Conceptual illustration of current transformers around a conductor with metering and protection devices in the background

Объяснение классов точности трансформаторов тока (ТТ) (0,2/0,5, 5P/10P): Измерение и защита

Understand CT accuracy classes 0.2S, 0.5S, 5P and 10P, including rated burden, effective ALF and checks for metering and protection applications.

Последнее обновление: .

Current transformers supply measuring instruments and protection relays with scaled current signals. Metering classes describe measurement accuracy over a specified load-current range; protection classes describe performance under the fault conditions covered by their designation. A metering-class label alone does not establish suitability for protection, and a protection-class label alone does not establish revenue-metering accuracy.

В этом руководстве приведены обозначения классов точности по стандарту IEC 61869-2, объяснены технические различия между классами измерения (0,1, 0,2, 0,5) и классами защиты (5P, 10P), а также даны практические рекомендации по выбору для средневольтных систем.

Что такое классы точности КТ?

A CT accuracy class defines permissible errors under specified current, burden, frequency and test conditions. For a metering CT, the class number identifies the rated-current ratio-error limit; other test currents have their own limits. In a 5P or 10P designation, the number identifies the composite-error limit at the rated accuracy-limit primary current, not the ratio-error limit at normal load.

Существуют две различные системы классификации. Классы измерения (0.1, 0.2, 0.5, 1.0) оптимизируют точность при нормальных рабочих токах - обычно от 5% до 120% от номинального тока. Классы защиты (5P, 10P) ставят во главу угла производительность в условиях неисправности, сохраняя точность при токах, значительно превышающих нормальный режим работы.

Metering and protection impose different design requirements. A CT may contain separate metering and protection cores, and some designs carry more than one accuracy designation. Select each core using its declared ratings and the connected equipment requirements; neither core size nor material alone proves its accuracy class.

Как трансформаторы тока вносят погрешности в измерения

Part of the primary ampere-turns supplies the core excitation rather than the secondary load. The resulting exciting current, together with the secondary circuit impedance, produces ratio error and phase displacement.

Ошибка соотношения (ε) is the difference between the primary current inferred from the rated ratio and the actual primary current, expressed as a percentage of the actual primary current. With a rated ratio of 1000/5 A, a secondary reading of 4.98 A at 1000 A primary gives (200 × 4.98 − 1000) / 1000 × 100 = −0.4%. The error varies with current and burden.

Смещение фазы (δ) измеряет угловую разницу между фазами первичного и вторичного тока, выраженную в минутах дуги. Идеальное преобразование дает нулевой сдвиг фаз; реальные ТТ демонстрируют небольшие смещения из-за требований к току намагничивания.

Core material, geometry, turns and excitation characteristics all influence CT performance. Rated output is stated in VA at the rated secondary current. Check the manufacturer’s declared burden range and burden power factor as well as the VA rating: a very small connected burden is not automatically within the metering accuracy guarantee.

The limits apply at the current and burden conditions specified for the class. At rated primary current, Class 0.2 has ratio-error and phase-displacement limits of ±0.2% and ±10 minutes. For protection classes, the rated-current ratio-error limits are ±1% for 5P and ±3% for 10P; their respective composite-error limits at the rated accuracy-limit current are 5% and 10%.

Классы точности измерительных СТ: 0,1, 0,2, 0,5 и расширенный класс “S”

Metering classes specify ratio-error and phase-displacement limits at several test currents. The table lists the limits at 100% rated current and the covered current range. It does not mean that the rated-current error limit applies unchanged over that entire range; use the full class table and the CT’s declared burden conditions for selection.

КлассОшибка соотношения при 100% ВPhase displacement at 100% InSpecified current rangeТиповое применение
0.1±0,1%±5 мин5-120%Лабораторные эталонные стандарты
0.2±0,2%±10 мин5-120%Учет доходов от передачи электроэнергии
0.2S±0,2%±10 мин1-120%Учет доходов от переменной нагрузки
0.5±0,5%±30 мин5-120%Учет на распределительных подстанциях
0.5S±0,5%±30 мин1-120%Учет доходов в промышленности
1.0±1,0%±60 мин5-120%Индикаторные инструменты

The “S” suffix identifies metering classes with additional low-current requirements. Classes 0.2S and 0.5S include a 1% rated-current test point, whereas the ordinary classes listed above start at 5%. Error limits differ by test point. Select a class and ratio that cover the expected minimum load and the applicable metering requirements.

