Request a Quote for High-Voltage Components&Equipment

Tell us your requirements — rated voltage, model, quantity, and destination — and our XBR Electric team will prepare a detailed quotation within 24 hours.
Contact Form Demo
Capacitive voltage sensor operating principle showing electric field coupling to energized MV cable conductor with LED indication

VPIS / Capacitive Sensors Basics: Selection, Wiring, False Indication Causes

Switchgear safety depends on knowing whether circuits are energized before maintenance work begins. Visual inspection cannot distinguish between 12 kV live and dead—workers rely on voltage presence indication systems (VPIS) to provide that confirmation. A single false indication can result in arc flash injury or fatality.

Capacitive sensors form the heart of most modern VPIS installations. Unlike potential transformers requiring insulation coordination and primary circuit modification, capacitive sensors mount externally on cables or busbars, detecting electric fields without galvanic connection. When properly selected and installed, they provide reliable voltage indication for decades. When installed incorrectly, they produce false positives, false negatives, or intermittent operation that erodes operator trust.

This guide explains how capacitive voltage sensors work, how to select appropriate models for different MV applications, proper wiring practices that prevent false indications, and troubleshooting techniques for the most common failure modes.


What VPIS and Capacitive Sensors Do in MV Switchgear

Voltage Presence Indication Systems (VPIS) provide visual confirmation that circuits are energized or de-energized. They serve three critical safety functions:

Lockout/Tagout verification — Before workers approach equipment, VPIS confirms that voltage has been removed
Earthing switch permissive — Interlocks prevent earthing switch closure unless VPIS indicates voltage absent
Three-phase verification — Detects single-phasing or blown fuse conditions where one or two phases remain energized

Early VPIS implementations used voltage transformers (VTs) or potential transformers (PTs) connected directly to the primary circuit. These provide accurate voltage measurement but require careful insulation coordination, add cost, and occupy space in compact switchgear. Capacitive sensors emerged as a simpler alternative: small disc-shaped devices that mount on cable terminations, busbar chambers, or epoxy insulation surfaces, detecting voltage presence through electric field coupling.

Capacitive sensors don’t measure voltage magnitude—they detect field presence above a threshold (typically 15–25% of rated voltage). A green LED indicates voltage present; no illumination (or red LED on some models) indicates voltage absent. More sophisticated systems integrate three single-phase sensors with a central display unit showing per-phase status and alarm outputs for control circuit integration.

[SAFETY NOTE: Capacitive sensors indicate voltage presence but do NOT prove circuits are safe to touch—always verify with properly rated test equipment before working on de-energized equipment]

The vacuum circuit breaker applications discussed at https://xbrele.com/what-is-vacuum-circuit-breaker-working-principle/ frequently incorporate VPIS at cable terminations and busbar chambers to enhance personnel safety during maintenance and switching operations.


How Capacitive Sensors Work: Electric Field Coupling Fundamentals

Capacitive sensors operate on the principle that energized conductors create electric fields extending into surrounding space. The sensor becomes one plate of a capacitor, with the energized conductor as the other plate and air/insulation as the dielectric.

Physical Operating Principle

When an MV cable or busbar is energized at 12 kV, an AC electric field radiates outward. A metallic sensing element placed near the conductor couples to this field capacitively. Even though no galvanic (direct electrical) connection exists, a tiny displacement current flows:

I = C × dV/dt

Where:

  • I = displacement current (typically nanoamperes to microamperes)
  • C = capacitance between sensor and conductor (typically 0.1–10 pF)
  • dV/dt = rate of voltage change (proportional to frequency and amplitude)

For a 50 Hz, 12 kV (phase-to-ground = ~7 kV RMS) system:

dV/dt = 2π × 50 × 7000 = 2.2 MV/s

With 1 pF coupling capacitance:

I = 1 pF × 2.2 MV/s = 2.2 μA

This microampere-level displacement current charges a small internal capacitor in the sensor’s electronics. When the accumulated charge exceeds a threshold, the sensor’s LED activates, indicating voltage presence. If the primary circuit voltage drops below ~15–25% of rated value, insufficient displacement current flows to maintain the indication.

