Vacuum Circuit Breakers · Series

ZW32 Vacuum Circuit Breaker Series

ZW32 series outdoor vacuum circuit breakers are widely used on 12kV and 40.5kV distribution networks. The unit integrates vacuum interrupter, solid-insulated embedded pole, operating mechanism and current transformer, offering reliable breaking performance for overhead lines, ring main systems and compact substations.

12kV 40.5kV Outdoor Pole-mounted Vacuum Interruption
Series overview

ZW32 vacuum circuit breaker with integrated pole & operating mechanism

ZW32 series is an outdoor high-voltage vacuum circuit breaker designed for overhead distribution networks. Each unit integrates the vacuum interrupter, solid-insulated embedded pole, operating mechanism and current transformer into a compact body, forming a fully enclosed structure suitable for long-term field operation.

The embedded pole design improves insulation performance and protects the interrupter from moisture, dust and environmental stress. Combined with a stable spring operating mechanism, the breaker provides dependable opening and closing under frequent switching conditions.

The series includes models for both 12kV and 40.5kV, allowing utilities and EPC contractors to deploy a unified breaker platform across different distribution voltage levels. Line-mounted installation reduces on-site work and shortens outage windows during upgrades or replacements.

For a broader look at XBRELE’s outdoor and indoor VCB ranges, please visit the Vacuum Circuit Breaker pillar page .

Technical data & installation dimensions

ZW32-12 & ZW32-40.5 — specifications and outline drawings

Select the voltage level below to view the corresponding product photo, key electrical ratings, and outline & mounting dimensions for engineering design and selection.

ZW32-12 · 12kV
ZW32-40.5 · 40.5kV
ZW32-12 outdoor vacuum circuit breaker 12kV – XBRELE
ZW32-12 outdoor vacuum circuit breaker (12kV), pole-mounted construction with embedded pole.

ZW32-12 technical overview

ZW32-12 is an outdoor vacuum circuit breaker for 12kV overhead distribution networks, typically used as feeder breaker, sectionalizing switch or tie switch on pole-mounted structures.

The breaker adopts a solid-insulated embedded pole and spring operating mechanism, providing reliable switching performance under frequent operations and harsh outdoor environments.

12kV Outdoor Pole-mounted Embedded pole

The table below lists the main electrical ratings for ZW32-12.

Key electrical ratings — ZW32-12

Values according to the ZW32-12 technical parameter sheet.

No.ItemUnitZW32-12
1Rated voltagekV12
2Rated currentA630 / 1250
3Rated frequencyHz50
4Power-frequency withstand voltage (1 min, dry-type, phase-to-phase / across break)kV42 / 48
5Power-frequency withstand voltage (1 min, wet-type)kV34
6Power-frequency withstand voltage (1 min, secondary circuit to ground)kV2
7Lightning impulse withstand voltage (peak, phase-to-phase / across break)kV75 / 85
8Rated short-circuit breaking currentkA20 / 25
9Rated short-circuit closing current (peak)kA50 / 63
10Rated short-term withstand currentkA20 / 25
11Rated peak withstand currentkA50 / 63
12Rated short-circuit breaking current breaking timesoperations30
13Rated short-circuit durations4
14Rated operating voltage / auxiliary circuit voltageVDC/AC110; AC/DC220
15Rated operating sequence—O – 0.3s – CO – 180s – CO
16Over-current trip rated currentA5
17Mechanical lifeoperations10,000
18Cumulative allowable wear of dynamic & static contactsmm3
19Rated current of overcurrent releaseA5
20Current ratio of current transformerA200/5; 400/5; 600/5
21Contact spacingmm9 ± 1
22Contact overtravelmm2.5 ± 0.5
23Average opening speedm/s1.0 ± 0.2
24Average closing speedm/s0.6 ± 0.2
25Opening timems≤ 50
26Closing timems≤ 100
27Closing bounce timems≤ 2
28Different periods of three-pole closing and openingms≤ 2
29DC resistance of each phase loopµΩ≤ 80 (band isolation ≤ 150)

Outline & mounting dimensions — ZW32-12

Outline and mounting dimensions for typical ZW32-12 pole-mounted installation.

ZW32 outline and mounting dimensions – XBRELE
ZW32 outline & mounting dimensions for pole-mounted installation.
ItemSymbolValue (mm)Note
Overall heightH—Overall height of breaker assembly
Overall widthW—Including phase spacing
Mounting hole spacing (horizontal)L1—Base horizontal bolt distance
Mounting hole spacing (vertical)L2—To match cross-arm or steel structure
Mounting hole sizeΦ—Oval or round hole diameter
ZW32-40.5 outdoor vacuum circuit breaker 40.5kV – XBRELE
ZW32-40.5 outdoor vacuum circuit breaker (40.5kV), suitable for overhead lines and substation feeders.