For variable-load facilities, compare the expected minimum primary current with the CT rating before choosing between 0.2 and 0.2S. Billing value alone does not define the required class. Include the meter, voltage measurement and wiring in the overall measurement-accuracy assessment.

Instrument security factor (FS) describes the overcurrent behavior specified for a metering core at rated burden. FS5 and FS10 are common declared ratings, but the accuracy class alone does not prescribe a universal saturation multiple. Reducing the connected burden can increase the current at which the core saturates. Verify FS and the meter’s withstand capability rather than assuming every metering CT saturates at 2–5 times rated current.


Metering CT selection checks

  • Compare the expected minimum load with the class test points and the CT ratio.
  • Verify the complete connected burden is within the CT’s declared metering accuracy range.
  • Obtain the selected meter’s actual input burden; verify accuracy at the resulting total burden.
  • Запрашивайте сертификаты заводских испытаний с указанием фактических погрешностей измерений, а не только соответствия классу

Классы точности защитных ТТ: Расшифровка обозначений 5P и 10P

Классы защиты имеют другую систему обозначений, отражающую их основную функцию: точное измерение тока повреждения. Обозначение “5P20” кодирует три параметра, необходимых для координации работы реле.

Номенклатурная разбивка:

  • 5 = Предел погрешности композита (максимум 5%)
  • P = Обозначение класса защиты
  • 20 = rated accuracy limit factor at rated burden; the specified composite-error limit is checked at 20 times rated primary current
КлассКомпозитная ошибка в ALFОбщие ценности ALFТиповое применение
5P≤5%10, 15, 20, 30Overcurrent protection; verify each relay application
10P≤10%10, 15, 20Overcurrent protection where the scheme accepts 10P

The accuracy limit factor (ALF) is the rated accuracy-limit primary current divided by the rated primary current. A 1000/5 A, 5P20 CT has a rated accuracy-limit current of 20,000 A at its rated burden. This is a defined steady-state error test condition, not a sharp physical saturation threshold or a guarantee of transient performance.

For a 5P20 CT, the composite error must not exceed 5% at 20 times rated primary current under the specified test conditions and rated burden. Composite error includes waveform distortion and is not a signed ±5% ratio-error band. DC offset, remanent flux and the required operating time can impose additional CT requirements.

Initial steady-state screening: if the scheme requires class accuracy at the maximum symmetrical through-fault current, compare the effective ALF at the actual burden with that fault-current multiple.

Required effective ALF ≥ Maximum symmetrical through-fault current ÷ CT rated primary current

For a 12.5 kA symmetrical fault and a 500/5 A CT, the fault-current multiple is 12,500 / 500 = 25.

At rated burden, 5P20 alone does not demonstrate the above 25-times screening requirement; a 5P30 rating would cover that steady-state multiple. Final selection still requires the relay manufacturer’s criteria, actual secondary burden, fault duration and transient assessment. Some protection functions tolerate partial CT saturation, so this screening rule is not a universal relay-sizing formula.

Protection CT selection also involves excitation characteristics, secondary winding resistance and short-time thermal and dynamic ratings. A 5P or 10P designation does not replace these checks. For differential or transient duties, the relay manufacturer may specify PX, PR or a transient class, or give a calculation for an acceptable P-class CT.

Счетчики и защитные СТ: сравнение по отдельности

The following comparison summarizes the different performance specifications. Individual CTs can have additional ratings beyond the class names shown.

ПараметрИзмерительный прибор CTЗащита CT
Основная функцияВыставление счетов, мониторинг энергопотребленияОбнаружение неисправностей, работа реле
Диапазон точности1-120% из номинальных (S класс)Rated error limit at ALF × rated current and rated burden
Спецификация ошибокОшибка соотношения + сдвиг фазRated-current ratio error and composite error at ALF
Поведение при насыщенииSpecified by FS and burden; not by metering class aloneSpecified accuracy-limit and transient characteristics
Основной дизайнDesign depends on accuracy, burden and FSDesign depends on burden, fault and transient duty
Типичные классы0,2, 0,2 С, 0,5, 0,5 С, 1,05P10, 5P20, 10P10, 10P15
Подключенные устройстваСчетчики кВт/ч, анализаторы мощностиРеле защиты, регистраторы неисправностей

A saturated CT produces a distorted secondary waveform. Depending on the relay function and settings, this can delay operation or affect differential stability. The magnitude and timing of the effect must be assessed for the actual protection scheme; they cannot be inferred from the metering class alone.