Sensor Construction

A typical capacitive sensor contains:

Sensing electrode — Metallic disc or plate positioned close to the primary conductor
Electronics module — Amplifier, threshold detector, and LED driver powered by the sensed field itself or by harvested energy from the electric field
LED indicator — Green (voltage present) or red/none (voltage absent)
Mounting hardware — Adhesive pad, screw mount, or snap-on clip depending on application

Advanced models add:

  • Auxiliary contacts for remote alarm or interlock circuits
  • Dual-LED (green + red) for positive indication in both states
  • Self-test circuitry that flashes LED pattern to prove sensor functionality
  • Communication interface (Modbus, Profibus) for SCADA integration
Sensor TypePower SourceTypical Application
Self-powered (field harvesting)Energy extracted from sensed electric fieldCable terminations, outdoor switchgear
Battery-poweredInternal lithium cell (5–10 year life)Low-field applications, retrofit installations
Externally powered24 VDC or 110 VDC auxiliary supplySystems requiring auxiliary contacts or SCADA integration

Selecting the Right Capacitive Sensor: Application Considerations

Capacitive sensor selection depends on installation location, voltage level, environmental conditions, and system integration requirements. Incorrect selection leads to unreliable operation or complete failure.

Voltage Rating and Sensitivity

Sensors must match the system voltage class:

System Voltage (kV)Sensor Pickup ThresholdDropout ThresholdTypical Model Rating
3.6 / 7.2 kV0.9–1.8 kV0.6–1.2 kV3.6 kV class
12 / 13.8 kV1.8–3.5 kV1.2–2.3 kV12 kV class
24 / 27 kV3.6–6.8 kV2.4–4.5 kV24 kV class
36 / 40.5 kV5.4–10 kV3.6–6.8 kV36 kV class

Pickup threshold — Voltage at which sensor reliably indicates “voltage present”
Dropout threshold — Voltage below which sensor indicates “voltage absent”

Hysteresis between pickup and dropout prevents LED flickering when voltage hovers near threshold. Typical hysteresis is 20–40% of pickup value.

Critical selection point: Sensors designed for 12 kV systems may fail to operate reliably on 7.2 kV systems due to insufficient field strength. Conversely, 7.2 kV sensors may indicate “voltage present” on 12 kV systems even when capacitive coupling from adjacent energized phases creates stray fields—leading to false positives.

Installation Location: Cable vs Busbar vs Epoxy Parts

Cable terminations (most common):

  • Sensors mount directly on cable insulation shield or stress cone
  • Strong electric field concentration provides reliable signal
  • Shield continuity must be maintained (sensor does not interrupt shield grounding)
  • Outdoor cable terminations require weatherproof sensor enclosures

Busbar chambers:

  • Sensors mount on chamber walls or directly on busbar insulation
  • Field strength varies with distance to busbar—closer mounting improves reliability
  • Metal chamber walls can shield field—sensor placement critical
  • Three-phase configurations require careful phase identification

Epoxy insulated bushings/parts:

  • Sensors mount on epoxy surface near internal conductor
  • Field uniformity in epoxy provides stable sensing
  • Epoxy surface must be clean (no contamination reducing field coupling)
  • Some epoxy parts include factory-molded sensor pockets
Cross-section diagram showing capacitive sensor mounting on cable termination, busbar chamber, and epoxy bushing with electric field lines
Figure 1. Capacitive sensor mounting locations: cable termination provides optimal field strength, busbar chamber requires close proximity, epoxy bushing offers stable field uniformity.

