the required net free area, not the other way around. If net free area of, say, 0.5 m² is required at the inlet, and the louvre has a 50% free-area ratio, the gross face area of that louvre must be 1.0 m². This distinction applies equally to inlet and exhaust openings.
The pressure loss through the ventilation system is not just the inlet opening and the outlet opening. It is the sum of all resistances along the complete air path: inlet louvre, any ductwork or bends, the transformer enclosure (if the air is routed through it), the room space, any filters, the exhaust louvre, and any dampers. Fans must be selected to deliver the required flow rate against the total system resistance at the design operating point, not against the opening resistance alone.
Filters deserve particular attention. A clean filter has a low, known pressure drop. A dirty filter — one that has accumulated dust over weeks or months between maintenance visits — may have a pressure drop several times higher than the clean value. The fan must deliver the required airflow against the dirty-filter resistance, not the clean-filter resistance. Specifying a fan that just meets flow requirements with a clean filter means the system will be underperforming for most of its operational life.
In the absence of mechanical fans, ventilation depends on the buoyancy of warm air. Warmer air is less dense; it rises and exits through high-level openings, drawing cooler air in through low-level openings. The driving pressure available from buoyancy is proportional to the height difference between inlet and outlet openings and to the temperature difference between the internal and external air. Greater height separation and higher internal temperature both increase the buoyancy driving force.
The airflow delivered by natural convection depends on this driving pressure and on the total resistance of the airflow path, exactly as for a mechanical system. Because the driving pressure is small (typically a few Pascals for typical room geometries and temperature differences), natural ventilation is sensitive to opening resistance. Reducing free area increases resistance; the resulting flow reduction depends on the complete pressure-flow balance.
Simplified opening rules carry specific assumptions. Schneider Electric FAQ FA358662 defines net inlet/outlet areas excluding grille blockage and opening height, with stated conditions of 20 °C annual-average ambient, altitude no greater than 1000 m and an unobstructed path. Its worked example is an oil-filled Minera with losses referenced to 75 °C. Those conditions do not establish the required opening area for a different dry-type room. Use an applicable OEM method or a validated airflow model incorporating the actual heat load, height, resistance, air properties and service conditions; coordinate the final design with the room designer.
Where natural convection is insufficient — either because the available height is small, the internal-to-external temperature difference is limited, or the heat load is high — mechanical fans are needed. Fan selection requires:
Duty point. The fan must deliver the required airflow (m³/h) against the system total pressure (Pa) at the worst operating condition, which is the dirty-filter, maximum-heat-load case.
System curve. Pressure drop in the system scales approximately with the square of flow rate. The fan’s characteristic curve (flow versus pressure) must intersect the system curve at or above the required flow rate.
Redundancy. A single fan failure in a room containing a large transformer can lead to rapid thermal overload. Many installations use two fans in parallel or duty-standby arrangements. The redundancy strategy must be coordinated with the transformer’s OEM thermal limits and alarm/trip settings.
Inlet conditions. A fan mounted immediately behind a louvre with high resistance may be starved of inlet air. The fan static pressure must be matched to the system resistance, including the inlet approach loss.
Enclosure matching. If the transformer is in an IP-rated enclosure, the enclosure’s own ventilation openings become part of the system resistance. The enclosure airflow path must be matched to the external room ventilation to avoid a mismatch where the room has sufficient flow but the enclosure is the bottleneck.

A ventilation system that is correctly sized on paper can still fail to cool the transformer if the air does not follow the intended path through the room.
A high-level inlet close to a high-level exhaust can let fresh air pass directly between openings while cooler replacement air barely reaches the transformer. That internal bypass is different from external recirculation, where discharged warm air returns to the room intake. Either can leave the heat source poorly served despite a satisfactory total-flow measurement.
A low inlet with a high exhaust near the heat source generally favours a useful buoyancy-assisted route. The actual positions must be checked against partitions, enclosure openings and equipment arrangement: their height alone does not prove that the cool air reaches the transformer.
