Start and run motor panels with an autotransformer symbol at start and a direct supply arrow at run.

MV Autotransformer Starters: Start, Transition and Run Contactor Duties

Map MV autotransformer starter contactor duties through start, transition and run, including interlocks, failed acceleration and supplier data to request.

Краткий вывод

  • Assign duties by function and topology: the start path, winding neutral and run path do different jobs, even when a supplier uses similar contactor hardware.
  • Reduced voltage lowers supply current and available starting torque; inadequate torque margin can extend acceleration and make thermal or aborted-start duty govern selection.
  • Closed transition preserves a supply path through a defined intermediate state. Verify permitted states, transfer duty and failure responses against the actual drawings before accepting the starter.

An autotransformer starter reduces the voltage applied to a medium-voltage motor during acceleration and then switches the motor to full supply voltage for running. This article maps the making, carrying, transfer, and breaking duties that fall on each contactor position across start, transition, and run states, and identifies what sequence evidence a designer or buyer needs to verify the assembly.

The starting autotransformer is a dedicated power transformer whose tapped windings present reduced voltage to the motor terminals during acceleration. It is not the same device as a control-power transformer, which supplies the low-voltage control circuit from the MV bus. Confusing the two leads to wrong sizing and wrong duty assignments. The autotransformer leaves the power path once the motor reaches sufficient speed; at that point the contactors reconfigure so the motor connects directly to line voltage and continues running without transformer losses or impedance.

The Eaton AMPGARD medium-voltage motor control application guide describes this topology as requiring a run contactor and a start contactor with both electrical and mechanical interlocks, the starting autotransformer sized for locked-rotor amperes, and the fundamental distinction between start and run as separate duties. The Littelfuse PGR-6300 manual, section 6.15 describes a closed-transition autotransformer sequence that closes the neutral contactor before the main start contactor and opens the neutral before the run contactor closes, illustrating that the roles and their order matter to the protection relay and to the contactors alike.


Reduced Motor Voltage Also Reduces Available Starting Torque

If the autotransformer tap presents a fraction k of rated line voltage to the motor terminals (where 0 < k < 1), the motor sees k times normal voltage. Because a squirrel-cage motor at locked rotor behaves approximately as a fixed impedance, the motor current drawn from the transformer secondary is also approximately k times the direct-on-line locked-rotor current. The transformer steps that current back to the primary side by the same transformation ratio, so the current drawn from the supply is approximately k squared times the direct-on-line locked-rotor current. At fixed frequency and under the usual approximate motor assumptions, air-gap flux varies with applied voltage and starting torque varies with voltage squared. Available locked-rotor torque is therefore approximately k squared times the direct-on-line value.

These ideal relationships hold only at the moment of starting with fixed rotor impedance and neglect transformer losses, supply impedance, and the effect of the motor’s own voltage dip on the supply. Actual acceleration depends on the difference between motor and load torque and on total rotational inertia. An intersection of their torque-speed curves is an equilibrium point; verify sufficient positive accelerating torque over the required speed range. The relationships are useful for initial sizing and tap selection but are not guaranteed performance curves.

The practical consequence is that too low a tap setting can leave available torque below the load torque at standstill, and the motor will not accelerate at all or will stall at partial speed. For high-inertia loads — large fans, compressors with heavy flywheels, loaded conveyor drives — the torque margin at the selected tap must remain positive throughout the acceleration run. When torque margin is tight, acceleration time extends, and the starting autotransformer and all contactors carry starting-level currents for longer. This directly affects thermal duty and must be reflected in the contactors’ short-time and thermal ratings, not only their continuous current ratings.


Assign Contactor Roles Before Assigning Names

A common closed-transition autotransformer starter uses three functional contactor positions. Naming conventions differ between manufacturers and project documents, so it is more reliable to define roles by what each position must make, carry, and break than to rely on labels such as K1, K2, or K3.