[Application Note: Sensor Placement for Maximum Reliability]

  • Mount sensors within the equipotential grounding zone—never on isolated metal that could float to dangerous voltage
  • Position sensors where they couple to the intended phase conductor only—avoid locations sensing multiple phases simultaneously
  • Verify that sensor LED is visible from normal operator position without requiring panel opening
  • On cable terminations, mount sensors on the straight section below the stress cone, not on the flared portion

Environmental Ratings: Indoor vs Outdoor vs Harsh Conditions

Capacitive sensors must withstand the installation environment:

EnvironmentRequired RatingsTypical Challenges
Indoor switchgear (clean)IP40, -5°C to +40°CMinimal environmental stress
Indoor industrial (dusty)IP54, -10°C to +50°CDust accumulation on sensor face can reduce coupling
Outdoor distribution (temperate)IP65, -40°C to +70°C, UV resistanceCondensation, temperature cycling, UV degradation
Outdoor coastal (corrosive)IP66/IP67, -40°C to +85°C, salt fog testedCorrosion of terminals, moisture ingress
Mining/heavy industrialIP67, vibration rated, -25°C to +60°CMechanical shock, dust, vibration affecting LED visibility

Temperature extremes affect both electronics reliability and battery life (for battery-powered models). Sensors rated only to +40°C may fail prematurely in outdoor switchgear experiencing direct solar heating—internal temperatures can exceed +70°C.

Auxiliary Contacts and Alarm Integration

Basic sensors provide local visual indication only. Applications requiring remote monitoring or electrical interlocks need sensors with auxiliary contacts:

SPDT relay output:

  • “a” contact closes when voltage present
  • “b” contact closes when voltage absent
  • Contact rating typically 1–5 A at 250 VAC or 30 VDC

Common uses:

  • Earthing switch interlock (prevents earthing switch closure if any sensor detects voltage)
  • Control room alarm panel (annunciates voltage present/absent status)
  • SCADA integration (sensor status transmitted to central monitoring)

Sensors with contacts require external power (cannot be self-powered from electric field alone). Connection requires additional wiring—typically 3–4 wires for power supply plus 2–3 wires per contact.


Proper Wiring Practices: Preventing False Indications

Capacitive sensors are simple devices, yet improper wiring causes the majority of field failures and false indications. Most issues trace to grounding errors, electromagnetic interference, or contact wiring mistakes.

Grounding and Shielding

Capacitive sensors must be grounded to the switchgear ground bus to establish a reference potential:

Correct grounding practice:

  • Connect sensor housing/mounting bracket to ground bus via dedicated ground wire (minimum 2.5 mm² / 14 AWG)
  • Ground connection should be low impedance (<0.1 Ω)
  • For sensors on cable terminations, ensure cable shield continuity is maintained through sensor mounting
  • Do NOT ground sensor to painted surfaces or through mounting screws alone—paint creates high-resistance connection

Cable shielding (for sensors with auxiliary contacts):

  • Use shielded cable for wiring between sensor and display unit/alarm panel
  • Shield connected to ground at sensor end only (avoid ground loops)
  • Minimum shield coverage 80% (preferably 90%+)
  • Route sensor cables separately from high-current power cables to reduce EMI pickup
Wiring ErrorConsequenceCorrect Practice
Sensor not groundedErratic operation, false positives from stray fieldsDedicated ground wire to switchgear ground bus
Shield grounded at both endsGround loop current causes false indicationsGround shield at sensor end only
Sensor cable routed with power cablesEMI-induced false indicationsRoute sensor cables in separate conduit/tray
Sensor mounted on painted surfaceIntermittent operation due to poor ground contactRemove paint at mounting point or use grounding strap

Auxiliary Contact Wiring Configuration

Sensors with relay outputs require careful attention to contact wiring polarity and configuration:

For earthing switch interlock:

  • Use sensor “b” contact (closed when voltage absent)
  • Wire “b” contact in series with earthing switch close circuit
  • If ANY of three sensors (R, Y, B phases) detects voltage, corresponding “b” contact opens, blocking earthing switch closure
  • Test by simulating sensor failure (disconnect power)—should block earthing switch

For alarm indication:

  • “a” contact (closed when voltage present) drives “voltage present” alarm
  • “b” contact (closed when voltage absent) drives “voltage absent” alarm
  • Alarm circuit should annunciate unexpected voltage (e.g., voltage present when breaker open)

Critical: Verify contact type (NO vs NC) matches circuit requirement. Some manufacturers label contacts using “working” vs “resting” terminology instead of “a”/“b”—consult manufacturer documentation to avoid wiring errors.