In rooms with complex geometry, partitions, cable trays or multiple items of equipment, the natural airflow path may still bypass the transformer even with low-level inlet and high-level exhaust. Baffles, plenums or directed ductwork can guide air through the heat source rather than around it. The investment in guiding is usually modest but the thermal improvement can be substantial.
As an example scenario: a room initially has both inlet and exhaust positioned at high level, with a short distance between them. Fan capacity tests may show adequate total flow. But thermal measurements show the transformer running hot because most of the air travels directly from inlet to exhaust along the high zone, while the heat source sits at floor level. Relocating the inlet to low level, or adding a baffle that forces incoming air downward before it rises through the heat source, can improve the heat-removal path. Recalculate the resistance after the change and verify delivered airflow and local inlet temperatures; a baffle may also change the fan duty.
As noted earlier, fans mounted on the transformer coil assembly are thermal management devices for the transformer, not room ventilation devices. If a transformer is specified in AN/AF cooling mode (natural air cooling / forced air cooling), the AF mode fans support the manufacturer’s declared load and duration by improving internal heat transfer. They do not exhaust hot air from the room. The room ventilation system must still remove all the transformer losses from the room air, and when the coil fans are running, those fan motors themselves add to the room heat load.
A ventilated transformer enclosure has openings in its casing; the IP code alone does not define its airflow or cooling arrangement. These openings must be accessible to the room airflow. Placing a transformer enclosure hard against a wall, covering its ventilation slots with cable trays, or positioning it in a corner where room airflow cannot reach the enclosure openings will restrict the transformer’s own heat dissipation even if the room ventilation is otherwise adequate. The room layout must allow airflow to reach, surround and exit the enclosure.
Ventilation openings bring outdoor air into the room. Outdoor air carries humidity, dust, insects and other contaminants. Condensation is possible where surface temperature falls below the local dew point; assess shutdowns, cold equipment and incoming humid air together. Filters reduce particulate ingress but add to the system resistance and require maintenance. In dusty, high-humidity or coastal environments, the tradeoff between ventilation adequacy and contamination protection is a genuine design decision that affects both the thermal design and the maintenance schedule.
Fire and smoke dampers, where required by local building regulations, add further resistance and must be in the open position for the ventilation system to function. Their position feedback and control must be coordinated with the ventilation control. These requirements are determined by the responsible building services and fire safety engineers for the specific installation and jurisdiction.
If a mechanical fan fails or an inlet becomes partially blocked, the airflow through the room drops. The transformer’s thermal protection (winding temperature sensors, thermistors or thermocouples) must be coordinated with the OEM’s thermal limits and the project protection study. Fan/airflow failure indication may reveal the problem before a winding-temperature alarm, but neither signal guarantees sufficient intervention time. The transformer’s loading limit under degraded ventilation is set by the OEM based on the specific unit’s thermal design; a universal derating figure does not apply across all units, enclosures and room configurations.
A ventilation design brief is the document that connects the electrical engineer’s transformer selection to the building services engineer’s room design. It should be specific enough to allow the ventilation engineer to size openings, fans and controls without having to make guesses about the transformer or the room.
The following table organises the inputs and outputs that should appear in a coordinated brief.
