Benötigen Sie die vollständigen Spezifikationen?
Laden Sie unseren Produktkatalog 2025 herunter, um detaillierte Zeichnungen und technische Parameter aller Schaltanlagenkomponenten zu erhalten.
Katalog anfordern
Laden Sie unseren Produktkatalog 2025 herunter, um detaillierte Zeichnungen und technische Parameter aller Schaltanlagenkomponenten zu erhalten.
Katalog anfordern
Laden Sie unseren Produktkatalog 2025 herunter, um detaillierte Zeichnungen und technische Parameter aller Schaltanlagenkomponenten zu erhalten.
Katalog anfordern

Medium-voltage vacuum contactors operate 10,000–100,000 mechanical cycles over their service life. Unlike circuit breakers that interrupt fault currents occasionally, contactors switch load currents repeatedly—often multiple times daily in motor control, capacitor switching, and frequent start-stop applications.
This repetitive duty creates wear patterns maintenance teams must detect before they cause failures. Contact erosion from repeated arcing, mechanical fatigue in operating mechanisms, and gradual vacuum degradation are inevitable—but predictable. Structured maintenance catches deterioration early, when repairs cost hundreds instead of thousands and downtime measures minutes instead of days.
Most contactor failures don’t announce themselves dramatically. They creep forward through measurable indicators: contact resistance rising 20% above baseline, timing drifting 5 ms outside specification, mechanical play appearing in linkages. These signals, when tracked systematically, predict failures weeks or months in advance.
This checklist provides the specific tests, measurements, and acceptance criteria maintenance engineers need to assess vacuum contactor health efficiently. Whether you’re managing industrial motor circuits requiring vacuum contactors for reliable switching or maintaining capacitor banks in utility substations, these procedures apply across manufacturers and ratings.
Circuit breakers interrupt faults—high current, but infrequent operations (perhaps 5–20 over their lifetime). Vacuum contactors switch loads—moderate current, but thousands of operations per year.
Duty comparison:
| Parameter | Vakuum-Leistungsschalter | Vakuumschütz |
|---|---|---|
| Typical operations/year | 5–20 (fault clearing) | 5,000–50,000 (load switching) |
| Current interrupted | 10–40× rated (fault) | 1–8× rated (inrush/load) |
| Arc energy per operation | Very high | Mäßig |
| Cumulative arc energy | Low (few operations) | High (many operations) |
| Wartungsintervall | 2.000–5.000 Operationen | 5,000–20,000 ops |
This frequent switching accumulates arc energy that erodes contacts, stresses mechanisms, and eventually degrades vacuum integrity. Maintenance prevents these gradual failures from causing unexpected outages.

Maintenance frequency depends on operating duty, environmental conditions, and manufacturer recommendations. Use the more conservative interval when conditions vary.
Interval guidelines:
More accurate than time-based for high-duty applications:
How to track operations:
Perform unscheduled inspection when:
Contact resistance directly indicates contact erosion and surface contamination. As contacts wear, resistance increases—reducing current capacity and increasing I²R heating.
Absolute limits (typical for 12–38 kV contactors):
Relative limits:
Example evaluation:
| Pole | Baseline (new) | Current Reading | Bewertung |
|---|---|---|---|
| A | 80 μΩ | 120 μΩ | Acceptable (+50%, normal wear) |
| B | 85 μΩ | 135 μΩ | Acceptable (+59%, monitor closely) |
| C | 82 μΩ | 210 μΩ | Action required (+156%, approaching service limit) |
Pole C shows excessive wear—plan contact replacement at next maintenance window.