Three-phase VPIS wiring diagram showing auxiliary contacts wired to earthing switch interlock and alarm panel
Figure 2. Three-phase capacitive sensor system with auxiliary contacts: series “b” contacts interlock earthing switch (permits closure only when all phases de-energized), parallel “a” contacts drive voltage present alarm.

Power Supply Requirements (for Active Sensors)

Self-powered sensors harvest energy from the sensed electric field—no external wiring required. Battery-powered and externally-powered sensors require proper supply connection:

Battery-powered:

  • Internal lithium cell (typically CR2032 or similar)
  • 5–10 year battery life under normal conditions
  • Low-battery indication (LED flash pattern or separate indicator)
  • Battery replacement requires sensor disassembly—schedule during maintenance outages

Externally-powered:

  • Supply voltage typically 24 VDC or 110 VDC from station battery/control supply
  • Current consumption 5–20 mA per sensor
  • Supply polarity must be correct (reverse polarity can damage electronics)
  • Fused supply recommended (1 A fuse protects multiple sensors)

Power supply wiring:

  • Use minimum 1.0 mm² (18 AWG) for supply wiring
  • Observe polarity markings (red = +, black = -)
  • For long cable runs (>50 m), increase wire size to compensate for voltage drop
  • Verify supply voltage at sensor terminals (should be within ±10% of rated voltage)

Common False Indication Causes and Troubleshooting

False positives (indicating voltage present when circuit is dead) and false negatives (failing to indicate voltage when circuit is energized) undermine operator confidence in VPIS. Understanding root causes enables effective troubleshooting.

False Positive: Indicating Voltage When Circuit De-energized

Cause 1: Capacitive coupling from adjacent energized phase

  • In three-phase systems, electric fields from energized phases can couple to de-energized phase sensors
  • Particularly common in compact switchgear with close phase spacing
  • Diagnosis: De-energize all three phases—false indication should disappear

Solution: Shield sensor from adjacent phase fields using grounded metal barriers, or relocate sensor to position with less cross-coupling. Some installations require phase-selective sensors with directional sensing elements.

Cause 2: Induced voltage on long de-energized cable

  • Long cables (>100 m) can develop induced voltage from parallel energized cables
  • Induced voltage sufficient to trigger sensor pickup threshold (~2 kV)
  • Diagnosis: Measure voltage with high-impedance voltmeter—typically see 1–5 kV induced voltage

Solution: Ground the de-energized cable through temporary earthing before relying on VPIS indication. Alternatively, use sensors with higher pickup threshold or dual-confirmation (voltage measurement + field sensing).

Cause 3: Sensor electronics failure

  • LED remains illuminated regardless of circuit status
  • Self-test function (if available) indicates fault
  • Diagnosis: Disconnect sensor from field source—LED should extinguish

Solution: Replace faulty sensor. Check for environmental damage (moisture ingress, overheating) that may have caused failure.

False Negative: Failing to Indicate Voltage When Circuit Energized

Cause 1: Sensor positioned too far from conductor

  • Electric field strength decreases rapidly with distance (inverse square law for point sources)
  • Sensor beyond effective range (typically >50 mm for 12 kV systems)
  • Diagnosis: Temporarily reposition sensor closer to conductor—indication should appear

Solution: Remount sensor in proper location. For retrofit installations where mounting position is constrained, consider higher-sensitivity sensor model.