Start-path contactor: Connects the supply to the high-voltage terminals of the starting autotransformer. In the common sequence discussed here, the neutral point is established before the start path is energized. The start-path contactor makes the transformer energizing and motor-starting event, then carries transformer primary current during acceleration. It opens (or is released) during or after the transition sequence, depending on the exact topology.

Neutral-point contactor: Connects the appropriate winding ends of the autotransformer to form the star point, completing the winding configuration that creates the reduced voltage at the motor terminals. Its current and open-contact recovery-voltage duty follow from the winding connection and tap ratio; neither should be inferred from the role name. It is not a protective earth connection; the star point it forms is a floating winding midpoint, not system earth. Opening this contactor during transition turns the remaining energized winding into a series reactor between the supply and the motor.

Run contactor: Connects the motor terminals directly to the supply, bypassing the autotransformer entirely. This position must make full-voltage motor current once the motor has partially accelerated, carry continuous rated current for the full running period, and break the running current on a normal stop or emergency trip.

Three cards identify start path, neutral point and run path duties.
Identify the start-path, neutral-point and run-path duties before mapping the supplier’s contactor labels.

The duty obligations of these three roles differ significantly. In the common topology described here, the start-path position is released for running; it must nevertheless be assessed for starting and aborted-start events. The neutral-point position sees its most severe breaking duty on the deliberate transition step, not on a normal stop. The run position sees its most severe making duty at the moment of transfer, not at initial energization.

RoleNormal making dutyShort-time carryingNormal breaking dutyAbnormal breaking duty
Start pathTransformer energizing and motor-starting eventTransformer primary current during startReleased after transfer (topology dependent)Full starting current on aborted start or emergency trip
Neutral pointEstablishes winding star point before energization in this sequenceWinding-branch current defined by tap and topologyDeliberate neutral-open during transitionSame if transition fails or is aborted
Run pathMotor transfer event at the achieved speedRated motor current in continuous serviceRunning motor current on stopActual current at interrupted transfer or emergency event

Pole counts and contact ratings in an actual assembly must come from the assembly manufacturer’s drawings for the specific topology, not from this generic matrix. Vendor documentation should be verified against project-specific motor data.


Start, Transition and Run: What Changes Electrically

The closed-transition state sequence

In a common closed-transition topology, the sequence moves through three electrical states. Understanding what is energized and what is carrying current in each state is what determines where the contactor duty events actually fall.

Reduced-voltage start state: The start-path contactor and the neutral-point contactor are both closed. The motor is connected to the tapped voltage from the autotransformer secondary. The transformer and both contactors carry starting current. This state persists until the control system determines that the motor has accelerated sufficiently — judged by time, by current decay, or by speed sensing, depending on the protection relay and control design.

Transition state (reactor stage): The neutral-point contactor opens deliberately while the start-path contactor remains closed and the run contactor remains open. Opening the neutral breaks the star point of the transformer winding. The portion of the winding that remains connected between the supply and the motor acts as a series reactor, reducing but not eliminating supply voltage to the motor. The motor remains continuously supplied throughout this period — it neither coasts nor sees an interruption. This is the defining characteristic of closed transition. The motor and the remaining winding carry current during this brief interval.

Run state: With the motor still supplied through the reactor path, the run contactor closes, connecting the motor directly to line voltage. The direct line connection bypasses the transitional impedance. Winding and contactor currents during this commutation depend on the actual circuit and must be assessed accordingly. At this point the topology’s specific logic determines when and how the start-path contactor is released. This varies between designs; following the approved drawing for the actual assembly is required.

Reduced, transition and run cards show impedance blocks only in the first two states above a motor icon.
A common closed-transition arrangement keeps the motor supplied while the winding changes from transformer action to a transitional impedance path and then direct running.