ZW32-40.5 technical overview

ZW32-40.5 is designed for medium-voltage overhead line power grids and 35–40.5kV substations, providing higher insulation level and breaking capacity based on the same embedded pole concept.

The breaker combines a solid-sealed pole with a reliable operating mechanism, offering long mechanical and electrical life with minimal maintenance.

40.5kV Outdoor Pole / structure mounted High insulation level

The table below lists typical electrical ratings for 40.5kV ZW32 configurations.

Key electrical ratings — ZW32-40.5

Typical values for 40.5kV outdoor vacuum circuit breaker applications.

No.ItemUnitZW32-40.5
1Rated voltagekV40.5
2Rated frequencyHz50 / 60
3Rated currentA1250 / 1600 / 2000 / 2500
4Power-frequency withstand voltage (1 min, phase-to-phase / to earth)kV95
5Lightning impulse withstand voltage (peak)kV185
6Rated short-circuit breaking currentkA25 / 31.5
7Rated short-time withstand current (4s)kA25 / 31.5
8Rated short-circuit making current (peak)kA63 / 80
9Mechanical lifeoperations10,000
10Rated operating sequence—O – 0.3s – CO – 180s – CO

Outline & mounting dimensions — ZW32-40.5

Outline and mounting dimensions for typical 40.5kV ZW32 installation.

ZW32-40.5 outline and mounting dimensions – XBRELE
ZW32-40.5 outline & mounting dimensions for medium-voltage overhead line applications.
ItemSymbolValue (mm)Note
Overall heightH—Overall height of 40.5kV breaker
Overall widthW—Including phase spacing
Mounting hole spacing (horizontal)L1—Base horizontal bolt distance
Mounting hole spacing (vertical)L2—To match steel structure or frame
Mounting hole sizeΦ—Oval or round hole diameter
Configuration & options

Protection, control and automation around the ZW32 series

ZW32 outdoor vacuum circuit breakers can be combined with protection relays, CTs/VTs and communication devices to form complete pole-mounted switching and automation solutions for distribution networks.

Protection

Protection & measuring combinations

Build a complete protection scheme around the ZW32 using your preferred relays and instrument transformers.

  • Feeder over-current and earth-fault protection
  • Directional / non-directional protection according to system design
  • Integrated CTs for metering and protection functions
  • Support for recloser curves and sectionalizing logic
Control

Operating & control options

Flexible operating configurations to match manual, local and remote control requirements.

  • Spring operating mechanism with motor charging
  • Local/remote control selector with clear position indication
  • AUX contacts for SCADA status feedback (open/close/ready)
  • Compatible with pole-mounted control cabinets and RTUs
Automation

Distribution automation & communication

When combined with suitable controllers, ZW32 breakers can be used in automated distribution systems and smart grid projects.

  • Support for common protocols via external IEDs (Modbus, IEC 60870-5-104, etc.)
  • Remote open/close and status monitoring through SCADA
  • Fault location, isolation and service restoration (FLISR) schemes
  • Customized wiring and terminal arrangements on request
Manufacturing & quality control

How XBRELE builds reliable ZW32 outdoor vacuum circuit breakers

Behind every ZW32 unit there is a controlled manufacturing flow – from embedded pole casting to routine testing – designed to ensure long-term reliability on harsh outdoor lines.

From embedded pole to finished breaker

XBRELE manufactures the vacuum interrupter pole assemblies, operating mechanism and housing in a coordinated process. Each step is monitored and recorded for traceability of every ZW32 unit.

  • 01

    Vacuum interrupter & pole assembly

    Vacuum interrupters are checked for stroke, over-travel and resistance, then built into the solid pole.

  • 02

    Solid insulation casting & curing

    Epoxy insulation is degassed, poured and cured to form a compact embedded pole resistant to tracking.

  • 03

    Mechanism integration & adjustment

    The spring mechanism is assembled, lubricated and tuned so speeds, timing and bounce meet ZW32 limits.

  • 04

    Final assembly & sealing

    Poles, CTs, terminals and enclosure parts are combined into a sealed outdoor body with anti-corrosion coating.

  • 05

    Routine testing & inspection

    Each breaker passes electrical, mechanical and dielectric tests before packing and shipment.

Electrical & dielectric tests

Routine tests for every ZW32

Electrical routine tests verify insulation level and switching performance.

Insulation & switching verification

  • Power-frequency withstand between phases and to earth
  • Lightning impulse withstand on sample basis
  • Contact resistance check for each main circuit
  • Mechanical operating tests for O / CO sequences

Routine-test records can be supplied with the shipment if required.