Cause 2: Shielding by grounded metal

  • Grounded metal chamber walls or mounting brackets shield electric field
  • Sensor cannot couple to conductor field
  • Diagnosis: Remove/reposition shielding metal (if safe to do so)—indication should appear

Solution: Relocate sensor to position outside shielded zone, or install busbar-mounted sensor that bypasses chamber shielding.

Cause 3: Contamination on epoxy surface

  • Conductive contamination (dust, moisture, carbon tracking) on epoxy insulation surface
  • Contamination provides alternative path for displacement current, reducing sensor signal
  • Diagnosis: Clean epoxy surface with isopropyl alcohol—indication may return

Solution: Regular cleaning of sensor mounting surfaces. For outdoor installations, verify IP rating adequate to prevent moisture ingress.

Cause 4: Low system voltage

  • System voltage below sensor pickup threshold (e.g., 7.2 kV sensor on 3.6 kV system)
  • Transformer tap setting reduced voltage below expected level
  • Diagnosis: Measure actual system voltage—may be significantly below nameplate rating

Solution: Replace sensor with lower-voltage-rated model appropriate for actual operating voltage.

Cause 5: Battery depletion (battery-powered sensors)

  • Internal battery exhausted (typical life 5–10 years)
  • Low-battery warning may have been missed
  • Diagnosis: Check battery voltage (requires sensor disassembly)

Solution: Replace battery or replace entire sensor if battery non-serviceable.

SymptomMost Likely CauseQuick Verification Test
All three phases indicate voltage when one de-energizedCross-phase couplingDe-energize all phases—indications should disappear
Intermittent indication (flickering LED)Marginal field strength or poor ground connectionCheck sensor mounting tightness and ground wire continuity
One phase never indicates even when energizedSensor failure or positioning errorSwap sensors between phases to isolate faulty unit
Sudden failure of all sensors simultaneouslyPower supply failure (externally-powered sensors)Verify control supply voltage at sensor terminals
VPIS troubleshooting flowchart showing decision tree for false positive and false negative voltage indications with corrective actions
Figure 3. Systematic troubleshooting flowchart for capacitive sensor false indications, covering cross-phase coupling, induced voltage, positioning errors, shielding, and contamination issues.

Installation Best Practices: Ensuring Long-Term Reliability

Proper installation extends sensor life and maintains reliable operation for years:

Pre-Installation Checks

  • Verify sensor voltage rating matches system voltage class
  • Confirm environmental rating (IP code, temperature range) adequate for installation location
  • Check that sensor model includes required features (auxiliary contacts, self-test, etc.)
  • Inspect mounting surface condition—clean, dry, free of contamination

Mounting Procedure

  1. Clean mounting surface with isopropyl alcohol (for epoxy/cable insulation) or wire brush (for metal surfaces)
  2. Remove paint or coating at mounting point to ensure electrical continuity for grounding
  3. Apply sensor according to manufacturer instructions:
    • Adhesive-mount: Ensure full contact across sensor base, apply pressure for 30 seconds
    • Screw-mount: Torque to specified value (typically 2–4 Nm), do not overtighten
    • Clip-mount: Verify positive engagement, clip should not be removable by hand
  4. Connect ground wire (minimum 2.5 mm²) from sensor housing to switchgear ground bus
  5. For sensors with auxiliary contacts/power supply, connect wiring per manufacturer diagram (observe polarity)

Commissioning Verification

  • Energize circuit and verify LED illuminates (green for voltage present)
  • De-energize circuit and verify LED extinguishes or changes to red (voltage absent)
  • If auxiliary contacts provided, measure contact state and verify correct operation (NO closes on energization, NC opens on energization)
  • Operate circuit breaker through several open-close cycles—sensor should track circuit status reliably
  • Simulate adjacent phase energization (if possible) to check for false positives from cross-coupling
  • Verify LED visible from normal operator viewing position
Step-by-step installation sequence showing capacitive sensor mounting on cable termination with surface preparation, placement, grounding, and verification
Figure 4. Proper installation sequence for capacitive voltage sensor on cable termination: clean surface, position sensor, connect ground wire, verify operation.