Why continuity is not permission for overlap

Closed transition is designed to preserve the motor supply path throughout the state changes. It does not mean that all contactors can be simultaneously closed at any moment. The sequence includes prohibited overlap states — in particular, closing the run contactor at the same time as holding both the start-path and the neutral contactors closed can short part of the autotransformer winding through the run connection in this topology. The interlocking scheme and control logic must enforce the allowed transitions and block the forbidden ones. The term “closed transition” describes the motor’s supply path, not the state of all contactors simultaneously.

Open transition and its reconnection risks

An open-transition supply band has a gap while the closed-transition band stays continuous through a shaded stage.
Open transition deliberately interrupts the supply path; closed transition preserves a path while the intermediate impedance changes.

Open-transition autotransformer starting, by contrast, interrupts the motor’s supply completely between the reduced-voltage and full-voltage states. The motor coasts and begins to decelerate during the interruption. Its rotor flux decays but does not collapse instantaneously; the decaying rotor flux drives a residual voltage at the motor terminals. If the run contactor closes and reconnects the supply before rotor flux has decayed sufficiently, the residual voltage and the supply voltage may be out of phase. The resulting transient current can be substantially larger than the direct-on-line starting current and can impose severe mechanical torque impulses on the motor and driven equipment. A closed-transition design can avoid the deliberate open interval, but introduces its own transfer and interlock requirements; suitability still depends on the motor, load and approved starter design.

The practical implication for contactors in an open-transition design is that the run contactor must be rated for reconnection duty that may include significant transient overcurrent, and the timing of reconnection must be controlled. This making duty is different from and potentially more severe than a normal direct-on-line start, depending on how much flux has decayed before reconnection.


Rate the Contactors for the Events That Can Actually Occur

Specifying contactor ratings based solely on continuous running current is inadequate for autotransformer starter service. The events that actually determine whether a contactor is correctly rated are dominated by abnormal and infrequent conditions, not by steady-state running.

Normal running current settles to a held level while an aborted start returns to zero during the starting event.
An aborted acceleration can require interruption of starting current, which differs from a normal stop at running current.

Normal and aborted starts

In a normal successful start, the start-path and neutral-point contactors carry starting current for the full acceleration time and then are released or opened in sequence. The run contactor makes the transfer current and then carries running current indefinitely. This normal sequence is the baseline duty; aborted starts and failed transfers add different demands.

An aborted start — where a trip or manual command interrupts acceleration before the motor reaches running speed — requires one or more contactors to interrupt starting current. Starting current in an MV motor circuit may be several times full-load current. The contactor assigned to break in this event must be rated for that interrupting duty. Identifying which contactor is required to break in an aborted start depends on the control logic for the specific assembly; it cannot be assumed without reviewing the sequence diagram.

Emergency interruption and failed transfer

An emergency stop command arriving during acceleration requires the starter to clear the circuit promptly. If the motor has not yet reached the transition state, clearing may require the start-path contactor to break transformer primary current. If transition has begun and the neutral has opened, the remaining current path and the contactor assigned to break it must both be evaluated.

Failed transfer — where the transition sequence starts but the run contactor does not close as commanded — can leave the motor in the reactor stage until the designed protective action clears it. The motor and winding carry current in a state not designed for continuous operation. The protection relay must detect this condition and trip, requiring a contactor to break an intermediate-state current. The contactor rated for this event and the relay response time together determine whether the transformer winding is damaged by prolonged reactor-stage current.

Stuck contactor and repeated starts

If a contactor fails to open on command — a welded or mechanically stuck contact — the topology is in an unintended state. The control system must detect the contradiction between command and feedback and initiate a protective trip. The design must identify another qualified switching or isolation device, potentially the upstream circuit breaker, that can remove the relevant supply paths. Its ability to clear this event depends on the topology and its declared interrupting duty; another contactor cannot automatically be assumed to provide isolation. This scenario is a reason to include feedback monitoring in the acceptance test, not only command monitoring.