Separate cores allow the metering burden and protection burden to be specified and tested independently when both functions are needed.

Эффект нагрузки и практические соображения по выбору

Connected burden affects the voltage the CT must develop and therefore its accuracy and saturation behavior. Include the relay or meter input and the complete secondary wiring circuit. Keep the metering burden within its declared accuracy range, and calculate protection performance at the actual burden.

Компоненты бремени включают:

  • Instrument burden: use the selected meter, relay or transducer input data.
  • Нагрузка на проводник: сопротивление вторичного кабеля (значительное для длинных линий)
  • Connection burden: include terminals and test switches using their actual resistance.

Lead burden calculation for a separate outgoing and return pair:
Lead VA = Isecondary² × Rloop = Isecondary² × 2 × Rone-way

Example: a 50 m one-way run with a measured or calculated one-way resistance of 0.35 Ω has a 0.70 Ω loop. At 5 A, its burden is 25 × 0.70 = 17.5 VA; at 1 A, it is 0.70 VA. Use the cable resistance at the design temperature and the actual return-circuit arrangement.

Это объясняет, почему вторичные кабели 1 А подходят для длинных кабельных трасс - нагрузка на них снижается на 25× по сравнению с вторичными кабели 5 А для идентичного кабеля.

Контрольный список отбора:

  • Obtain maximum and minimum fault currents and the relay operating-time requirements.
  •  Сумма общей нагрузки, включая сопротивление свинца
  • Verify the declared burden conditions for metering and the effective ALF for protection.
  • Include credible future fault levels and transient duty using the relay manufacturer’s calculation method.
  • Choose the metering class and ratio to cover the actual load range and project requirements.

Protection CT specification checks

  • For auto-reclosing, assess remanence, fault duration and the required operating cycle.
  • For differential protection, follow the selected relay’s CT ratio and saturation requirements.
  • Use the relay’s actual input burden and the complete wiring burden when calculating effective ALF.
  • Request excitation curves and secondary winding resistance when required by the protection calculation.

Двухъядерные ТТ и интеграция распределительных устройств

Большинство установок среднего напряжения требуют как учета, так и защиты от каждого фидера. Двухжильные (или многожильные) ТТ решают эту задачу благодаря наличию отдельных магнитопроводов, намотанных на один и тот же первичный проводник.

Illustrative dual-core specification, subject to the actual meter, relay and wiring calculations:

  • Ядро 1: класс 0,5S, нагрузка 10 ВА (измерение дохода)
  • Сердечник 2: 5P20, нагрузка 30 ВА (реле защиты)

Specify and verify the accuracy and burden of each core separately. Confirm metering FS, protection performance, insulation level and the assembly’s thermal and dynamic withstand ratings. Separate cores do not remove the need to coordinate the complete secondary circuits.

Интеграция с вакуумные выключатели среднего напряжения requires a common system fault study. ALF is a dimensionless ratio and cannot be compared directly with a breaker breaking-current rating in kA. Evaluate the CT against the maximum through-fault current, its primary rating, actual burden and relay requirements. Separately verify the CT short-time/dynamic withstand ratings and the breaker interrupting duty. Ask the производители компонентов for the data needed to complete those checks.

При выборе ТТ для новых установок предоставьте поставщику следующие данные:

  • Максимальный уровень неисправности системы (кА)
  • Диапазон тока нагрузки (от минимального до максимального)
  • Расстояние по кабелю до измерительных/релейных панелей
  • Конкретные модели счетчиков и реле с данными о нагрузке

Распространенные ошибки спецификации КТ и как их избежать

Review the following specification errors before purchasing or replacing a CT.

Ошибка 1: Использование измерительного ТТ для защиты

A metering class alone does not verify fault-current performance. Решение: select a core with the protection characteristics required by the relay scheme and verify its performance at the actual burden, through-fault current and required operating time.

Ошибка 2: игнорирование нагрузки на свинец при расчете общей нагрузки

Long secondary circuits can add substantial burden, particularly at 5 A. Решение: calculate the complete loop resistance at the design temperature. Compare 1 A and 5 A options using the actual cable and compatible relay inputs; cable length alone is not a universal selection threshold.

Ошибка 3: несогласованные ТТ в дифференциальной защите

Different saturation behavior can produce unwanted differential current during an external fault. Решение: use the relay manufacturer’s ratio-compensation, excitation, winding-resistance and stability requirements. Transformer differential schemes may use different primary CT ratios; identical ratios and knee-point voltages are not a universal requirement.