Mechanical reliability

  • Type-test verification of 10,000 mechanical operations
  • Check of opening / closing speeds within limits
  • Control of closing bounce time and pole synchronism
  • Environmental checks for lubrication and low-temperature duty

Documentation & traceability

  • Type-test reports and routine-test certificates
  • Factory inspection records with serial number traceability
  • Outline drawings & terminal diagrams in editable format
  • Recommended maintenance guidelines for field crews

FAT / QAP / ITP witness testing can be arranged for utility or EPC projects.

Delivery & project support

Lead time, export packing and engineering support for ZW32 projects

XBRELE supports utilities, EPC contractors and distributors with predictable delivery, export-ready packing and engineering documentation for ZW32 outdoor vacuum circuit breakers at 12 kV and 40.5 kV.

Lead time

Standard & project delivery

Typical delivery times for ZW32 breakers, depending on configuration and quantity.

  • Standard 12 kV / 40.5 kV ZW32: about 15–25 days after order confirmation
  • Projects with mixed ratings or accessories: usually 25–35 days
  • Urgent orders can be discussed case-by-case according to production load
  • Sample units available on request for type checking and approvals
Export packing & logistics

Seaworthy packing & flexible shipment

ZW32 breakers are packed for long-distance sea or land transportation with proper protection.

  • Individual breaker packed in export carton or wooden case with shock protection
  • Moisture-protection and anti-rust treatment for outdoor installation parts
  • Suitable for mixed containers with other XBRELE switchgear and transformers
  • FOB Ningbo / Shanghai, CIF or other Incoterms can be supported according to the contract
Project support

Documentation & engineering assistance

XBRELE provides the documentation and technical support needed for network planning and project approval.

  • Outline drawings, terminal diagrams and foundation details for ZW32
  • Type-test reports, routine-test certificates and factory inspection records
  • QAP / ITP preparation and FAT witness testing for utility & EPC projects
  • Support with selection of ratings and configuration for specific overhead line schemes
FAQ · ZW32 Series

Frequently asked questions about ZW32 outdoor vacuum circuit breakers

Below are some typical questions from utilities, EPC contractors and distributors when selecting XBRELE ZW32 vacuum circuit breakers for 12kV and 40.5kV overhead lines.

What is the difference between ZW32-12 and ZW32-40.5? +
ZW32-12 is designed for 12 kV distribution networks, while ZW32-40.5 supports 40.5 kV overhead systems with higher insulation and short-circuit ratings. Both use embedded poles and vacuum interrupters, but the 40.5 kV version features higher Basic Insulation Level (BIL), higher breaking capacity and larger overall dimensions to meet medium-voltage requirements.
Does the ZW32 series support automatic reclosing functions? +
Yes. XBRELE supplies ZW32 automatic recloser configurations with matched controller, auxiliary CTs and wiring. The controller can be programmed with reclosing sequences, protection curves and remote communication. Standard ZW32 breakers can also be combined with third-party feeder automation controllers if required by the project.
Can ZW32 be installed on concrete poles or steel cross-arms? +
Yes. The ZW32 mounting base allows installation on steel cross-arms, concrete poles and lattice structures. Designers can refer to the outline & mounting dimensions (H, W, L1, L2 and mounting hole size) provided in this page to match the support structure and hardware.
What routine tests are performed before shipment? +
Every ZW32 breaker is 100% routine-tested at the factory. Tests typically include power-frequency withstand between phases and to earth, lightning impulse withstand on a sample basis, contact resistance measurement of each main circuit, mechanical operating tests for O / CO sequences, and visual checks of sealing, wiring and markings. Routine-test records can be supplied with the shipment when required.
Can XBRELE provide drawings and documentation for project approval? +
Yes. XBRELE can support customers with outline drawings, terminal diagrams, type-test certificates, routine-test reports and factory inspection records. For utility and EPC projects, we can also provide QAP/ITP documents and support FAT witness testing according to the project specification.
What is the typical delivery time for ZW32 outdoor vacuum circuit breakers? +
For standard 12 kV and 40.5 kV ZW32 configurations, the typical lead time is about 15–25 days after order confirmation. For customized breakers with special accessories, controllers or testing requirements, lead time is normally 25–35 days depending on quantity and project scope.
Which international standards does the ZW32 series comply with? +
ZW32 outdoor vacuum circuit breakers are designed and type tested with reference to the IEC 62271 series for high-voltage switchgear, in particular IEC 62271-100 for high-voltage AC circuit-breakers. For more information about the scope and latest edition of IEC 62271-100, you can refer to the official IEC webstore page IEC 62271-100 .