Repeated starts impose cumulative thermal duty on the autotransformer windings and on all contactors that carry starting current. MV motor standards and application guides specify the number of successive cold and hot starts that equipment must withstand. Contactor thermal ratings must accommodate the total energy deposited during the full permitted start sequence, not only a single start event.

Separating rating categories

For MV vacuum contactors in autotransformer starter service, the relevant ratings to verify are: the declared load and overload making capacity with its stated current basis and test conditions, the short-time withstand current and duration, the continuous current rating, and the declared breaking capacity and applicable duty category. Keep any short-circuit making peak rating separate: it does not establish motor-switching or transfer capability. No AC utilization category should be applied from low-voltage contactor standards without confirming that the specific MV contactor standard and category actually apply to the duty. The assembly manufacturer and the contactor manufacturer must both confirm the applicable standard, the declared duty category, and the interrupting performance for the specific circuit conditions including supply short-circuit level.

The Eaton AMPGARD guide confirms that locked-rotor amperes determine sizing for the autotransformer starter, and that start and run are distinct duties requiring separate contactors with electrical and mechanical interlocks. The specific ratings for any given assembly must come from the assembly’s certified documentation, not from general published curves for a different manufacturer’s equipment.

For project inquiries, the XBRELE vacuum contactor catalogue lists the CKG, JCZ, and LCZ series families. Configuration-specific ratings and documentation should be requested directly; the catalogue entries are not independent verification of ratings or test results for a specific application.


A Supplier Worksheet and Sequence Acceptance Plan

Per-role duty input worksheet

Before requesting contactor selection or assembly review, compile the following data for each role. Gaps in this list typically result in returned requests or unverifiable assumptions.

Motor data (required for all roles): – Rated voltage, frequency, and rated power – Full-load current (FLA) – Locked-rotor current (LRA) at rated voltage – Locked-rotor torque and breakdown torque (or torque-speed curve if available) – Rotor moment of inertia (GD² or J) – Number of poles and synchronous speed – Insulation class and thermal withstand class

Load data: – Load torque-speed curve or load type (fan, pump, compressor, conveyor) – Load moment of inertia referred to motor shaft – Duty cycle: continuous, intermittent, or repeated short-time

Starting duty data: – Autotransformer tap ratio (or requested motor voltage during start) – Maximum permitted starts per hour – Maximum permitted successive starts from cold – Maximum permitted successive starts from hot (motor at operating temperature) – Minimum acceptable torque margin at locked rotor on the selected tap

Supply data: – Nominal supply voltage and frequency – Maximum supply short-circuit level at the starter (symmetrical kA) – Minimum supply voltage during the start event (voltage dip under full LRA) – Earthing system (solidly earthed, impedance earthed, or isolated)

Control data: – Control supply voltage and source – Coil burden of each contactor (VA, resistive and inductive) – Control power transformer capacity

Per-role event duty matrix and acceptance evidence

For each role, complete an event row against the approved power and control drawings. The intended sequence is an engineering input, not a universal terminal list.

Event to reviewEvidence to recordCondition that must be resolved before acceptance
Reduced-voltage startCommands, actual state feedback, start current and acceleration durationUnconfirmed neutral formation, wrong start order or prohibited run closure
Neutral opening and reactor stageNeutral-open evidence, remaining supply path, winding current and permitted stage durationFailed opening or an unbounded intermediate state
Run transferConfirmed neutral state, run command and feedback, measured or validated transfer dutyRun closure without required permissives or excessive transfer stress
Start-path releaseDrawing-defined release order, feedback and current commutationUnintended energized winding branch or contradictory status
Aborted accelerationIdentified interrupting device, actual event duty and coordinated protective responseA contactor being assigned a breaking duty outside its declared capability
Missing or contradictory feedbackDefined alarm, inhibit or trip response for the specific failureControl progression based only on a command that was not proved

Commissioning should use an approved isolated test plan that separates control-logic simulation from power-duty verification. Healthy sequence, failed feedback, unavailable transfer and abort cases can be assessed with the permitted simulator or relay-test arrangement before a motor is connected. The plan must define how any temporary test configuration is controlled and restored; it must not depend on improvised jumpers or defeated interlocks. Where actual motor-duty verification is required, the responsible engineer and manufacturer must define the safe test scope, instruments, acceptance basis and operating envelope. Record command and feedback timestamps, current evidence, prohibited-state blocking and restoration of the final configuration.