Vacuum interrupter performance depends on maintaining vacuum pressure below 10⁻⁴ Pa (10⁻⁶ Torr). Gradual vacuum degradation over years allows gas molecules to enter, reducing dielectric strength and interrupting capability.
Degraded vacuum doesn’t cause immediate failure—contactors continue switching resistive loads. But fault interruption capability declines, creating risk during inrush currents or abnormal conditions.
Apply AC voltage across open contacts and measure leakage current or observe breakdown.
Ausrüstung:
Procedure:
Acceptance:
Einschränkungen:
Similar to Method 1 but uses lower voltage available from standard Megger or insulation testers.
Procedure:
Vorteile:
Einschränkungen:
Not a direct vacuum test, but contact travel below specification often correlates with vacuum loss (contacts stick together slightly when vacuum fails and internal pressure equalizes).
Baseline travel: Typically 8–12 mm for MV contactors
Action level: <80% of rated travel may indicate vacuum failure
Failed vacuum causes increased contact heating due to reduced interrupting capability and internal arcing.
Procedure:
Indicators of vacuum failure:
Advantage: Non-invasive, can be performed during operation
Limitation: Requires baseline data and trained thermographer
Vacuum interrupters cannot be repaired or re-evacuated in the field. Only option: replacement.
Replacement decision tree:
Vacuum interrupters from qualified manufacturers typically cost $200–$800 depending on voltage and current rating. Replacement is straightforward—most designs allow swapping interrupters without disassembling the entire contactor.
Operating mechanisms contain bearings, linkages, springs, and latches subject to wear, corrosion, and misalignment. Mechanical failures often give warning signs before catastrophic failure.
Check for:
Maßnahme:
Check for:
Maßnahme:
Check for:
Maßnahme:
Contact travel measurement:
Ausrüstung: Dial indicator or travel measuring tool
Procedure:
Typische Werte: 8–12 mm for 12 kV contactors, 10–15 mm for 24 kV
Acceptance:
Timing test:
Ausrüstung: High-speed recorder or relay test set with timing function
Procedure:
Typical closing time: 50–100 ms
Typical opening time: 20–50 ms
Acceptance:

Check:
Common failures:
Test procedure:
Some contactors include arc chutes or barriers around the vacuum interrupter for additional protection.
Inspect for:
Maßnahme:
Operating coils and control circuits fail more frequently than vacuum interrupters in well-maintained systems.
Zweck: Detect shorted turns, insulation breakdown, or coil damage
Procedure:
Acceptance:
Procedure:
Low insulation resistance (<1 MΩ) indicates moisture ingress or insulation damage—dry out or replace coil.
Contactors designed for AC or DC control voltage (110 V, 125 V, 220 V, etc.) are sensitive to under-voltage and over-voltage.
Maßnahme:
Under-voltage (<85%):
Over-voltage (>110%):
Check voltage drop in control wiring—long cable runs or undersized conductors cause excessive drop.
Raw measurements are useless without context. Trending data over time reveals deterioration patterns.
For each maintenance interval, document:
Plot key parameters over time:
Example trend interpretation:
If contact resistance increases from 100 μΩ to 150 μΩ over 20,000 operations, linear extrapolation suggests reaching 250 μΩ service limit at ~50,000 operations—plan replacement before that.
Sample checklist format:
VACUUM CONTACTOR MAINTENANCE RECORD
Equipment ID: VC-101
Location: MCC-3, Bay 5
Manufacturer: XBRELE
Rated voltage: 12 kV
Rated current: 400 A
Application: Motor starter (fan motor)
Date: _______ Operations since last inspection: _______
Ambient temp: _______°C
CONTACT RESISTANCE (μΩ):
Phase A: _______ (Baseline: 85 μΩ)
Phase B: _______ (Baseline: 82 μΩ)
Phase C: _______ (Baseline: 88 μΩ)
TIMING:
Closing time: _______ ms (Spec: 60-80 ms)
Opening time: _______ ms (Spec: 25-35 ms)
CONTACT TRAVEL: _______ mm (Spec: 10 ± 1 mm)
VISUAL INSPECTION:
[ ] Mechanism clean, lubricated
[ ] No visible damage or corrosion
[ ] Auxiliary contacts function correctly
[ ] Interlocks operate properly
[ ] No unusual noise or vibration during test operation
CORRECTIVE ACTIONS TAKEN:
_____________________________________________
NEXT INSPECTION DUE: _________ (Date) or _________ operations
Inspector: __________________ Signature: __________
Keep records for the life of the equipment—trends visible over years reveal patterns not apparent in single inspections.
| Symptom | Mögliche Ursache | Diagnostic Test | Remedy |
|---|---|---|---|
| Won’t close | Low control voltage, coil failure, mechanical binding | Measure coil voltage, check for binding, test coil resistance | Correct voltage supply, free mechanism, replace coil |
| Won’t open | Opening coil failure, mechanical jam, stuck contacts | Manually operate (if safe), test opening coil, check contact resistance | Replace coil, free mechanism, if contacts welded→replace interrupter |
| Contact chatter | Under-voltage, contaminated auxiliary contacts, mechanical resonance | Check coil voltage during operation, inspect auxiliary contacts | Increase voltage, clean contacts, add damping |
| Excessive heating | High contact resistance, overload, poor vacuum | Measure resistance, verify load current, vacuum test | Clean/replace contacts, check load, replace interrupter |
| Timing out of spec | Worn linkage, dried lubricant, spring fatigue | Inspect mechanism, measure timing, check spring condition | Re-lubricate, adjust mechanism, replace worn parts |