Ошибка 4: Учет остаточного потока в схемах автозакрытия

Remanent flux can change CT saturation during a subsequent fault or reclosing sequence. Решение: assess the specified operating cycle, system time constant and relay requirements. Select suitable remanence or transient performance where required; a blanket 50% ALF increase is not a verified substitute.

Понимание Номинальные характеристики вакуумного выключателя helps establish the switching duty. CT accuracy selection is a separate calculation based on the actual through-fault duty and protection scheme, while CT thermal/dynamic withstand must also cover the clearing duty.

Часто задаваемые вопросы

Что означает 5P20 на заводской табличке трансформатора тока?

5P20 specifies a protection CT with a composite-error limit of 5% at a rated accuracy-limit current of 20 times rated primary current, at rated burden and the specified test conditions. For a 400/5 A CT this test current is 8,000 A. It does not identify an exact saturation threshold or guarantee performance for every transient waveform.

Может ли измерительный ТТ класса 0,5 питать реле защиты?

Do not assume that a Class 0.5 metering core is suitable for protection. Its class establishes metering accuracy under specified conditions, not the fault-current performance required by a relay. Use a core whose declared protection characteristics have been checked against the particular relay scheme.

Когда следует указывать 0,2S вместо стандартного класса 0,2?

Consider 0.2S when accurate measurement is required at low load, especially between 1% and 5% of rated CT current. The required class also depends on the utility or project metering specification. Check the limits at each current test point and the declared burden range; 0.2S does not mean ±0.2% at every current.

Как нагрузка влияет на эффективность работы КТ?

A lower external burden generally increases the effective ALF of a P-class CT, but winding resistance must be included. For mainly resistive burdens, ALFactual ≈ ALFс рейтингом × (Rct + Rrated burden) / (Rct + Ractual burden). Therefore, halving external burden does not generally double ALF. Use manufacturer data for the actual circuit and transient duty.

Что такое напряжение в точке колена и почему оно имеет значение?

Knee-point voltage characterizes the bend in the secondary excitation curve. The IEC convention uses the point at which a 10% voltage increase produces a 50% increase in exciting current. It is particularly relevant when specifying PX-type CTs. Apply the relay manufacturer’s knee-point, excitation-current and winding-resistance requirements; a simple voltage comparison does not establish suitability for every protection scheme.

Чем отличаются стандарты точности КТ IEC и IEEE?

IEC 61869-2 includes metering classes such as 0.2 and 0.5 and protection classes such as 5P, 10P and PX. IEEE C57.13 uses a different set of designations, including voltage-based relaying classes such as C100 and C200. The test conditions and burden definitions differ. Specify the standard required by the project and compare the full ratings rather than treating the class names as direct equivalents.

Какой класс точности подходит для коммутации конденсаторных батарей?

A capacitor bank can need phase overcurrent, earth-fault and sensitive unbalance protection, each with different measurement duties. Select CT ratio, accuracy, burden and transient performance from the bank configuration, expected unbalance level and relay instructions. A universal 5P10 or 0.5 recommendation cannot establish suitability for all capacitor banks.


Для получения поддержки по спецификации ККТ, соответствующей вашим требованиям к распределительным устройствам, свяжитесь с командой инженеров XBRELE по адресу страница технических контактов. Мы предлагаем комплексные решения, сочетающие в себе технология вакуумного прерывателя с правильно согласованными приборными трансформаторами для надежной работы приборов учета и защиты, включая проверки координации реле для трансформаторных фидеров.

Technical references: IEC 61869-2:2012 — inductive current transformers; ABB — calculation of actual accuracy limit factor; ABB — CT requirements for non-directional overcurrent protection; ABB — transformer differential CT requirements. The ABB application notes explain calculation methods; final selection must use the applicable project standard and the selected relay’s current instructions.


Ханна Чжу, директор по маркетингу XBRELE
Ханна

Ханна является администратором и координатором технического контента в XBRELE. Она курирует структуру веб-сайта, документацию по продуктам и контент блога, посвященный распределительным устройствам среднего и высокого напряжения, вакуумным выключателям, контакторам, прерывателям и трансформаторам. Ее основная задача — предоставлять четкую, надежную и удобную для инженеров информацию, чтобы помочь клиентам по всему миру принимать уверенные технические и закупочные решения.

Статей: 189