Maintenance and Testing Intervals

Capacitive sensors are largely maintenance-free but require periodic verification:

Annual inspection:

  • Visual check for physical damage (cracked lens, corrosion, mounting looseness)
  • Verify LED illumination corresponds to actual circuit status
  • Check auxiliary contact operation (if applicable)

5-year detailed test:

  • Clean sensor mounting surface and surrounding insulation
  • Verify ground connection continuity (<0.1 Ω)
  • Measure auxiliary contact resistance (should be <50 mΩ when closed)
  • For battery-powered units, check low-battery indication and replace battery if needed

10-year replacement consideration:

  • LED degradation (reduced brightness) can affect daytime visibility
  • Electronics aging may shift threshold voltage
  • Consider replacement at major maintenance outages even if sensor still functional

After fault events:

  • Inspect sensors on faulted circuit and adjacent circuits
  • Verify that fault current or transient overvoltage did not damage sensor electronics
  • Test operation through energize-de-energize cycle

Advanced VPIS Configurations: Three-Phase Systems and SCADA Integration

Basic installations use independent sensors per phase. Advanced systems integrate three sensors with centralized logic and remote monitoring.

Three-Phase Display Units

Centralized display units consolidate three single-phase sensors:

Features:

  • Three-LED array showing per-phase status (R-Y-B or A-B-C)
  • Logic processing: Alarm if phases disagree (one indicates voltage, others don’t)
  • Single auxiliary contact output: “All phases dead” permissive for earthing switch interlock
  • Redundant power supply inputs

Wiring:

  • Each sensor connects to display unit via 2–4 wire cable (power + signal)
  • Display unit mounted on switchgear door or panel for operator visibility
  • Auxiliary contacts wire to earthing switch control, alarms, or SCADA

Advantages over independent sensors:

  • Single point of operator reference
  • Enhanced diagnostic capability (single-phase loss detection)
  • Easier integration with protection and control systems

SCADA and IED Integration

Modern switchgear integrates VPIS with intelligent electronic devices (IEDs) and SCADA:

Communication protocols:

  • Modbus RTU/TCP (most common)
  • Profibus DP
  • DNP3 (utility applications)
  • IEC 61850 (for substations with process bus)

Data points transmitted:

  • Per-phase voltage presence status (binary: present/absent)
  • Sensor health/self-test status (binary: healthy/fault)
  • Battery status (for battery-powered units)
  • Time-stamped event logging (voltage transition events)

Applications:

  • Remote confirmation of circuit de-energization before issuing work permits
  • Automatic alarm generation on unexpected voltage (security detection)
  • Coordination with automated switching sequences
  • Long-term reliability trending (sensor failure prediction)
Three-phase VPIS system architecture showing central display unit with auxiliary contacts to earthing switch interlock and Modbus connection to SCADA
Figure 5. Advanced three-phase VPIS architecture: centralized display unit processes three sensor inputs, provides earthing switch permissive, and integrates with SCADA via Modbus for remote monitoring.

Choosing a Capacitive Sensor Supplier

Sensor quality varies significantly among manufacturers. When evaluating suppliers:

Verify type test certification: Sensors should have independent test reports confirming voltage threshold, temperature performance, and EMC immunity per IEC 61243-5 (live working—voltage detecting devices).

Check application experience: Has the supplier provided sensors for similar applications (same voltage class, environment, mounting type)?

Evaluate technical support: Can the supplier assist with sensor placement optimization and troubleshooting false indication issues?

Assess spare parts availability: Sensors may remain in service 20+ years—ensure replacement units and batteries remain available.