For project-specific assembly review, send a complete data package using the XBRELE contact form. The vacuum contactor families listed in the catalogue can be reviewed against project duty; a complete starter assembly supply claim should not be assumed from catalogue presence alone.


Часто задаваемые вопросы

Do all three contactors in an autotransformer starter need the same current rating?

No, and specifying identical ratings for all three positions is usually either over-specified in some positions or under-specified in others. The start-path contactor must carry transformer primary current during the full acceleration period and may need to interrupt starting current on an aborted start, so its short-time and breaking ratings are dominant. The neutral-point contactor carries a winding-branch current set by the tap ratio and connection and must perform the specified transition interruption. Its carrying, breaking and recovery-voltage duties all need confirmation; its current is not universally lower than primary current. The run contactor must make motor current at partial speed at the transition moment and carry full-load current continuously; its making rating at transfer and its continuous rating are the governing parameters. These three duty profiles are different enough that the contactors may legitimately be of different frame sizes or types, depending on the manufacturer’s range. Using the same part number for all three positions simplifies spares management but requires that the shared rating satisfies each role’s worst-case event, which must be verified separately for each position.

Is closing the run contactor simultaneously with the start-path and neutral contactors the same as closed transition?

No. Closed transition refers to maintaining a continuous supply path to the motor throughout the state changes, not to simultaneously closing all contactors. For the common topology discussed here, the prohibited all-closed combination can short part of the autotransformer winding rather than produce a controlled transition. In a correctly implemented closed-transition sequence, the neutral-point contactor opens deliberately before the run contactor closes, leaving the motor supplied through the transformer winding acting as a reactor. The run contactor then closes while that reactor path is still active, ensuring the motor is never without supply. The key characteristic is uninterrupted motor voltage, achieved through a carefully ordered sequence of individual contactor operations and enforced by interlocking. The control system must prohibit the forbidden overlap states, not simply allow any contactor to close at any time.

How does a high-inertia load change the starting duty on the autotransformer and its contactors?

A high-inertia load extends the time the motor spends in the starting impedance range, which is the time the autotransformer and the start-path and neutral-point contactors carry starting current. Where a standard HVAC pump might accelerate to near synchronous speed in a few seconds on a typical tap, a large induced-draft fan or a compressor with significant flywheel may take tens of seconds. During this entire period the autotransformer carries the transformer primary current and accumulates heat in its windings; the start-path contactor carries the same current and accumulates heat in its contacts and coil. The thermal starting duty — expressed as the integral of I²t over the starting period — may govern the autotransformer’s design temperature rise and the contactor’s short-time thermal rating more than any peak current value. If the selected tap produces insufficient torque margin, the motor may not fully accelerate within the allowable starting time, requiring either a higher tap (increasing supply current) or a different starting method. High-inertia applications therefore require the torque-speed curve, the load inertia, and the thermal withstand curve to be evaluated together, not each in isolation, before specifying the autotransformer tap ratio and contactor thermal ratings.

Ханна Чжу, директор по маркетингу XBRELE
Ханна

Ханна является администратором и координатором технического контента в XBRELE. Она курирует структуру веб-сайта, документацию по продуктам и контент блога, посвященный распределительным устройствам среднего и высокого напряжения, вакуумным выключателям, контакторам, прерывателям и трансформаторам. Ее основная задача — предоставлять четкую, надежную и удобную для инженеров информацию, чтобы помочь клиентам по всему миру принимать уверенные технические и закупочные решения.

Статей: 198