Vacuum contactor maintenance involves electrical and mechanical hazards.
Before starting work:
During testing:
After maintenance:
For proper maintenance of the complete VCB and contactor systems, reference XBRELE’s vacuum circuit breaker maintenance guide.
Externe Referenz: IEC 62271-106 — IEC 62271-106 standard for AC contactors
Q1: How often should I measure contact resistance on a vacuum contactor?
A: For high-duty contactors (motor starting, capacitor switching), measure every 5,000 operations or semi-annually, whichever comes first. For low-duty contactors (<1,000 ops/year), annual measurement suffices. Always establish baseline when new and track trends.
Q2: What’s the difference between contact resistance testing for contactors vs. circuit breakers?
A: Technique is identical, but acceptance criteria differ—contactors accumulate more arc energy from frequent operations, so contacts wear faster. Circuit breaker contacts may last 10,000 operations before replacement; contactor contacts often need replacement at 30,000–50,000 operations despite lower per-operation current.
Q3: Can I use a standard multimeter to measure contact resistance?
A: No—multimeters use milliamp-scale test currents that cannot break through surface films on contacts, giving falsely high readings. Use dedicated micro-ohmmeters with 100A+ test current to penetrate surface oxide layers and measure true metal-to-metal resistance.
Q4: How do I know if vacuum has failed if I don’t have high-voltage test equipment?
A: Perform 1,000V DC insulation test across open contacts—good vacuum shows >100 MΩ. Also check for: excessive contact heating during operation (thermal imaging), reduced contact travel (<80% of rated), or unusual arc flash visible through inspection windows. Any of these warrant interrupter replacement.
Q5: What causes vacuum interrupters to lose vacuum over time?
A: Gradual permeation of gas molecules through ceramic-metal seals (helium, hydrogen), micro-cracks from thermal cycling, and internal outgassing from contact erosion. Vacuum typically degrades over 15–25 years, though severe duty or manufacturing defects can accelerate failure.
Q6: Should I lubricate vacuum interrupter contacts?
A: Never—contacts operate in vacuum and should never be lubricated. Only lubricate operating mechanism bearings, linkages, and pivot points external to the vacuum envelope. Use manufacturer-specified lubricant (typically lithium grease rated -40 to +125°C).
Q7: How do I predict when contacts need replacement?
A: Track resistance trend: if increasing linearly from 100 μΩ to 180 μΩ over 20,000 operations, extrapolate to reach 250 μΩ service limit at ~50,000 ops—plan replacement before that. Sudden resistance jump (>20% between intervals) warrants immediate investigation and possible early replacement.