Review warranty terms: Minimum 2-year warranty standard; some manufacturers offer 5 years for premium models.

XBRELE provides capacitive voltage sensors engineered for reliable operation in MV switchgear applications from 3.6 kV through 40.5 kV. Our sensors feature dual-LED indication (green + red), self-test functionality, and auxiliary contacts for interlock integration. Complete installation documentation, commissioning support, and spare parts availability ensure long-term system reliability. Explore our full range of switchgear components and accessories at https://xbrele.com/vacuum-circuit-breaker-manufacturer/.


Key Takeaways

  • Capacitive sensors detect voltage presence through electric field coupling without galvanic connection to primary circuits
  • Sensor selection must match system voltage, installation location (cable vs busbar), and environmental conditions
  • Proper grounding and shielding prevent false indications caused by cross-phase coupling and EMI
  • False positives often result from adjacent phase coupling or induced voltage; false negatives from positioning errors or shielding
  • Regular inspection and testing maintain long-term reliability, with battery replacement required every 5–10 years for battery-powered units
  • Advanced three-phase systems with SCADA integration enhance safety and enable remote monitoring

Frequently Asked Questions

Q1: Do capacitive sensors require physical connection to the high-voltage conductor?
A: No. Capacitive sensors operate through electric field coupling and require no galvanic (direct electrical) connection to the MV conductor. They mount externally on cable insulation, busbar chambers, or epoxy surfaces, sensing the electric field radiated by energized conductors.

Q2: Can capacitive sensors measure the actual voltage value?
A: No. Capacitive sensors detect voltage presence/absence only, not magnitude. They indicate whether voltage exceeds a threshold (typically 15–25% of rated voltage) but do not provide numeric voltage readings. For voltage measurement, use voltage transformers or electronic voltage transducers.

Q3: What causes capacitive sensors to indicate voltage present when the circuit is actually de-energized?
A: Common causes include capacitive coupling from adjacent energized phases, induced voltage on long de-energized cables running parallel to energized cables, and sensor electronics failure. Troubleshooting involves verifying all phases are de-energized, checking for induced voltage with a high-impedance voltmeter, and testing sensor function.

Q4: How long do battery-powered capacitive sensors last before battery replacement?
A: Battery life typically ranges from 5 to 10 years depending on sensor model, ambient temperature, and LED activation frequency. Most battery-powered sensors provide low-battery warning (LED flash pattern) 6–12 months before complete battery depletion.

Q5: Can I install a 12 kV-rated sensor on a 24 kV system?
A: No. Sensors must be rated for the system voltage class. Installing a lower-voltage-rated sensor on a higher-voltage system risks sensor damage and unreliable operation. Electric field strength at higher voltages may saturate sensor electronics or exceed component ratings.

Q6: Why does my sensor work reliably in winter but fail to indicate in summer?
A: Temperature affects sensor electronics and battery performance. If the sensor is rated only to +40°C but experiences +70°C in summer (due to solar heating or proximity to transformers), electronics may malfunction or battery voltage may drop below operating threshold. Verify sensor temperature rating exceeds maximum expected ambient temperature by at least 10°C.

Q7: How close must a capacitive sensor be positioned to the conductor for reliable operation?
A: Effective sensing distance depends on voltage level and sensor design. Typical ranges: 3.6–12 kV systems require sensor within 50 mm of conductor; 24–36 kV systems may operate reliably up to 100 mm distance. Consult manufacturer specifications for specific models. Field strength decreases rapidly with distance—doubling distance reduces signal strength by 75% or more.


Further Reading

Hannah Zhu marketing director of XBRELE
Hannah

Hannah is the Administrator and Technical Content Coordinator at XBRELE. She oversees website structure, product documentation, and blog content across MV/HV switchgear, vacuum breakers, contactors, interrupters, and transformers. Her focus is delivering clear, reliable, and engineer-friendly information to support global customers in making confident technical and procurement decisions.

Articles: 61