| Brief Section | Required Input from Electrical Team | Output for Ventilation Design |
|---|---|---|
| Heat load | Agreed P0 and Pk at stated reference temperature, load factor K, harmonic spectrum and operating duty, auxiliary equipment losses, fan motor power | Total room heat load P (W) at worst concurrent case |
| Duty and reference temperature | Expected operating load factor range, seasonal peak, continuous or intermittent duty | Heat load range; maximum and minimum heat load cases |
| Ambient and altitude | Site altitude (m above sea level), outdoor design dry-bulb temperature (summer peak and annual average), humidity range | Air density for calculations; inlet design temperature |
| Maximum inlet temperature | OEM-specified maximum continuous inlet air temperature for the transformer at rated cooling class | Verify air at each transformer cooling intake against OEM ambient/inlet conditions; select the separate room heat-rise case |
| Room geometry | Plan dimensions, ceiling height, positions of transformer, switchgear and other equipment, available wall positions for openings | Airflow path options; inlet/exhaust height difference available |
| Opening free area | Net free area required (from Qv and design inlet/outlet velocity) | Gross louvre area = net free area ÷ free-area ratio; specified for inlet and outlet separately |
| System resistance and fan duty | Resistance of louvres, filters (clean and dirty), enclosure, ductwork and exhaust; redundancy requirement | Fan duty point (Qv at total Pa); standby arrangement; motor power |
| Enclosure and airflow matching | Transformer enclosure type, enclosure ventilation slot positions and effective area | Room layout must expose enclosure openings to airflow; clearances specified |
| Control and alarm coordination | Transformer winding temperature sensor outputs; alarm and trip setpoints | Fan start/stop logic; alarm on fan failure; inlet damper control |
| Access and maintenance | Filter change interval; fan service access requirement | Filter location and access clear of live parts; scheduled maintenance interval |
| Commissioning measurement | Method statement for verifying delivered airflow at realistic load | Measurement points, instruments and pass criteria; thermal survey protocol |
For a project using XBRELE cast-resin dry-type transformers, the agreed loss data, cooling class, enclosure type and maximum inlet temperature should be obtained directly from the product team. The catalogue page at xbrele.com/power-distribution-transformers/dry-type-transformer/ provides the product range and reference data starting point. Specific project data — including confirmed loss values at operating temperature, enclosure ventilation area and thermal alarm settings — should be discussed with XBRELE before the ventilation brief is issued to building services.
To submit a project brief or request loss and enclosure data for a specific transformer size and cooling class, use the contact route at xbrele.com/contact/.
No. The rated kVA is the transformer’s output capacity, not its heat output. Units with different ratings, loading and loss designs can have similar heat loads; a larger unit is not automatically the larger room heat source at its actual duty. Air changes per hour is a ventilation metric that depends on room volume, which is not directly related to transformer losses. The correct starting point is the actual watt losses at the operating load factor, not a rule based on kVA rating or air changes.
No. Coil-mounted fans circulate air across the transformer’s own windings to improve heat transfer from conductor to air. They are part of the transformer’s thermal rating system; AF (forced-air) cooling may support a higher declared duty than AN (natural-air), subject to the manufacturer’s rating, duration and service conditions. But the heat still enters the room. The room ventilation must remove it. Coil fans also add their own motor heat to the room load. Treating coil fans as room ventilation is a design error that leads to undersized room ventilation.
Check the temperature of the air actually entering the transformer’s cooling path, including any local warming and recirculation. The room heat-balance ΔT is exhaust minus room intake; it is not the difference between outdoor temperature and the OEM’s maximum permitted cooling-air temperature. Clean air at the specified OEM limit can still cool a transformer within its declared loading and cooling conditions. The design must prevent that air being warmed beyond the applicable limit before reaching the unit and must reject the room losses along a validated path. If outdoor air itself exceeds the permitted intake condition and there is no cooler air source, increasing ventilation alone cannot reduce intake temperature below outdoor temperature. Then evaluate active cooling or an OEM-approved change of duty.
No. Simplified natural-ventilation formulas, such as the one documented in Schneider Electric’s FAQ FA358662, are derived for specific conditions: a stated annual-average ambient temperature, an altitude limit, a specific loss reference temperature and an absence of obstructions. The example in that document applies to an oil-filled transformer with losses evaluated at 75 °C. Applying the same coefficient to a dry-type cast-resin transformer without adjusting for its different operating temperatures, geometry and loss profile does not establish that the opening is adequate. The opening area formula is an approximation that collapses a physical model (buoyancy driving pressure versus opening resistance) into a single coefficient valid only within its stated scope. Outside that scope, the engineer must either return to the physical model, obtain a validated formula specific to the transformer type and room configuration, or confirm the opening sizes through commissioning measurements at representative load.